ML20052A438
| ML20052A438 | |
| Person / Time | |
|---|---|
| Site: | Bellefonte |
| Issue date: | 04/14/1982 |
| From: | Mills L TENNESSEE VALLEY AUTHORITY |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| RTR-NUREG-0578, RTR-NUREG-578 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8204280333 | |
| Download: ML20052A438 (2) | |
Text
..
~.
TENNESSEE VALLEY AUTHORITY ~
CH ATTANOOGA. TENNESSEE 374oh O ^ S 5 (,7l ~ y -
400 Chestnut Street Tower II Aprill 34",91982 A /
50 BLRD-50-438/81-75 9 I i::
BLRD-50-439/81-74 g'
,q,
,:O N
.. e s
c g%
)
U.S. Nuclear Regulatory Commission
,S
, [.
o Region II
~
o*$+-
Attn:
Mr. James P. O'Reilly, Regional Administrator eQS d
)
M 101 Marietta Street, Suite 3100
}!#
Atlanta, Georgia 30303 j
Dear Mr..O'Reilly:
Dil BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - OVERPRESSURE PROTECTION IN THE DECAY HEAT REMOVAL SYSTEM - BLRD-50-438/81-75, BLRD-50-439/81 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector C. Julian on November 27, 1981 in accordance with 10 CFR 50.55(e) as NCR BLN BLP 8127. This was followed by our first interim report dated December 21, 1981. Enclosed is our second interim report. We expect to submit our next report by August 19, 1982.
If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.
Very truly yours, TENNESSEE VALLEY AUTHORITY s
ills, Mapager Nuclear Regulation and Safety Enclosure cc:
Mr. Richard C. DeYoung, Director (Enclosure)
Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 J
esc @-
' gt on 8204280333 gs
- f An Equal Opportunity Employer
//
4 ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 OVERPRESSURE PROTECTION IN THE DECAY HEAT REMOVAL SYSTEM NCR BLN BLP 8127 BLRD-50-438/81-75, BLRD-50-439/81-74
~
SECOND INTERIM REPORT Description of Deficiency -
The Decay Heat Removal (DHR) cooler inlet relief valve discharge and the cooler outlet relief valve discharge have been combined into a single discharge header. The line size of the common header is the i
same as the relief valve discharge lines. This is in violation of ASME Section III, NC3677 3(d) which states that, "in no case shall the area of such common lines be less than the combined area of all lines discharging into it." This condition exists on both trains A and B for both units. This situation arose as a result of changes made to comply with item 2.1.6.a of NUREG-0578. The 2-inch relief valve discharges were combined into a single line and connected to a 2-inch embedded drain line. This problem was discovered during a checking of the system drawings for other changes.
Interim Progress TVA is reviewing the possibility of qualifying the present piping design instead of rerouting the relief valve discharge. Using ASME Section III, NB3677.2, as a tasis, calculations are being made to determine whether, with the two relief valve discharges combined, a sufficient discharge area exists and undue back pressure is prevented.
Investigations are also continuing into the design of relief Valve discharges from other systems.
i
. -..