Amend 56 to License NPF-49,revising Tech Spec Table 3.3-9, Remote Shutdown Instrumentation & Corrects Editorial Error in Table 4.3-6
ML20065F534
Person / Time
Site: Millstone Dominion icon.png
Issue date: 09/26/1990
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Northeast Nuclear Energy Co (NNECO)
Shared Package
ML20065F542 List:
References
NPF-49-A-056 NUDOCS 9010100167
Download: ML20065F534 (5)


Text

i y cd UNITED STATES

/

NUCLEAR REGULATORY COMMISSION o

wAsHmorow. o. c. nosos h,,...+.

NORTHEAST NUCLEAR ENERGY COMPANY. ET AL.

DOCKET NO.-50-423 MILLSTONE NUCLEAR POWER STATION, UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE s

Amendment No. 56 License No. NPF-49 i

1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Northeast Nuclear Energy Company,.

- et al. (the licensee) dated-July 10,1990 complies with the standards-and requirements of the Atomic Energy Act of 1954, as amended-(the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; L

The facility will operate in conformity with the application, the l

srovisions of. the Act, and the rules' and regulation:: of the

=!

amission;

.C

. care-isreasonableassurance(1)thattheactivitiesauthorizedby

his' amendment can be conducted without endangering the health and safety of the. public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the common.

defense and security or to the health and safety of the public; and issuance of this amendment is in accordance with 10 CFR Part 51' a

the Comission's regulations and all applicable requirements-have l

v.

I.

en satisfied.

l i

9010100167 900926 PDR P

ADOCK 05000423;.

PNu

E

?

's 4.

-2

'E.

Accordingly. the license is amended by changes to the Technical Specifications as-indicated in the attachment to this license amendment, a9d paragraph 2.C.(2) of Facility Operating License No. NPF-49 is hereby cmended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No.

56

, and the Environmental Protection Plan contained in Appendix B, both of which-are attached hereto are-hereby incorporated in the license.

The licensee shall operate the-4 facilit3 m Accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance, to be.

implemented within 30 days of issucce.

FOR THE NUCLEAR REGULATORY COMMISSION' 1

John F. Stolz, Director

/

Project Directorate I-4 Division of Reactor P_rojects - I/II Office of Nuclear Reactor Regulation

Attachment:

I Changes to the Technical Specifications j

Date of Issuance:

September 26,:1990 1

r-ATTACHMENT TO LICENSE AMENDMENT NO.< 56 FACILT1Y OPERATING LICENSE NO. NPF-49 DOCKET NO. 50-423 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change, Remove Insert 3/4 3-54 3/4 3-54' 3/4 3-58 3/4 3-58 t $

a

v==

~;

7 -.-

TABLE 3.3-9-

3 if:

REMOTE SHUTDOWN INSTRUMENTATION 13

~ 5E TOTAL NO.

MININUM READOUT OF

-CHANNELSL INSTRUMENT LOCATION CHANNELS OPERABLE-C 25 1.

Reactor Trip Breaker Indication Reactor Trip Switchgear 1/ trip breaker 1/ trip breaker 2.

Pressurizer Pressure Aux. Shutdown Panel 2

1

-d 3...

Pressurizer Level Aux. Shutdown Panel

.2

.1 4.

Steam Generator Pressure Aux. Shutdown Panel 2/ steam generator 1/ steam generator.

5.

Steam Generator Water Level Aux.4 Shutdown Panel 2/ steam generator 1/ steam generator 6.

Auxiliary Feedwater Flow Rate Aux. Shutdown Panel 1/ steam generator 1/ steam generator 7.

Loop Hot Leg Temperature Aux. Shutdown Panel I/ loop 1/ loop-8.

Loop Cold Leg Temperature Aux. Shutdown Panel 1/ loop 1/ loop-9.

Reactor Coolant System Pressure Aux. Shutdown Panel 2

1-(Wide Range)

10. DWST Level Aux. Shutdown Panel 2

1

11. RWST Level Aux. Shutdown Panel 2

1 u,

3

12. Containment Pressure Aux. Shutdown Panel 2

1 13.

Emergency Bus Voltmeters Aux. Shutdown Panel 1/ train I/ train u,

a,

14. Source Range Count Rate Aux. Shutdown Panel 2

1 2

l~

15.

Intermediate Range Flux Aux. Shutdown Pinel

. 2/ tank 1/ tank 16.

Boric Acid Tank Level Aux. Shutdown Panel TRANSFER SWITCHES SWITCH LOCATIGN 1.

Auxiliary Feedwater Isolation FWA*MOV35A -

Transfer Switch Panel 2.

Auxiliary Feedwater Isolation FWA*MOV358 Transfer Switch Panel 3.

Auxiliary Feedwater Isolation FWA*MOV35C Transfer Switch Panel 4.

Auxiliary Feedwater Isolation FWA*MOV350 Transfer Switch Panel F

5.

-Auxiliary Feedwater Pump Ah.-Suction 8

FWA*A0V23A Transfer Switch Panel 6.

Auxiliary Feedwater Pump'AhnSuction 8

FWA*A0V23B Transfer Switch Panel

.?

=

a m

l ll

y.:

~

~

TABLE 4.3-6

~

x;:.

REMDTE SHUTDOWN MONITORING INSTRUMENTATION-0; SURVEILLANCE REOUIREMENTS g

i'i

-CHANNEL-CHANNEL -

INSTRUMENT CHECK

- CALIBRATION b

1.

Reactor Trip Breaker Indication M:

M. A.'

y 2.

Pressurizer Pressure M

R w

3.

Pressurizer Level M

R 4.

Steam Generator Pressure M

R 5.

Steam Generator Water Level

'M R

6.

Auxiliary Feedwater Flow Rate M

'R 7.

Loop Hot leg Temperature M

R 8.

Loop Cold Leg Temperature M

R 9.

Reactor Coolant System Pressure M

R Y,

(Wide Range) u*

10. DWST Level M

R

11. RWST Level M

'R

12. Containment Pressure M

R

13. Emergency Bus Voltmeters M

R

14. Source Range Count Rate M*

R

15. -Intermediate Range Amps M

R-g

16. Boric Acid Tank Level M-R When below P-6 (intemed' ate range neutron.. flux interlock setpoint).

e p

-+

-w

s. - -, '-

.e e

+- y.,..-

e

+, - -

y..,

yee

-f

-u..,-,-

___, _ _, _ _ _ _. _