- ML19345A558 + (ML19345A558)
- ML19345A560 + (ML19345A560)
- ML19345A561 + (ML19345A561)
- 05000029/LER-1977-021-03, /03L-0:on 770420,air Mass Calculation Performed on 770419 Indicated That Significant Leak in Primary Containment Might Exist.Data Point Indicated That VC Air Pressure Had Fallen.No Leak Found,Reactor Cooled Down + (ML19345A562)
- 05000029/LER-1977-023, Forwards LER 77-023/03L-0 + (ML19345A563)
- 05000029/LER-1977-023-03, /03L-0:on 770425,net Decrease in Sys Vol Found. Sys Check Performed & Leaking Diaphragm Valve Discovered.Caused by Petroleum Based Substance on Valve. Diaphragm Replaced + (ML19345A565)
- 05000029/LER-1977-025, Forwards LER 77-025/03L-0 + (ML19345A566)
- ML19345A568 + (ML19345A568)
- ML19345A570 + (ML19345A570)
- 05000029/LER-1977-025-03, /03L-0:on 770503,when Component Cooling Radiation Monitor Channel Drawer Removed,Cables Dropped Into Uncovered High Voltage Power Supply Used for Loop Seal Discharge Monitor Causing Short Circuit & Failure of Monitor + (ML19345A571)
- 05000029/LER-1977-019, Forwards LER 77-019/03L-0 + (ML19345A572)
- 05000029/LER-1977-019-03, /03L-0:on 770402,radioactive Gaseous Waste Monitor Loop Seal Discharge Monitor Alarm Failed to Operate.Caused by Alarm Setpoint & Meter Pointer Contacts Being Corroded. Contacts Cleaned,Mylar Film & Protective Tape Replaced + (ML19345A574)
- ML19345A575 + (ML19345A575)
- 05000029/LER-1977-010, Forwards LER 77-010/03L-0 + (ML19345A576)
- ML19345A578 + (ML19345A578)
- 05000029/LER-1977-010-03, /03L-0:on 770224,light Leakage Found from Weld on Discharge Line of Charging Pump 3 at Inlet to Pump Relief Valve.Caused by Failure of Weld & Pipe Nipple.Piping Sections Replaced + (ML19345A580)
- ML19345A581 + (ML19345A581)
- 05000029/LER-1977-011, Forwards LER 77-011/03L-0 + (ML19345A582)
- 05000029/LER-1977-011-03, /03L-0:on 770301,emergency Diesel Generator 1 Starter Motor Failed During Surveillance Test.Caused by Armmature Shaft Being Broke.Starting Motor Replaced + (ML19345A584)
- 05000029/LER-1977-012, Forwards LER 77-012/03L-0 + (ML19345A585)
- ML19345A587 + (ML19345A587)
- 05000029/LER-1977-012-03, /03L-0:on 770306,alarm Setpoint Adjustment of Radiation Monitor for Steam Generator Blowdown Found Defective.Caused by Alarm Setpoint Control Failure to Adjust.Control Replaced + (ML19345A589)
- ML19345A590 + (ML19345A590)
- 05000029/LER-1977-013, Forwards LER 77-013/03L-0 + (ML19345A591)
- ML19345A593 + (ML19345A593)
- 05000029/LER-1977-013-03, /03L-0:on 770307,following Power Reduction to Identify Plug Leaking Condenser Tube,Chlorides in Steam Generators 1 & 4 Exceeded Tech Specs Limits.Caused by Chloride Concentration Buildup in Steam Generator + (ML19345A594)
- 05000029/LER-1976-005, Forwards LER 76-005/03L-0 + (ML19345A595)
- 05000029/LER-1976-005-03, /03L-0:on 760520,auxiliary Operator Noted Slight Leakage from Weld on Inlet Charging Pump 3 Relief Valve. Caused by Pullback Gap Not Allowed During Installation of Pipe & Vibration Induced Fatigue Failure + (ML19345A597)
