Jump to navigation Jump to search
Ro:While Performing Required Insps Per IE Bulletin 79-01B, Determined That Documentation Did Not Exist to Prove That Splices Connecting Automatic Valve Co Solenoids Are Environmentally Qualified.Splices Being Evaluated
ML19318A076
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 06/12/1980
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
References
BSEP-80-1002, IEB-79-01B, IEB-79-1B, NUDOCS 8006180425
Download: ML19318A076 (2)


Text

  • %

OO ya Carolina Power & Light Company c c- ;,;y-~.- r-p m .

Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461 1

I June 12, 1980 l

FILE: B09-13516 SERIAL: BSEP/80-1002 )

Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, GA 30303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 & 2 LICENSE NOS. DPR-71 AND DPR-62 DOCKET NOS. 50-325 AND 50-324 CONFIRMATION FACSD!ILE FOR AN D! MEDIATELY REPORTABLE EVENT (LER 2-80-46)

Dear Mr. O'Reilly:

This facsimile confirms the conversation between Mr. J. M. Brown, Operations Manager, and Mr. R. C. Saver, of your office, at 1600 on June 11, 1980, con-carning an immediately reportable event per IE Bulletin'79-01B, Item 6. Mr.

R. Hardwick, of your office, is aware of this report as a result of his being on site for a review of the Brunswick Steam Electric Plant's forty-five day submittal in response to IE Bulletin 79-01B.

While performing the required inspections per IE Bulletin 79-01B, it was determined that documentation does not exist to prove that the splices connecting the Automatic Valve Company solenoids' pigtail leads on the safety-relief valves B21-F013(A-L) to the nuclear grade power. cables to those valves are environmentally qualified. Since the documentation does not exist that would prove them to be qualified, arid since a visual inspection of several of those splices indicates that they might not be nuclear grade qualified splices, we consider them to be nonenvironmentally qualified. Engineering is now eval-uating the splices and corrective actions will be developed before either unit is started up from its present refueling outage.

[oo9 5

//0 8 0,0 618 0V25~ J , . ,,

Mr. James P. O'Reilly June 12, 1980 This event is being reported under IE Bulletin 79-01B and Technical Specification 6.9.1.81. .

. Very truly yours, A. C. To111 son, Jr., General Manager Brunswick Steam Electric Plant RMP/jro cc: .Mr. R. . 'Hartfield Mr. V. Stello l l 1