Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19344D992 + (ML19344D992)
- ML19344D993 + (ML19344D993)
- ML19344D994 + (ML19344D994)
- 05000293/LER-1980-040-03, /03L-0:on 800724,standby Gas Treatment Sys Found Inoperable.Caused by Breaker Being Unintentionally Moved to Open Position,Possibly During Daily Operator Tour.Breaker Returned to Normal.Operational Check Satisfactory + (ML19344D995)
- 05000267/LER-1980-042-03, /03L-0:on 800725,plant Was Operated at Approx 47% Thermal Power & 131 Mwe W/Two Inoperable Reserve Shutdown Units in 30 Hopper Subsystem.Caused by Isolation of Bottle for Repair of Leakage at Brass Fitting for Region 15 Hook + (ML19344D996)
- 05000312/LER-1980-038, Forwards LER 80-038/041-0 + (ML19344D997)
- ML19344D999 + (ML19344D999)
- ML19344E000 + (ML19344E000)
- ML19344E001 + (ML19344E001)
- 05000312/LER-1980-038-41, /041-0:on 800729,review of Plant Effluent Data for Jul 1980 Indicated That on 800629 & 30,sample Indicated 0.25 & 0.3 Mg/Liter Chlorine.Second Followup Sample Not Obtained.Caused by Personnel Error.Personnel Reinstructed + (ML19344E002)
- 05000338/LER-1980-063, Forwards LER 80-063/01T-0 + (ML19344E003)
- ML19344E004 + (ML19344E004)
- 05000312/LER-1980-036, Forwards LER 80-036/041-0 + (ML19344E005)
- 05000312/LER-1980-036-41, /041-0:on 800710,review of Jul 1980 Effluent Monitoring Charts Indicated Plant Liquid Effluent Ph in Excess of 8.5 Tech Spec Limit.Cause Unknown.Automatic Diversion Setpoint Lowered to Minimize Recurrence + (ML19344E007)
- ML19344E009 + (ML19344E009)
- 05000338/LER-1980-063-01, /01T-0:on 800808,w/unit at 100% Power,Feedwater Flow Signal to Reactor Trip Sys Determined to Be in Error by Approx 4%.Caused by Venturi Fouling in Lines.Fouling Will Be Monitored by Comparing Feed Flow to Steam Flow + (ML19344E010)
- ML19344E011 + (ML19344E011)
- 05000321/LER-1980-089, Forwards LER 80-089/03L-0 + (ML19344E012)
- ML19344E013 + (ML19344E013)
- 05000317/LER-1980-036, Forwards LER 80-036/03L-0 + (ML19344E014)
- ML19344E015 + (ML19344E015)
- 05000366/LER-1980-121-01, /01T-0:on 800813,w/unit at 2412 MW While Performing HNP-2-3102,pressure Switches Actuated Out of Tolerance.Caused by Setpoint Drift.Switches Recalibr. HNP-2-3102 Performed Satisfactorily + (ML19344E016)
- 05000321/LER-1980-089-03, /03L-0:on 800726,during Normal Operation,Drywell & Torus Temp Recorder lT47-R611 Found Inoperative.Caused by Stripped Gear in Print Drive Mechanism.Gear Replaced.Design Change Initiated to Replace Recorder + (ML19344E017)
- ML19344E018 + (ML19344E018)
- ML19344E019 + (ML19344E019)
- 05000302/LER-1980-030, Forwards LER 80-030/03L-0 + (ML19344E020)
- ML19344E021 + (ML19344E021)
- ML19344E022 + (ML19344E022)
- 05000298/LER-1980-026, Forwards LER 80-026/03L-0 + (ML19344E024)
- ML19344E025 + (ML19344E025)
- ML19344E026 + (ML19344E026)
- 05000302/LER-1980-030-03, /03L-0:on 800731,during Monthly Diesel Generator Surveillance,Emergency Diesel Generator B Tripped as Result of Separation of Turbocharger Discharge Ductwork Due to Sheared Bolts on Mounting Bracket.Caused by Vibration + (ML19344E027)
- 05000321/LER-1980-088, Forwards LER 80-088/03L-0 + (ML19344E028)
- ML19344E030 + (ML19344E030)
- 05000298/LER-1980-026-03, /03L-0:on 800701,during Routine Measurement of Identified Reactor Leakage,Drywell Equipment Drain Sump Flow Instrument Found Inoperable.Caused by Broken Slide Wire in Recorder & Blown Fuse in Power Supply.Fuse & Wire Replace + (ML19344E031)
- ML19344E032 + (ML19344E032)
- ML19344E033 + (ML19344E033)
- ML19344E034 + (ML19344E034)
- 05000321/LER-1980-088-03, /03L-0:on 800725,w/reactor in start-up Mode & Reactor Pressure at 150 1b & 0% Power,During HPCI Overspeed Trip Test,Turbine Failed to Trip at or Below 5,000 Revolutions Per Minute.Caused by Setpoint Drift + (ML19344E035)
- 05000317/LER-1980-036-03, /03L-0:on 800721,after Performing Preventative Maint,Discovered That Diesel Generator 11 Had No Speed or Voltage Control.Caused by Water Dripping on Generator Voltage Transformer & Regulator from Jacket Cooling Sys + (ML19344E036)
- ML19344E037 + (ML19344E037)
- 05000368/LER-1980-047-03, /03L-0:on 800703,during Mode 1 Operation,While Making Routine Check of Radiation Monitoring Sys,Containment Atmosphere Radiation Monitor Found Inoperable.Caused by Overload Trip Due to High Room Temp + (ML19344E038)
- 05000321/LER-1980-090, Forwards LER 80-090/03L-0 + (ML19344E039)
- 05000029/LER-1980-015, Forwards LER 80-015/03L-0 + (ML19344E041)
- ML19344E046 + (ML19344E046)
- 05000298/LER-1980-027, Forwards LER 80-027/03L-0 + (ML19344E047)
- ML19344E048 + (ML19344E048)
- ML19344E050 + (ML19344E050)
- 05000327/LER-1980-133, Forwards LER 80-133/03L-0 + (ML19344E051)
- ML19344E052 + (ML19344E052)
- 05000029/LER-1980-015-03, /03L-0:on 800721,during Maint Outage,Yard Hydrant 11 & 18 Were Individually Removed from Svc to Repair Leaking Valves.Caused by Wearing of Fiber Disc & Seat Due to Valve Cycling.Valves Disc,Seat & Drain Replaced + (ML19344E053)