3/4.6 CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2.
Verifying that each unit operates for at least 15 minutes.
3.
Verifying a cooling water flow rate of > 2000 gpm to each cooling unit when the full flow service water outlet valves are fully open.
ecFoeuutr zareavnt b.
At least once per IS.T.e.ths by verifying that each unit starts automatically on the appropriate ESFAS test signal.
l{
L
- (
9406130259 940609 PDR ADOCK 05000317 P
PDR CALVERT CLIFFS - UNIT 1 3/4 6-19 Amendment No. +72-
j ATTACIIMENT (2)
UNIT 2 TECHNICAL SPECIFICATION MARKED-UP PAGE 3/4 6-15
1 l
3/4.6 CONTAINMENT SYSTEMS SURVEILUNCE REQUIREMENTS (Continued) 2.
Verifying that each unit operates for at least 15 minutes.
3.
Verifying a cooling water flow rate of 3 2000 gpm to each cooling unit when the full flow service water outlet valves are fully open.
REfvELIMG IdTEAVAL b.
At least once per 40 inenths by verifying that each unit starts I
automatically on the appropriate ESFAS test signal.
3
(
I i
i l
1 CALVERT CLIFFS - UNIT 2 3/4 6-15 Amendment No. 449-
.