ML19345B941

From kanterella
Jump to navigation Jump to search
Submits Response to IE Bulletin 80-15 W/Required Oath of Affirmation Per NRC .Review of Emergency Notification Sys Conducted in Conjunction W/Bell of Pa.Sys Will Remain Functional in Event of Loss of Offsite Power
ML19345B941
Person / Time
Site: Crane  Constellation icon.png
Issue date: 09/29/1980
From: Hukill H
Metropolitan Edison Co
To: Grier B
NRC Office of Inspection & Enforcement (IE Region I)
Shared Package
ML19345B935 List:
References
IEB-80-15, TLL-435, NUDOCS 8012020799
Download: ML19345B941 (3)


Text

.

U pummmma Metropoliten Edison Company j-r Post Office Box 480

.d i'

K

.1. l Middletown. Pennsylvania 17057 717 944 4041 Writers Direct DW Nurneer September 29, 1980 TLI, 435 Office of Inspection and Enforcemen:

At:n:

3. H. Grier, Director Region I U. S. Nuclear Regulatory Cot:=ission 631 Park Avenue King of Prussia, PA 19406

Dear Sir:

Three Mile Island Nuclear Station, Uni:s 1 & 2 ( M -1 and M -2)

Operating License Nos. DPR-50 and D?R-73 Docket Nos. 50-289 and 50-320 II Bulletin 80-15

~his letter is in response to IE Sulle:in 80-15, concerning :he possible loss of emergency notification sys:em (ENS) with :he loss of offsite power.

A review of the INS telephone installation a: M vas conducted in conju-etion with Bell of Pennsylvania personnel.

The INS telephone is a dedicated line leaving M via ::ansmission/ distribution (T/D) carrier equipmen: installed on site.

This installation recuires power supplies be:h at the si:e and at Harrisburg, PA 3 ell facili:ies.

The 3 ell facilities have a ba::ery emergency power syste=.

~he telephone ecuipment, including :he T/D carrier equipment, is fed from a breaker on :he 13 IS Valve Motor Conrrol Center a: M -1.

This control center has safeguards diesel generator backup from the II engineered safeguards bus.

This supply backed up by an ensi:e emergency power source, is considered an ecually reliable pcver supply as a battery and inver:er supply.

During a loss of offsite power, the ENS vould be available af:er a =aximum 10-second delay for diesel start and load acceptance.

Ad=inistrative procedures for each uni: vill be in place prior to Nove=ber 1, 1980, requiring notifica:1on to :he NRC Operations Cen:er within one hour of the :ime one or nore of :he ENS extensions were found :; be inoperable.

A procedure, presently exists for testing :he safeguards diesels.

During i=plementation of thic l

procedure, the entire ES train is supplied power from the safeguards diesels and offsite power is severed.

l The 13 Valve 3us will be supplied power safely fro: :he II safeguards diesel.

Tnis surveillance verifies and records that " block 1" components located on

he 13 ES Valve Bus do no: trip on undervel: age during diesel load acceptance.

The breaker supplying the T/D carrier te.lephone eculpment vill reac: to under-vol: age conditions in an iden:ical =anner as the IS valve supplied from the 13 IS Valve Motor Con:rol Cen:er.

~hese tes: results vill be available for onsi:e review.

Tnis ces: is :he mos: :horough way available :o verify :ha:

acasoso 797

.B..H.-Grier, Direat;r

-2 TIL 435 extensions of the INS will rammin functional in the event of loss of offsite power.

This procedure will be implemented prior to startup.

This revir* and preparation of this report required 75 hours8.680556e-4 days <br />0.0208 hours <br />1.240079e-4 weeks <br />2.85375e-5 months <br />.

sincerely, siped H.D. Hukill H. D. Hukill Director-TMI-1 HDH:DCM:1ma ec:

R. W. Reid B< J. Snyder J. T.* Collins H. Silver D. DiIanni

~

- - - - - - - ~ ~

Director Division of Ret.ctor Operations Inspecticn U. S. Nuclear Regulatory Commission Office of Inspection and Inforcement Washington, D.C.

20555 o

METROPOLITAN EDISON COMPANY JERSEY CENTRAL POWER AND LIGHT COMPANY AND PENNSYLVANIA ELECTRIC COMPANY TEREE MILT NUCLEAR STATION, UNITS 1 & 2 Operat!

,aso Nos. DPR-50 and DPR-73 Doca c Nos. 50-289 and 50-320 This letter is submitted in support of the Nuclear Regulatory Commission request concerning the June 18, 1980 letter transmitting IE Bulletin 80-15. The response to the suoject letter is attached. Further, all statements contained in this response have been reviewed and all such stacaments made and matters set forth therein are true and correct to the best of my knowledge, information and belief.

By ector,fMI-l Sworn and subscribed to me this 3 /

dayofO b, 1980.

By d-N ff.4 Notar//Pfic PAMELA JOY LUBRECHTs Notary PMc W Atewit.

trahin C::: sty; Pa, J.j Comsmsman Expres August 4 D53

\\

-