7590-01 UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of
)
)
WOLF CREEK NUCLEAR OPERATING CORPORATION )
Docket No. 50-482
)
(Wolf Creek Generating Station, Unit 1)
)
EXEMPTION 1.
On June 4, 1985, the Commission issued Facility Ope. rating License No, NPF-42 to Wolf Creek Nuclear Operating Corporation (the licensee) for Wolf Creek Generating Station, Unit 1.
The license provides, among other things, that it is subject to all rules, regulations, and orders of the Nuclear Regulatory Commission (the Commission) now and hereafter in effect.
II.
Section Ill.D.l(a) of Appendix J to 10 CFR Part 50 requires, "... a set of three Type A tests [0verall Integrated Containment Leakage Rate Tests, or ILRTs] shall be performed, at approximately equal intervals during each 10-year service period.
The third test of each set shall be conducted when the plant is shutdown for the 10-year plant inservice inspections."
By letter dated October 27, 1993, the licensee requested an exemption from this requirement of the Commission's regulations.
The NRC may grant exemptions from the requirements of the regulations, pursuant to 10 CFR 50.12, that (1) are authorized by law, will not present an
]
l undue risk to the public health and safety, and are consistent with the common defense and security; and (2; present special circumstances.
Section 9408170167 940810 PDR ADOCK 05000482 P
PDR l
50.12(a)(2) of 10 CFR Part 50 describes special circumstances as including cases that would not serve the underlying purpose of the rule or are not necessary to achieve the underlying purpose of the rule.
In a letter also dated October 27, 1993, the licensee applied for an amendment to Facility Operating License No. NPF-42 to change related provisions of the Wolf Creek Generating Station Technical Specifications.
III.
The Type A test is defined in 10 CFR Part 50, Appendix J, Section II.F, as a " test intended to measure the primary reactor containment overall integrated leakage rate (1) after the containment has been completed and is ready for operation, and (2) at periodic intervals thereafter." The licensee conducted ILRTs during October 198C and September 1991 that satisfied the requirements of Appendix J and related technical specifications. The measured leakage rates during these tests were well below the acceptance criteria with the majority of leakage being from containment penetrations and not the containment barrier itself. The requested exemption does not affect the performance of local leakage rate testing which would be expected to detect the most probable sources of containment leakage.
In order to schedule the next ILRT such that it coincides with the 10-year inservice inspections, as required by Appendix J, the licensee has requested a one-time exemption and related technical specification changes to perform the test during the eighth refueling outagr. The eighth refueling outage is currently scheduled for Spring 1996 and would result in a test interval of approximately 54 months with the test being performed approximately six months after the end of the first 10-year service period.
In the aosence of the exemption and related technical specification changes, the licensee would be required to perform an ILRT during both the seventh and eighth refueling outages.
This discrepancy results from the circumstances related to the operating cycle schedules and their correlation with the end of the 10-year service period.
Performance of a fourth ILRT coincident with the 10-year inservice inspections is clearly beyond the intent of the regulations or technical specifications which specifically require three tests during 10-year service intervals.
For the reasons set forth above, the NRC staff concludes that this one-time relief from the requirement to perform the third ILRT within a 10-year service period is not significant in terms of complying with the intent of Appendir J,Section III.D.l(a). Accordingly, the staff finds that the performance of ILRTs during both the seventh and eighth refueling outages would not result in a commensurate increase in the confidence of containment integrity. Therefore, the subject exemptior, request meets the special circumstances of 10 CFR 50.12, in that the fourth test is not necessary to achieve the underlying purpose of the rule.
On this basis, the NRC staff finds that the licensee has demonstrated that special circumstances are present as required by 10 CFR 50.12.
Further the staff also finds that extending the schedule for the third ILRT to beyond the 10-year service period will not present an undue risk to the public health and safety.
IV.
~
Accordingly, the Commission has determined pursuant to 10 CFR 50.12, this exemption is authorized by law and will not endanger life or property or I
,-,n.w,
, ~,,, -
-4_
the common defense and security and is otherwise in the public interest.
Therefore, the Commission hereby grants Wolf Creek Nuclear Operating Corporation an exemption from the requirements of 10 CFR 50, Appendix J, Section III.D.l(a).
Pursuant to 10 CFR 51.32, the Commission has determined that the granting of this exemption will have no significant impact on the environment (59 FR 27076).
Dated at Rockville, Maryland this 10th day of August 1994.
FOR THE NUCLEAR REGULATORY COMMISSION
- w. %
ack W. Roe, Director Division of Reactor Projects III/IV Office of Nuclear Reactor Regulation 9