- 05000295/LER-1978-144, Forwards LER 78-144/03L-0 + (ML19261A812)
- 05000318/LER-1979-003-01, /01T-0 on 790120:during Normal operation,22A Lower Seal Temp Alarm Was Received & RCS Leak Rate Increased. Caused by Cracked Weld on 22A Lower Seal Pressure Sensing Line.Design Change Is in Progress + (ML19261A814)
- 05000295/LER-1978-138-03, /03L-0 on 781224:during Normal Operation Component Cooling Liquid Radiation Monitor 1RE-0017 Failed Low & Was Taken Out of Svc.Cause Was Defective High Voltage Power Supply + (ML19261A815)
- ML19261A816 + (ML19261A816)
- ML19261A817 + (ML19261A817)
- 05000295/LER-1978-144-03, /03L-0 on 780925:generator 1NM-441B Output Out of Tolerance;Low 2.5%.Caused by Instrument Drift Resulting in Nontolerance of Function Generator Model 113.Model Recalibrated & System Returned to Normal + (ML19261A818)
- ML19261A819 + (ML19261A819)
- ML19261A820 + (ML19261A820)
- ML19261A821 + (ML19261A821)
- 05000295/LER-1978-027, Forwards LER 78-027/03X-1 + (ML19261A822)
- 05000295/LER-1978-140, Forwards LER 78-140/03L-0 + (ML19261A824)
- 05000295/LER-1978-027-03, /03X-1 on 780402:steam Flow Channel 1F522 Failed Low Due to Plugging of High Side Sensing of Transmitter While Sealing Valve Steam Leak.Valve Was Replaced + (ML19261A826)
- 05000295/LER-1978-140-03, /03L-0 on 781227:steam Generator Pressure Channel 1P-546 Pegged High Several Times.Caused by Detuned Oscillator in Transmitter Model 50EP 1041BCXA.Oscillator Replaced & Sys Returned to Normal + (ML19261A827)
- ML19261A828 + (ML19261A828)
- 05000254/LER-1978-033, Forwards LER 78-033/03L-0 + (ML19261A829)
- ML19261A832 + (ML19261A832)
- 05000265/LER-1978-039, Forwards LER 78-039/03L-0 + (ML19261A833)
- ML19261A834 + (ML19261A834)
- ML19261A835 + (ML19261A835)
- ML19261A836 + (ML19261A836)
- 05000254/LER-1978-033-03, /03L-0 on 781219:during Automatic Isolation of Ventilation Sys,Inlet Isolation Dampers 1-5741 a & B Failed to Close.Pilot Solenoid on Air Operator of Damper Valves Stuck & Failed to Supply Air Signal Needed to Close Valve + (ML19261A837)
- 05000265/LER-1978-039-03, /03L-0 on 781218:test Results Found HPCI Initiation Switches Associated W/Drywell Pressure Instruments Not in Accordance W/Tech Specs.Caused by Procedural Inadequacy;Switches Excluded from Test Program + (ML19261A838)
- ML19261A840 + (ML19261A840)
- ML19261A841 + (ML19261A841)
- ML19261A842 + (ML19261A842)
- 05000295/LER-1978-130, Forwards LER 78-130/99X-0 + (ML19261A843)
- ML19261A845 + (ML19261A845)
- ML19261A846 + (ML19261A846)
- 05000295/LER-1978-130-99, /99X-0 on 781205:two Safety Injections Ocurred from False Steam Pressure Differential Signals.False Signals Caused by Shocks from Water Hammers + (ML19261A847)
- ML19261A848 + (ML19261A848)
- 05000295/LER-1979-003, Forwards LER 79-003/01T-0 + (ML19261A849)
- ML19261A851 + (ML19261A851)
- 05000295/LER-1979-003-01, /01T-0 on 790109:Westinghouse Results of Feb 1978 ECCS Model Analysis Determined That Fq Limit Should Be 1.86 Rather than the Current Limit of 2.02.Plant Operations Modified to Adhere to New Limit + (ML19261A853)
- ML19261A854 + (ML19261A854)
- ML19261A855 + (ML19261A855)
- ML19261A860 + (ML19261A860)
- ML19261A862 + (ML19261A862)
- ML19261A863 + (ML19261A863)
- ML19261A864 + (ML19261A864)
- ML19261A866 + (ML19261A866)
- ML19261A867 + (ML19261A867)
- ML19261A868 + (ML19261A868)
- ML19261A869 + (ML19261A869)
- ML19261A871 + (ML19261A871)
- ML19261A876 + (ML19261A876)
- IR 05000336/2019010 + (ML19261A879)
- ML19261A883 + (ML19261A883)
- ML19261A885 + (ML19261A885)
- ML19261A892 + (ML19261A892)
- ND-19-0928, ITAAC Closure Notification on Completion of ITAAC 2.3.07.07b.vii (Index Number 881) + (ML19261A894)