- ML20010H886 + (ML20010H886)
- ML20010H887 + (ML20010H887)
- ML20010H890 + (ML20010H890)
- 05000368/LER-1981-029-03, /03L-0:on 810806,two Unsealed Wall Fire Barrier Penetrations Found W/O Proper Fire Watch.Caused by Inadequate Instructions to Contractor Personnel.Fire Watch Set Up & Maintained Until Fire Barrier re-established + (ML20010H891)
- 05000324/LER-1981-079, Forwards LER 81-079/03L-0 + (ML20010H892)
- ML20010H893 + (ML20010H893)
- AECM-81-357, Forwards Responses to Informal Questions Presented During 810817 Meeting W/Nrc & Bechtel Re Cable Tray Testing.Info Presented Is Also in Direct Response to SER (NUREG-0831,Sept 1981 Item 1.9(1)) + (ML20010H894)
- 05000313/LER-1981-009, Forwards LER 81-009/03L-0 + (ML20010H895)
- ML20010H896 + (ML20010H896)
- ML20010H897 + (ML20010H897)
- IR 05000382/1981022 + (ML20010H899)
- ML20010H900 + (ML20010H900)
- 05000324/LER-1981-079-03, /03L-0:on 810828,while Performing Routine Maint on RHR Steam Leak Detection Temp Switches 2-E11-TS-N600A & B, HPCI Sys Isolated Automatically.Caused by Removal of Thermocouple Leads to HPCI Room Ambient Temp Switch + (ML20010H901)
- 05000313/LER-1981-009-03, /03L-0:on 810727,during Start Test of Steam Driven Emergency Feedwater Pump P7A,steam Generator B Valve CV-2617 Did Not Open on Demand.Caused by Excessive Play Due to Wear.Switch Replaced + (ML20010H902)
- 05000267/LER-1981-052, Forwards LER 81-052/03L-0.Detailed Event Analysis Encl + (ML20010H903)
- ML20010H904 + (ML20010H904)
- ML20010H905 + (ML20010H905)
- ML20010H906 + (ML20010H906)
- 05000265/LER-1981-015, Forwards LER 81-015/03L-0 + (ML20010H907)
- ML20010H908 + (ML20010H908)
- 05000368/LER-1981-031, Forwards LER 81-031/03L-0 + (ML20010H911)
- ML20010H912 + (ML20010H912)
- 05000267/LER-1981-052-03, /03L-0:on 810812,standby Bearing Water Makeup Pump Removed from Svc.Caused by Need to Repair Bonnet Leak in Valve in Suction Line to Pump.Pump Returned to Svc After Repair Completed + (ML20010H913)
- ML20010H914 + (ML20010H914)
- ML20010H915 + (ML20010H915)
- ML20010H918 + (ML20010H918)
- ML20010H919 + (ML20010H919)
- 05000265/LER-1981-015-03, /03L-0:on 810823,while Performing Suppression Chamber to Drywell Vacuum Breaker Monthly Exercise,Valve 2-1601-32C Failed to Indicate Fully Closed.Caused by Misalignment of Position Indication Limit Switches + (ML20010H920)
- ML20010H921 + (ML20010H921)
- 05000270/LER-1981-013-03, /03L-0:on 810815,reactor Bldg Spray Pump 2A Declared Inoperable Due to Oil Leak on Bearing Oil Reservoir.Caused by Loose Piping Allowing Leakage.Reservoir Refilled W/Oil + (ML20010H922)
- ML20010H923 + (ML20010H923)
- ML20010H924 + (ML20010H924)
- 05000267/LER-1981-049, Forwards LER 81-049/03L-0.Detailed Event Analysis Encl + (ML20010H925)
- ML20010H926 + (ML20010H926)
- ML20010H927 + (ML20010H927)
- 05000368/LER-1981-031-03, /03L-0:on 810808,during Axial Shape Index Dampening Maneuver,Part Length Control Element Assembly Dropped & Became Inoperable.After Repair,Dropped Again on 810809.Caused by Poor Connection of Coil Driver Card + (ML20010H928)
- ML20010H929 + (ML20010H929)
- 05000267/LER-1981-049-03, /03L-0:during 810802-07,increase Occurred in Offgassing from Core & Core Outlet Temps.Caused by Increased Primary Coolant Moisture & Oxidants from Refueling Shutdown + (ML20010H930)
- 05000368/LER-1981-030, Forwards LER 81-030/03L-0 + (ML20010H931)
- ML20010H932 + (ML20010H932)
- ML20010H933 + (ML20010H933)
- ML20010H935 + (ML20010H935)
- ML20010H936 + (ML20010H936)
- ML20010H937 + (ML20010H937)
- 05000368/LER-1981-030-03, /03L-0:on 810731,during Design Mod Check of Remote Control Hydrogen Analyzer Sample Pump 2P162,found No Air Flow Delivered to One Analyzer.Cause Undetermined.Sample Pump Operable within 30 Days + (ML20010H939)
- ML20010H940 + (ML20010H940)
- ML20010H941 + (ML20010H941)
- ML20010H943 + (ML20010H943)
- 05000313/LER-1981-010, Forwards LER 81-010/03L-0 + (ML20010H944)
- ML20010H945 + (ML20010H945)