- ML20003B736 + (ML20003B736)
- PNO-I-81-022, on 810216,licensee Informed That Thickness Gauge Containing 17 Mci Cs-137 Was Missing.Caused When Gauge Taken Off Line in Jan 1981 & Placed in Salvage Dept.Gauge Shipped to Prolerized Scrap Metal Company by Mistake + (ML20003B737)
- 05000296/LER-1981-007, Forwards LER 81-007/03L-0 + (ML20003B738)
- ML20003B739 + (ML20003B739)
- PNO-I-81-021, on 810213,based on Results from Charpy V-notch Impact Tests,Licensee Notified That Hydrostatic Test of RCS in Mar 1980 Performed at 27 Degrees Below Min Pressurization Temp + (ML20003B740)
- 05000296/LER-1981-007-03, /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 + (ML20003B741)
- PNO-I-81-023, liquid Observed in Truck Carrying Radiography Device & Nine Drums Phosphoric Acid Containing Natural U. Caused by Leaking Drum.Truck & Contents Surveyed for Radioactive Matl Leakage + (ML20003B742)
- 05000267/LER-1981-013, Forwards LER 81-013/01T-0.Detailed Event Analysis Submitted + (ML20003B743)
- ML20003B744 + (ML20003B744)
- PNO-I-81-025, on 810218,licensee Reported 9.65 Ci Kr-85 Released from Device Used for Leak Testing Electronic Components During Sampling Prior to Returning Device to Manufacturer.Stack Concentration Exceed 10CFR20 Limits + (ML20003B745)
- ML20003B747 + (ML20003B747)
- 05000267/LER-1981-013-01, /01T-0:on 810203,following Liquid Waste Release 429,tritium Concentration Exceeded Tech Spec.Caused by Sys Design Inadequacy W/Oil Separator on Liquid Waste Discharge Line.Bypass Installed Around Oil Separator + (ML20003B748)
- ML20003B749 + (ML20003B749)
- ML20003B750 + (ML20003B750)
- 05000317/LER-1981-005, Forwards LER 81-005/03L-0 + (ML20003B752)
- ML20003B753 + (ML20003B753)
- 05000318/LER-1981-006, Forwards LER 81-006/03L-0 + (ML20003B754)
- ML20003B755 + (ML20003B755)
- 05000317/LER-1981-005-03, /03L-0:on 810119,during Surveillance Testing, Containment Cooler 14 Would Not Start in Slow Speed.Caused by Contacts Not Closing on Slow Speed Motor Starter Interlock Contact Assembly Due to Cracked Case + (ML20003B756)
- 05000029/LER-1981-001, Forwards LER 81-001/03L-0 + (ML20003B757)
- 05000029/LER-1981-001-03, /03L-0:on 810122,low Main Coolant Flow Sys B Under Current Relays 2A & 4C Failed to Drop Out When de-energized. Caused by Residue Buildup on Relay Activation Plunger.Relay Plungers in Sys a & B Inspected & Cleaned as Require + (ML20003B759)
- 05000318/LER-1981-007, Forwards LER 81-007/03L-0 + (ML20003B760)
- ML20003B761 + (ML20003B761)
- 05000318/LER-1981-006-03, /03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested + (ML20003B762)
- ML20003B764 + (ML20003B764)
- 05000324/LER-1981-010, Forwards LER 81-010/03L-0 + (ML20003B766)
- ML20003B767 + (ML20003B767)
- 05000324/LER-1981-010-03, /03L-0:on 810120,RHR Svc Water Subsys a Suction valve,2-SW-V101,would Not Open Fully.Caused by Two Hex Nuts on Input Shaft of Valve Motor Operator,Model H3BC-SMB-00, Freezing to Shaft.Nuts & Shaft Reworked & Lubricated + (ML20003B769)
- 05000346/LER-1981-007, Forwards LER 81-007/03L-0 + (ML20003B770)
- ML20003B771 + (ML20003B771)
- ML20003B772 + (ML20003B772)
- 05000255/LER-1981-008-03, /03L-0:on 810124,component Cooling Water Pump P-52C Motor Caught on Fire.Caused by Motor Bearing Failure Due to Oil Loss.Motor Replaced + (ML20003B773)
- 05000346/LER-1981-007-03, /03L-0:on 810122,door 306 Found Partially Open,So That Spent Fuel Pool Emergency Ventilation Sys Could Not Have Maintained Area at Correct Pressure.Caused by Maladjusted Door Closure.Maint Work Order Issued + (ML20003B774)
- ML20003B775 + (ML20003B775)
- 05000302/LER-1981-006, Forwards LER 81-006/03L-0 + (ML20003B776)
- ML20003B777 + (ML20003B777)
- ML20003B778 + (ML20003B778)
- ML20003B779 + (ML20003B779)
- 05000302/LER-1981-006-03, /03L-0:on 810123,breaker for Control Complex Emergency Ventilation Fan AHF-18A Found Open.Caused by Inadvertent Bumping of Breaker.Breaker Shut,Operability Checks Performed & Personnel Advised to Exercise Caution + (ML20003B780)
- ML20003B781 + (ML20003B781)
- ML20003B782 + (ML20003B782)
- 05000249/LER-1981-003-03, /03L-0:on 810120,Model 288 Differential Pressure Indicating switch,3-1349B,tripped Above Tech Spec Limit. Caused by Instrument Drift.Switch Readjusted & Repeatability Verified + (ML20003B783)
- 05000317/LER-1981-006, Forwards LER 81-006/03L-0 + (ML20003B784)
- ML20003B785 + (ML20003B785)
- 05000317/LER-1981-006-03, /03L-0:on 810113,steam Generator 11,level Channel D Placed Out of Svc Per Tech Specs to Correct Problem W/Ref Leg.Caused by Indication Deviation Among Redundant Safety Channels Due to Level Transmitter Valve leak-through + (ML20003B786)
- ML20003B787 + (ML20003B787)
- ML20003B788 + (ML20003B788)
- 05000278/LER-1981-005-03, /03L-0:on 810127,setpoint of Temp Switch TS 5943 B (HPCI Steam Line Area High Temp Isolation) Found to Be Above Tech Spec Limit.Caused by Setpoint Drift.Instrument Recalibr to within Tech Spec Limits,Tested & Returned to Svc + (ML20003B789)
- ML20003B790 + (ML20003B790)
- ML20003B791 + (ML20003B791)
- NUREG-0760, Forwards Notice of Violation & NUREG-0760 Detailing Investigation Conducted Mar 1980-Jan 1981 Into Info Flow During 790328 Accident + (ML20003B792)