Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +, 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing + and 05000335/LER-1994-002, :on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing +
February 8, 1994 +
2 +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
18:47:37, 8 January 2025 +
11 +
10 CFR 50.73(a)(2)(v), Loss of Safety Function +, 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability +, 10 CFR 50.73(a)(2)(iv), System Actuation +, 10 CFR 50.73(a)(2)(i) +, 10 CFR 50.73(a)(2)(x) +, 10 CFR 50.73(a)(2)(iii) +, 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition +, 10 CFR 50.73(a)(2)(viii)(A) + and 10 CFR 50.73(a)(2)(viii)(B) +
February 8, 1994 +
Florida + and Washington +
:on 940113,inadvertent Load Shed of 1A3 4160 Volt Bus Occurred.Caused by Procedural Inadequacy. Electrical Maint Tested 2x-2 Relay & Proved Relay to Be Functioning Correctly at Time of Testing
+