ML17263A251
| ML17263A251 | |
| Person / Time | |
|---|---|
| Site: | Ginna |
| Issue date: | 04/20/1993 |
| From: | Mecredy R ROCHESTER GAS & ELECTRIC CORP. |
| To: | Andrea Johnson NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM), Office of Nuclear Reactor Regulation |
| References | |
| NUDOCS 9304290181 | |
| Download: ML17263A251 (8) | |
Text
A,CCELERAT DOCUMENT DIST UTION SYSTEM REGULAT ZNFORMATZON DZSTRZBUTZO STEM (RZDS)
ACCESSION NBR:9304290181 DOC.DATE: 93/04/20 NOTARIZED: NO DOCKET FACIL:50-244 Robert Emmet Ginna Nuclear Plant, Unit 1, Rochester G
05000244 AUTH.'NAME AUTHOR AFFILIATION MECREDY,R.C.
Rochester Gas 6 Electric Corp.
'ECIP.NAME RECIPIENT AFFILIATION JOHNSON,A.R.
Project Directorate I-3
SUBJECT:
Forwards mod to 930405 Relief Request 23 from ASME Section XI requirements for hydrostatic testing of svc water sys turbine-driven auxiliary feedwater sys,per NRC 900806 SER re third 10-yr inservice insp program.
DISTRIBUTION CODE:
A047D COPIES RECEIVED:LTR ENCL SIZE:
TITLE: OR Submittal: Inservice/Testing/Relief from ASME Code NOTES:License Exp date in accordance with 10CFR2,2.109(9/19/72).
l 05000244 RECIPIENT ID CODE/NAME PD1-3 LA JOHNSON,A INTERNAL: NRR/DE/EMEB
~~SlNB REG FILE 01 DS EIB EXTERNAL: EGSG BROWN,B NRC PDR COPIES LTTR ENCL 1
0 2
2 1
1 1
0 1
1 1
1 1
1 1
1 RECIPIENT ID CODE/NAME PD1-3 PD NUDOCS-ABSTRACT OGC/HDS1 RES MILLMANFG EGEG RANSOME,C NSIC COPIES LTTR ENCL 1
1 1
1 1
0 1
1 1
1 1
1 D
~QZZ p737C'S~ ~
NOTE TO ALL"RIDS" RECIPIENTS:
'LEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK.
ROOM Pl-37 (EXT. 504-2065) TO ELIMINATEYOUR NAME FROM DIS'I'RIDUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 15 ENCL 12
w t
///////I/////
/////////////
///////it)///
/////////////
/ ntlI rrrrrr ROCHESTER GAS AND ELECTRIC CORPORATION o
89 EAST AVENUE, ROCHESTER N.Y. 14649-0001 ROBERT C MECREOY Vice President Cinna Nuclear Prssductirsn April 20, 1993 TELEPHONE AREACODE 71B 546 2700 U.S. Nuclear Regulatory Commission Document Control Desk Attn:
Allen R. Johnson PWR Project Directorate I-3 Washington, D.C.
20555
Subject:
Ginna Nuclear Power Plant Inservice Program Quality Assurance Manual, Appendix B
ASME Section XI Required Examinations R.E.
Ginna Nuclear Power Plant Docket No. 50-244 Ref.(a):
Letter from R.
C. Mecredy (RGE), to A. R. Johnson (NRC),
to
Subject:
Quality Assurance Manual Revision, Appendix B, dated January 12, 1993 (b): Letter from A. R. Johnson (NRC), to R.C. Mecredy (RGE),
Subject:
Third 10-year In Service Inspected Program Safety Evaluation Report dated August 6, 1990
Dear Mr. Johnson:
The purpose of this letter is to modify Relief Request f23, dated 4/5/93, which requested relief from the provisions of the ASME
- Code,Section XI requirements for hydrostatic testing for two replacement activities at Ginna Station.
Because these activities are in progress during our present refueling shutdown, action on the attached (revised) Relief Request No. 23, which is for a "one-time" use for these two activities, is requested by April 21, 1993.
REJ'It272 Ver ruly yours, Pobert C.
Me redy xc:
Mr. Allen R. Johnson (Mail Stop 14D1)
Project Directorate I-3 Washington, D.C.
20555 U.S. Nuclear Regulatory Commission Region I 475 Allendale Road King of Prussia, PA.
19406 U.S.
NRC Ginna Senior Resident Inspector r
'7l3042Ti0,181,930420, PDR
ADOCK"-05000244 P
': 'DR p
g,9
)lI I
~
rr
~ c
~
'%g()gpss L
RELIEF REQUEST f23 RELIEF REQUESTED I.
Component for Which Relief is Requested:
A.
Service Water System, Rules for Hydrostatic Testing of
- Repairs, Replacements or Modifications to pressure retaining Class 3 components.
1.
Installation of isolation valves a ~b.
c ~d.
e.f.
g, V-4611 V-4613 V-4626 V-4669 V-4738 V-4739 V-4760 B.
