- ML20009F589 + (ML20009F589)
- 05000335/LER-1981-031, Forwards LER 81-031/03L-0 + (ML20009F591)
- ML20009F594 + (ML20009F594)
- 05000335/LER-1981-031-03, /03L-0:on 810605,electrical Ground Occurred on 125-volt Dc Bus B.Caused by Grounded Coil in Faulty Electrohydraulic Actuator for Governor Valve.Spare Actuator Installed + (ML20009F595)
- ML20009F596 + (ML20009F596)
- 05000369/LER-1981-067, Forwards LER 81-067/03L-0.Detailed Event Analysis Encl + (ML20009F597)
- ML20009F598 + (ML20009F598)
- ML20009F599 + (ML20009F599)
- 05000296/LER-1981-032, Forwards LER 81-032/03L-0 + (ML20009F600)
- ML20009F601 + (ML20009F601)
- 05000369/LER-1981-067-03, /03L-0:on 810425,while in Mode 3 Initial Fuel Loading,Boron Concentration in Upper Head Injection Accumulator Sys Was 2,153 Parts Per Meter.Caused by Insufficient Purging Before Sampling.Pressure Reduced + (ML20009F602)
- ML20009F603 + (ML20009F603)
- 05000296/LER-1981-032-03, /03L-0:on 810701,leak Discovered at Vent Nipple of RHR Pump Room Cooler 3A.Cause Unknown.Crack Was Silver Soldered + (ML20009F604)
- ML20009F606 + (ML20009F606)
- 05000366/LER-1981-051, Forwards LER 81-051/03L-0 + (ML20009F607)
- ML20009F608 + (ML20009F608)
- 05000369/LER-1981-068, Forwards LER 81-068/03L-0.Detailed Event Analysis Encl + (ML20009F609)
- 05000369/LER-1981-069, Forwards LER 81-069/03L-0.Detailed Event Analysis Encl + (ML20009F613)
- ML20009F615 + (ML20009F615)
- ML20009F616 + (ML20009F616)
- ML20009F617 + (ML20009F617)
- 05000366/LER-1981-051-03, /03L-0:on 810610,reactor Bldg to Torus Vacuum Breaker Isolation Valve 2T48-F310 Failed Open.Caused by Sticking Switch Reset.Switch Cleaned,Lubricated & Tested + (ML20009F619)
- 05000369/LER-1981-069-03, /03L-0:on 810426,while in Mode 3 Initial Fuel Loading,Cold Leg Accumulator D Low Level Alarm Received in Control Room.Caused by Leaking Safety Injection Test Header. Level Restored.Leaking Valve Will Be Replaced & Tested + (ML20009F620)
- 05000369/LER-1981-074, Forwards LER 81-074/03L-0.Detailed Event Analysis Encl + (ML20009F621)
- ML20009F622 + (ML20009F622)
- ML20009F623 + (ML20009F623)
- ML20009F624 + (ML20009F624)
- 05000369/LER-1981-074-03, /03L-0:on 810429,inadvertent Safety Injection Initiated on Train a When Solid State Protection Sys Logic Cabinets Were Returned to Svc W/O Blocking Injection Signals During Initial Fuel Load.Caused by Mods to Cabinets + (ML20009F625)
- 05000364/LER-1981-022-03, /03L-0:on 810603,recombiner Oxygen Outlet Analyzer a Found Not Responding to Changes in Oxygen Concentration. Probably Caused by Serviceman Failure to Place Analyzer in Measure Mode Following Performance of Alignment Procedu + (ML20009F626)
- ML20009F627 + (ML20009F627)
- 05000364/LER-1981-023-03, /03L-0:on 810604,boric Acid Storage Sys Declared Inoperable Due to Low Concentration in Boric Acid Tank 2A & Low Vol of Solution in Tank 2B.Caused by Prior Use of Sys for Boration & Personnel Error + (ML20009F628)
- 05000321/LER-1981-057, Forwards LER 81-057/03L-0 + (ML20009F629)
- ML20009F630 + (ML20009F630)
- 05000369/LER-1981-077, Forwards LER 81-077/01T-0.Detailed Event Analysis Encl + (ML20009F631)
- ML20009F632 + (ML20009F632)
- ML20009F633 + (ML20009F633)
- 05000364/LER-1981-025-03, /03L-0:on 810604,steam Jet Air Ejector Noble Gas Activity Monitor RE-15 Failed Low.Caused by Faulty Connection at Detector.Condition Corrected & Monitor Returned to Svc on 810615 + (ML20009F634)
- 05000369/LER-1981-095, Forwards LER 81-095/03L-0 + (ML20009F635)
- ML20009F636 + (ML20009F636)
- 05000369/LER-1981-077-01, /01T-0:on 810521,ASME Code Rejectable Indications Found in Vendor Seal Plate to Door Frame Welds During Nondestructive Exam of Personnel Lock Shim Plate Welds. Caused by Use of Seal Rather than Structural Welds + (ML20009F637)
- 05000335/LER-1981-027, Forwards LER 81-027/03L-0 + (ML20009F638)
- ML20009F639 + (ML20009F639)
- ML20009F640 + (ML20009F640)
- ML20009F641 + (ML20009F641)
- 05000369/LER-1981-082, Forwards LER 81-082/03L-0 + (ML20009F642)
- ML20009F643 + (ML20009F643)
- 05000321/LER-1981-057-03, /03L-0:on 810611,temporary Change to HNP-1-6907 (Reactor Core Isolation Cooling Pump Suction Hydro) Found Not Approved by Mgt within Reguired Time.Caused by Personnel Failure to Maintain Adequate Control Over Procedure + (ML20009F644)
- 05000369/LER-1981-095-03, /03L-0:on 810606,flow Rate Measurement Instrumentation on Waste Monitor Tank a Declared Inoperable During Attempted Liquid Water Release.Caused by Supply Air Isolation Valve to Transmitter Left Closed Following Maint + (ML20009F646)
- 05000348/LER-1981-044-03, /03L-0:on 810610,diesel Generator 1C Declared Inoperable During Test FNP-1-STP-28.1.Caused by Overvoltage Condition Due to Damaged Voltage Regulator Circuitry Resulting from Failed Engine Running Relay + (ML20009F647)
- 05000335/LER-1981-027-03, /03L-0:on 810519,while Cleaning Condenser Water Boxes,Control Element Assembly 65 Dropped While Being Inserted.Cause Unknown.Assembly Returned to Group Position + (ML20009F648)
- 05000369/LER-1981-082-03, /03L-0:on 810504-22,fire Detection Sys Found Inoperable.Caused by Const in Area.Fire Watches & Patrols Established + (ML20009F649)