- 05000309/LER-1982-001-03, /03L-0:on 811223,cracks Found in 0.5-inch Lines During Maint on Leaking Ball Valve.Caused by Frozen Lines Due to Failure of Heat Tracing on Recirculation Flow Transmitter Lines.Valve Parts & Heat Tracing Repaired + (ML20040C704)
- 05000321/LER-1981-143-03, /03L-0:on 811230,LPCI Reactor Level Switch, 1B21-N031A,contact on Switch 2,failed to Actuate at Tech Spec Levels.Caused by Bad Contact on Switch 2.Switch Replaced,Recalibr & Returned to Svc + (ML20040C705)
- ML20040C706 + (ML20040C706)
- ML20040C708 + (ML20040C708)
- ML20040C709 + (ML20040C709)
- 05000327/LER-1981-157, Forwards LER 81-157/03L-0 + (ML20040C710)
- 05000278/LER-1981-021-03, /03L-0:on 811211,D Core Spray Pump Failed to Start During Surveillance Test Due to Failure of Pump Breaker to Close.Cause Not Determined.Failed Breaker Replaced & Checked Daily for 2 Wks to Verify Core Spray Sys Operability + (ML20040C712)
- ML20040C713 + (ML20040C713)
- 05000366/LER-1982-001, Forwards LER 82-001/03L-0 + (ML20040C714)
- ML20040C716 + (ML20040C716)
- ML20040C717 + (ML20040C717)
- ML20040C718 + (ML20040C718)
- ML20040C719 + (ML20040C719)
- 05000366/LER-1982-001-03, /03L-0:on 820101,low Pressure Alarm Received on Control Rod Drive Line Hydraulic Control Unit 26-47 Due to Switch Being Out of Tolerance.Caused by Setpoint Drift. Switch Recalibr & Returned to Svc + (ML20040C720)
- ML20040C721 + (ML20040C721)
- 05000327/LER-1981-157-03, /03L-0:on 811222,pressurizer Level Transmitter 1-LT-68-335 Declared Inoperable Due to Failure to Meet Channel Check Requirements.Caused by Accumulation of Gases in Condensate Reservoirs & Sensor Bellows.Gases Vented + (ML20040C722)
- IR 05000320/1981022 + (ML20040C725)
- 05000324/LER-1981-137, Forwards LER 81-137/03L-0 + (ML20040C726)
- ML20040C728 + (ML20040C728)
- 05000327/LER-1981-151, Forwards LER 81-151/03L-0 + (ML20040C732)
- 05000272/LER-1981-121-03, /03L-0:on 811228,svc Water Leak Discovered in Containment Fan Coil Spool Piece Between Valves 125W57 & 125W58 in 78-ft Evaluation North Penetration Area.Cause Not Stated.Spool Will Be Changed to Stainless Steel + (ML20040C734)
- 05000324/LER-1981-137-03, /03L-0:on 811218,during Scram Recovery,Reactor Core Isolation Cooling Sys Turbine Tripped & Trip/Throttle Valve 2-E51-MOV-V8 Failed to Reset.Caused by Electrical Shorting to Ground of MOV-V8 Solenoid Control Lead + (ML20040C735)
- 05000260/LER-1981-065, Forwards LER 81-065/03L-0 + (ML20040C736)
- 05000327/LER-1981-151-03, /03L-0:on 811221,w/unit in Mode 1,one Containment Sump Level Transmitter Declared Inoperable Due to Erratic High Readings.Caused by Instrument Drift.Instrument Recalibr + (ML20040C738)
- ML20040C739 + (ML20040C739)
- 05000335/LER-1981-057, Forwards LER 81-057/03L-0 + (ML20040C741)
- 05000366/LER-1981-119, Forwards LER 81-119/03L-0 + (ML20040C743)
- ML20040C745 + (ML20040C745)
- 05000366/LER-1981-126, Forwards LER 81-126/03L-0 + (ML20040C746)
- ML20040C748 + (ML20040C748)
- ML20040C751 + (ML20040C751)
- 05000260/LER-1981-065-03, /03L-0:on 811211,HPCI Suppression Chamber High Level Switches Discovered to Be Set 8 Inches Above Normal Level.Caused by Change to Tech Specs Not Being Reflected in Table 3.2.B.Switches Physically Lowered + (ML20040C752)
- 05000335/LER-1981-057-03, /03L-0:on 811106,NRC Inspector Noticed Grease on Fitting Used to Addl Fluid to Hydraulic Snubber.Eight Snubbers in Component Cooling Sys Contaminated.Caused by Improper Lubrication.Snubbers Rebuilt + (ML20040C753)
- ML20040C754 + (ML20040C754)
- ML20040C755 + (ML20040C755)
- ML20040C757 + (ML20040C757)
- ML20040C758 + (ML20040C758)
- 05000366/LER-1981-126-03, /03L-0:on 811215,during steady-state Operation Analyzer 2T49-B001B Found Inoperative.Caused by Component Failure.Power Supply Filter Capacitor Replaced & Tested Satisfactorily + (ML20040C759)
- 05000366/LER-1981-119-03, /03L-0:on 811207,main Steam Line High Radiation Instrument 2D1-K603D,hi Hi Trip Was Found to Actuate at 4850 M/H.Caused by Setpoint Drift.Switch Recalibr & Successfully Functionally Tested Per HNP-2-3005 + (ML20040C760)
- ML20040C761 + (ML20040C761)
- ML20040C764 + (ML20040C764)
- ML20040C765 + (ML20040C765)
- 05000366/LER-1981-130, Forwards LER 81-130/03L-0 + (ML20040C767)
- ML20040C769 + (ML20040C769)
- ML20040C770 + (ML20040C770)
- 05000366/LER-1981-130-03, /03L-0:on 811217,while Making Power Changes from 2352 Mwt to 2111 Mwt,Low Pressure Alarms Were Received on CRD Hydraulic Control Units H26-47 & H46-15.Switches Found Out of Tolerance.Caused by Setpoint Drift.Switches Recalib + (ML20040C771)
- 1CAN018202, Informs That Addl Info Deemed Not Required for TMI Action Item II.K.2.16 (Reactor Coolant Pump Seal Damage) & 800523 Response + (ML20040C772)