- 05000220/LER-1981-048, Forwards LER 81-048/03L-0 + (ML20033B583)
- 05000311/LER-1981-110-03, /03L-0:on 811026,while Attempting to Place Containment Fan Coil Units 21 & 23 in Low Speed Accident Mode,Units Declared Inoperable Due to Low Flow Indication. Caused by Silt in Transmitter Sensing Lines + (ML20033B585)
- 05000245/LER-1981-029-03, /03L-1:on 810908,while Performing Reactor low-low Water Level Functional & Calibr Test,Switch 263-73B Found Sticking.Cause Unknown.Switch Cycled & Recalibr + (ML20033B586)
- 05000220/LER-1981-048-03, /03L-0:on 811019,during Normal Operation,Liquid Poison Pump 11 Was Removed from Svc.Prior to Removal,Pump 12 Was Run to Prove Operability.Pump Removed for Scheduled Maint of Packing + (ML20033B588)
- JAFP-81-1270, Responds to NRC Re Violations Noted in IE Insp Rept 50-333/81-21.Corrective Actions:Monitoring of Diesel Generator Door Monitoring Sys Completed on 811022 + (ML20033B589)
- ML20033B590 + (ML20033B590)
- ML20033B592 + (ML20033B592)
- ML20033B593 + (ML20033B593)
- 05000272/LER-1981-096, Forwards LER 81-096/01T-0.Detailed Event Analysis Encl + (ML20033B594)
- 05000311/LER-1981-111, Forwards LER 81-111/03L-0.Detailed Event Analysis Encl + (ML20033B596)
- IR 05000334/1981020 + (ML20033B598)
- ML20033B600 + (ML20033B600)
- 05000272/LER-1981-096-01, /01T-0:on 811107,during Insp,Svc Water Discovered Leaking from Containment Fan Coil Units 11 & 15.Cause Not Stated.Leak on Unit 15 Repaired W/Belzona Metal Filler. Coil on Unit 11 Isolated by Installing Blank Flange Insert + (ML20033B602)
- ML20033B603 + (ML20033B603)
- 05000311/LER-1981-111-03, /03L-0:on 811022,during Boration Process, Pressurizer Pressure Dropped Below DNB Parameter for 5 Minutes.Caused by Injection of Excessive Amount of Boron in Rcs.Personnel Counseled Re Correct Procedure + (ML20033B604)
- ML20033B605 + (ML20033B605)
- ML20033B608 + (ML20033B608)
- ML20033B609 + (ML20033B609)
- A01925, Responds to IE Bulletin 81-02,Suppl 1 Re Failure of Valves to Close Against Differential Pressure.Four Westinghouse Electro-Mechanical Div-mfg Motor Operated Gate Valves Found in safety-related Sys.Approx 60 Manhours Expended + (ML20033B610)
- 05000272/LER-1981-097-01, /01T-0:on 811106,boron Injection Tank Inlet Valves 1SJ4 & 1SJ5 Failed to Open Fully.Caused by Boron Buildup Around Stem.Boron Removed & Torque Settings Increased + (ML20033B611)
- ML20033B614 + (ML20033B614)
- 05000272/LER-1981-104, Forwards LER 81-104/03L-0.Detailed Event Analysis Encl + (ML20033B616)
- ML20033B618 + (ML20033B618)
- IR 05000277/1981012 + (ML20033B619)
- ML20033B621 + (ML20033B621)
- 05000272/LER-1981-104-03, /03L-0:on 811026,steam Generator 13 Steam Flow Channel 1 Discovered Indicating High.Caused by Transmitter Being Out of Calibr.Transmitter Recalibr + (ML20033B622)
- ML20033B623 + (ML20033B623)
- ML20033B624 + (ML20033B624)
- 05000272/LER-1981-102, Forwards LER 81-102/03L-0.Detailed Event Analysis Encl + (ML20033B625)
- ML20033B627 + (ML20033B627)
- ML20033B629 + (ML20033B629)
- ML20033B630 + (ML20033B630)
- ML20033B632 + (ML20033B632)
- ML20033B633 + (ML20033B633)
- ML20033B634 + (ML20033B634)
- 05000272/LER-1981-102-03, /03L-0:on 811021,discovered Inoperable Power Operated Relief Valve in Violation of Amend 39 to Tech Specs.Amend 39 Posted & Power Removed from Valves + (ML20033B635)
- ML20033B636 + (ML20033B636)
- ML20033B637 + (ML20033B637)
- ML20033B638 + (ML20033B638)
- ML20033B639 + (ML20033B639)
- 05000311/LER-1981-104, Forwards LER 81-104/01X-02.Detailed Event Analysis Encl + (ML20033B640)
- ML20033B642 + (ML20033B642)
- IR 05000278/1981021 + (ML20033B643)
- ML20033B645 + (ML20033B645)
- 05000320/LER-1981-028, Forwards LER 81-028/01L-0 + (ML20033B647)
- ML20033B649 + (ML20033B649)
- IR 05000151/1981001 + (ML20033B650)
- 05000320/LER-1981-028-01, /01L-0:on 811014,auxiliary Bldg Exhaust Flowrate Decreased Approx 7000 Cfm.Caused by One of Two Vortex Dampers on Each Exhaust Fan (AH-E-8A & 8B) Failing to Close. Dampers Repaired + (ML20033B651)
- ML20033B652 + (ML20033B652)
- ML20033B653 + (ML20033B653)
- ML20033B654 + (ML20033B654)