- 05000029/LER-1976-012, Forwards LER 76-012/01T-0 + (ML19345A598)
- 05000029/LER-1976-012-01, /01T-0:on 761119,safety Injection Accumulator for Boron Was 30 Ppm Over Tech Specs & 80 Ppm Over Administrative Limits.Investigation Revealed That Std Sodium Hydroxide Titrant Had Concentrations Lower than Predicted + (ML19345A600)
- 05000029/LER-1977-029, Forwards LER 77-029/03L-0 + (ML19345A601)
- 05000029/LER-1977-029-03, /03L-0:on 770603,during Mode 1,primary Vent Stack Radiation Detection Sys Particulate Channel Failed.Caused by Control Setpoint Being Set Too Close Together.Control Setpoint Readjusted + (ML19345A603)
- 05000029/LER-1977-014, Forwards LER 77-014/03L-0 + (ML19345A604)
- 05000029/LER-1977-014-03, /03L-0:on 770308,iodine Channel of Primary Vent Stack Radiation Monitoring Sys Failed to Meet High Level Count Rate Acceptance Criteria.Caused by Voltage Drift. Voltage Adjusted + (ML19345A606)
- 05000029/LER-1977-018, Forwards LER 77-018/03L-0 + (ML19345A607)
- 05000029/LER-1977-018-03, /03L-0:on 770326,steam Generator Chloride Concentration Increased to Max Level of 4 Ppm in Steam Generator 2,exceeding Tech Specs Limit + (ML19345A609)
- W3P80-0167, Forwards Amend 13 to OL Application & to Fsar,Including Responses to Addl Info Requests from Auxiliary Sys Branch, I&C Branch,Reactor Sys Branch & Info on Emergency Feedwater Sys.Two Hundred Oversize Drawings Encl + (ML19345A610)
- ML19345A611 + (ML19345A611)
- ML19345A612 + (ML19345A612)
- ML19345A614 + (ML19345A614)
- 05000029/LER-1977-027, Forwards LER 77-027/03L-0 + (ML19345A616)
- ML19345A618 + (ML19345A618)
- 05000029/LER-1977-027-03, /03L-0:on 770524,biannual Recalibr Performed on Two LPIS Accumulator Channels.Instruments Below Tech Specs Limit.Recalibr Adjustments Made to Bring Channels within Tech Specs Limit + (ML19345A619)
- 05000029/LER-1977-028, Forwards LER 77-028/03L-0 + (ML19345A620)
- 05000029/LER-1977-028-03, /03L-0:on 770530,noble Gas Monitor of Primary Vent Stack Radiation Detection Sys Failed.Cause Could Not Be Ascertained as Trouble Could Not Be Repeated After Alarm Reset + (ML19345A622)
- 05000029/LER-1977-026, Forwards LER 77-026/03L-0 + (ML19345A623)
- 05000029/LER-1977-026-03, /03L-0:on 770518,control Room Received Low Flow Alarm on Primary Vent Stack Particulate Radiation Monitor Channel.Caused by Paper in Util Being Slightly Oversized & Boundup.New Roll of Paper Installed + (ML19345A625)
- 05000029/LER-1977-024, Forwards LER 77-024/03L-0 + (ML19345A626)
- 05000029/LER-1977-024-03, /03L-0:on 770428,loop Seal Discharge Radioactive Gaseous Monitor Indication Went to Zero.Caused by Drift in RM-40 Power Supply High Voltage.High Voltage Adjusted + (ML19345A628)
- 05000029/LER-1977-020, Forwards LER 77-020/03L-0 + (ML19345A629)
- 05000029/LER-1977-020-03, /03L-0:on 770415,during Paper Replacement in Main Coolant Leakage Vapor Container Air Particulate Monitor Paper Drive Found Inoperative.Caused by Deterioration of Reduction Gears.Reduction Gears Rebuilt & Lubricated + (ML19345A631)