WSES-FSAR-UNIT-3 TABLE 9.5.1-1 (Sheet 1 of 4)
Revision 13 (04/04)
TABULATION OF DOORS WHICH ARE LOCATED WITHIN FIRE WALLS
¨ (DRN 00-1087, R11)
Door Location No.
RAB/No.
A" LABEL "B" LABEL EQUIVALENCE NOTES D7 8A, 8C X(DOOR)
X(FRAME) b D9 8B, 8C X(DOOR)
X(FRAME) b D10 Vestibule (EL. +21)
X D11 8C X
D14 13, 8C X
D15 12, 8C X
D17 8B X
D18 8A, 23 X
¨ (DRN 02-1351, R12-B)
(DRN 02-1351, R12-B)
D20 8C X
D21 23, 25 X
D22 23, 25 X
D23 15, 23 X
D24 15, 23 X
b D25 16, 23 X
D26 23 X
D28 22 a
D29 16, 23 X
b D30 16, 17 X
D31 23 X
D32 11, 8C X
D34A CTA c
D35 25, CTA a, b D36 25, CTA a, b D37 FHB, CTA a, b D38 21, 23 X
D39 20, 23 X
D40 19, 23 X
D41 18, 23 X
D42 17, 23 X
D43 23 X
D44 9, 8C X
D46 24, 25 X
b D47 24, 25 X
b D51 8B, CTB a
D53 8B X
¨ (DRN 03-993, R13)
(DRN 03-993, R13)
(DRN 00-1087, R11)
D59 TGB X
D60 TGB X
D61 TGB X
D63 TGB X
WSES-FSAR-UNIT-3 TABLE 9.5.1-1 (Sheet 2 of 4)
Revision 11 (05/01)
TABULATION OF DOORS WHICH ARE LOCATED WITHIN FIRE WALLS
Door Location No.
RAB/No.
"A" LABEL "B" LABEL EQUIVALENCE NOTES D70 Vestibule (EL. +46)
X D71 1C X
b D72 3
X D72A 3
X D72B 3
X D75 3, 1C X
b D77 1A, 1C X
b D78 1D, 1C X
b D80 1A, 1C X
D81 3, 1D X
D84 1A, 1C X
b D85 1B, 2 X
b D87 2
X D91 1A, 1D X
b D96 2, Roof E a, b D97 2, Roof W a, b D98 2
X D99 1B, 1C X
D101 27 X
D107 27 X
AD110 27, 3A X
D128 5
X b
AD129 1E, 23 X
D131 30 X
D136 30 X
D141 30, 31 X
b D142 30, 31 X
D143 30, 31 X
D144 30, 31 X
D146 31 X
D149 31 X
D150 30, 31 X
D151 30, 31 X
D161 31, 32 X
b D163 34, 39 X
b D165 39 X
D166 39 X
D167 33, 39 X
b D170 36, 39 X
b D172 39 X
D173 39 X
D174 5, 3 X
b D175 1E, 7A X
b D176 3
X D178 1E, 5 X
b D179 5, 6 X
b D186 3A X
WSES-FSAR-UNIT-3 TABLE 9.5.1-1 (Sheet 3 of 4)
Revision 11 (05/01)
TABULATION OF DOORS WHICH ARE LOCATED WITHIN FIRE WALLS
Door Location No.
RAB/No.
"A" LABEL "B" LABEL EQUIVALENCE NOTES D192 6, 1E X
b D194 6, 25 X
D204 FHB, CTB X
D206 FHB, CTA X
D208A 7C, 7B X(DOOR)
X(FRAME) b D208B 7C, 7A X(DOOR)
X(FRAME) b D209A 7D, 7B X(DOOR)
X(FRAME) b D209B 7D, 7A X(DOOR)
X(FRAME) b D217 22, 23 X
D218 7B, 3 X
b D219 7A, 3 X
b D220 23, 31 X
D221 23, 31 X
D222 23, 31 X
D228 3, TGB a
D242 33, 39 X
D245 38, 39 X
D246 37, 39 X
D250 33, 35 X
b D252 39 X
b D252A 39 X
b D256 1A, 1C X
D259 1A, 1C X
b D261 1C X
D263 23 a, b D265 2
a, b D266 15A a, b D270 16A a, b Personnel Lock 32, RCB b
AAL1 RCB, CTA a, b RCD 100 1A, 1C X
Escape Lock RCB, CTA c
RAB Elevator X
Shaft Doors RAB D258 X
WSES-FSAR-UNIT-3 TABLE 9.5.1-1 (Sheet 4 of 4)
Revision 11 (05/01)
Notes:
(DRN 00-1087) a.
Door has been approved by the exemption/deviation process as documented in NUREG-0787 Supplement 3 as acceptable for Appendix A to BTP ASB 9.5-1 purposes.
b.
Door has been approved by the exemption/deviation process as documented in NUREG-0787 Supplement 8 as acceptable for Appendix R to 10CFR50 purposes.
c.
Door has been evaluated and found acceptable as a fire door using the guidance of Generic Letter 86-10.