Turbine Driven Auxiliary Feedwater
- System, Rules for Hydrostatic Testing of
- Repairs, Replacements or Modifications to pressure retaining Class 3 components.
1.
Installation of valve V-4023 II.
ASME Requirement from which relief is r'equested:
Hydrostatic testing of Repairs, Replacements or Modifications on Class 3 systems is required by IWA-4400 which specifies that hydrostatic testing shall be performed to IWD-5223(a).
The system hydrostatic test pressure shall be at least 1.10 times the system pressure P~
for systems with Design Temperature of 200'F or less, and at least 1.25 times the system pressure P~ for systems with Design Temperature above 200'F.
The system pressure P>> shall be the lowest pressure setting among the number for safety or relief valves provided for overpressure protection within the boundary of the system to be tested.
For systems (or portions of systems) not provided with safety or 'relief valves, the system design pressure P~ shall be substituted for Pgy.
III. BASIS The first activity to be performed is the replacement of seven valves in the Class 3 Service Water System.
The second activity is the replacement of a
check valve in the Class 3 Turbine Driven Auxiliary Feedwater System.
Service Water System Seven valves within the service water system are cur'rently being replaced:
valve numbers
- 4611, 4613,
- 4626, 4669,
- 4738, 4739, and 4760.
The replacement of the valves is being performed to the 1986 edition of ASME B&PV Code,Section III.
An evaluation to establish the work area test boundaries for the valve replacements was performed as discussed below (refer to drawings 33013-1250 sheets 1-3):
V-4626:
The replacement valve is a gate valve.
Both the upstream and downstream isolations would require the use of butterfly type isolation valves, thus making an elevated (hydrostatic) pressure test impractical.
(see Relief Request f14 approved in Reference b)
V 4611' 4669/V 4738' 4739' 4760/V 4613 The first five replacement valves are gate valves and serve as loop cross-connects.
V-4613 is a butterfly type design and serves as a loop isolation valve.
In order to isolate the selected areas for replacement, freeze seals would be required to maintain some systems supplied by the Service Water System operational.
The use of freeze seals as isolation boundaries is not feasible.
In order to establish test boundaries, complete service water loops would be required to be isolated, thus creating an operational hardship resulting in a reduction in plant safety due to rendering certain critical operational and safety related equipment unavailable.
Turbine Driven Auxiliary Feedwater System The work activity being performed'is the replacement of check valve 4023 in the recirculation test line.
The Code used for this work is the 1989 edition of ANSI B31.1.
Once the valve is installed, the pipe section cannot be isolated to perform the elevated (hydrostatic) pressure test.
Referring to drawing 33013-1237, boundaries for the work area would be the pump suction valves (V-4024
& 4098),
the pump discharge valve (V-3996) and downstream flow control valve V-4291.
Both V-3996 and V-4291 are not designed for isolation applications, and would require the installation of test blocks.
Installation of these blocks was found to be impractical.
Part of the work area would incorporate piping having a design pressure of 150 psi, with a required test pressure of 2304 psi, therefore, an unacceptable condition would exist.
Installation of a test block at the discharge of the pump was reviewed and found to be impractical because disassembly of the pump would be required.
Proposed Alternate Method:
ALTERNATIVE PRESSURE TEST REQUIREMENT FOR WELDED REPAIRS OR INSTALLATION OF REPLACEMENT ITEMS BY WELDING For Class 3
Using ANSI B31.1 and ASME B 6
PV Code Case N-416 as a basis for relief, Rochester Gas and Electric considers the following alternative requirements to be acceptable:
1 ~
2 ~
NDE shall be performed in accordance with the methods and acceptance criteria of Subsection ND of the 1986 Edition of Section III.
Additional NDE also is performed by dye penetrant testing of the root pass weld for the service water valves.
For V-4023 a surface, examination.will be performed.
Prior to, or immediately upon return to service, a
VT-2 visual examination shall be performed in conjunction with an inservice or functional leakage
- test, using he 1986 Edition of Section XI, in accordance with IWA-5000, at nominal operating pressure and temperature.
This code required test pressure and the nominal system pressure at.
which a
leak test will be performed as proposed are shown in the table below:
SWS Valves V-4611 V-4613 V-4626 V-4669 V-4738 V-4739 V-4760 Code Req'd Test Press 165 psig 165 psig 165 psig 165 psig 165 psig 165 psig 165 psig Test Press to be Performed(1) 75 psig (Nom.)
75 psig (Nom.)
75 psig (Nom.)
75 psig (Nom.)
75 psig (Nom.)
75 psig (Nom.)
75 psig (Nom.)
(1)
Test pressure reflects system operating pressure of nominal 75 psig The test pressure (and nominal operating pressure) is considered adequate to detect potential leakage after performing the replacement.
AFW Valve V-4023 Code Req'd Test Press 2304 psig Test Press to be Perform(2) 1100 (Nom)
(2)
Test pressure reflects system operating pressure of nominal 1100 psig.
3.
Use of this Relief Request will be documented on the NIS-2 Form for the Replacement.
c 4