WSES-FSAR-UNIT-3 TABLE 9.5.1-2 (Sheet 1 of 2)
Revision 15 (03/07)
FIRE PROTECTION SYSTEM FAILURE MODE AND EFFECTS ANALYSIS Component Failure Mode Probable Cause Effect on System Inherent Self-Regulating Measures Control Room Indication Remarks
(DRN 06-874, R15)
- 1) Jockey Pump Failure to start or stops running Loss of power, or mechanical malfunction, or controller trouble.
Fire main pressure continues to drop Motor driven fire pump starts
- 1. Jockey Pump Trouble
- 2. Motor driven fire pump running.
Jockey pump is used to maintain fire main pressure and its loss does not affect the systems firefighting capability.
(DRN 06-874, R15)
- 2) Motor driven fire pump Failure to start or stops running Loss of power, or mechanical malfunction, or controller trouble.
Loss of pumping capability and fire main pressure continues to drop.
First diesel pump automatically starts on drop in fire main pressure.
- 1. First diesel pump running.
- 2. Loss of power to motor driven fire pump.
1st diesel driven fire pump will provide adequate capacity to yard.
- 3. Motor driven fire pump "trouble."
- 3) First diesel driven fire pump Failure to start or stops running Loss of battery starting capa-bility and/or engine trouble.
Loss of pumping capability and fire main pressure continues to drop.
Second diesel pump automatically starts on further drop in fire main pressure.
- 1. Second diesel fire pump running.
- 2. First diesel fire pump "trouble."
2nd diesel driven pump is a standby fire pump which will provide adequate capacity to the yard fire loop. If this pump is activated, the system is considered to have an active single failure.
(DRN 06-874, R15) 4a) Underground yard loop Pipe rupture (under fire condition)
Deteriorated pipe condition Loss of water supply of fire Motor and possibly diesel driven fire pumps will start.
- 1. Jockey Pump Running.
- 2. Area fire alarms.
- 3. Motor and/or diesel driven fire pump running alarms.
Post indicating valves will be used to isolate damaged poriton of the loop. Valving is arranged to ensure a continued water supply to all remaining sections of the loop.
4b) Underground loop Pipe rupture yard (no fire condition)
Deteriorated pipe condition Water starts flowing at break.
Motor and possibly diesel driven fire pumps will start.
- 1. Jockey Pump Running.
- 2. Motor and/or diesel driven pump running alarms.
Post indicating valves will be used to isolate damaged portion of the loop. Valving is arranged to ensure a continued water supply to all remaining section of the loop.
(DRN 06-874, R15)
WSES-FSAR-UNIT-3 TABLE 9.5.1-2 (Sheet 2 of 2)
Revision 11 (05/01)
FIRE PROTECTION SYSTEM FAILURE MODE AND EFFECTS ANALYSIS Component Failure Mode Probable Cause Effect on System Inherent Self-Regulating Measures Control Room Indication Remarks
- 5) FPS stand-pipe Pipe rupture (riser)
Deteriorated pipe condition or accidental damage.
Loss of hose con-nections supplied by riser.
Motor and possibly diesel driven fire pumps will start.
- 1. Motor and diesel engine driven fire pump running alarms.
Interior OS&Y control valves at base of riser provide isolation of that riser and discontinuation of flow.
- 6) FPS auto-matic fire suppression systems Pipe rupture (no fire condition)
Deteriorated pipe condition or accidental damage.
Loss of fire sup-pression system for protection of area, equipment or components involved.
Motor and possibly diesel driven fire pumps will start.
- 1. Motor and/or diesel driven fire pump running alarms.
- 2. Alarm check valve flow alarms (wet pipe systems) or deluge control valve operating alarms (pre-action, and water spray systems).
Manual shutoff of water supply at system main OS&Y valves to facilitate repair.
WSES-FSAR-UNIT-3 TABLE 9.5.1-3 (Sheet 1 of 4)
Revision 301 (09/07)
FIRE AREAS/ZONES Elevation Number Fire Area/Zone Designation (Ft. MSL)
Figure No.
<<(EC-5000081435, R301)
RAB 1 Control Room Complex
+46.00 9.5.1-6
ø(EC-5000081435, R301)
RAB 1A Control Room Proper
+46.00 9.5.1-6 RAB 1B Control Room H&V Room
+46.00 9.5.1-6 RAB 1C Control Room Emer. Living Quarters
+46.00 9.5.1-6 RAB 1D Computer Room
+46.00 9.5.1-6 RAB 1E Cable Vault
+35.00 9.5.1-21 RAB 2 H&V Mechanical Room
+46.00 9.5.1-6
+69.00 9.5.1-15
+91.00 9.5.1-6 RAB 3 HVAC Equipment Room & Corridor
+35.00 9.5.1-6
& Vestibule
+46.00 9.5.1-21 RAB 3A H&V Room, Elevator Machine Room
- 4.00 9.5.1-4
& Elevator Shaft
+ 7.00 9.5.1-10
+21.00 9.5.1-5
+35.00 9.5.1-21
+46.00 9.5.1-6
+69.00 9.5.1-6 RAB 5 Electrical Penetration Area B
+35.00 9.5.1-21 RAB 6 Electrical Penetration Area A
+35.00 9.5.1-21 RAB 7 Relay Room Envelope
+35.00 9.5.1-21 RAB 7A Relay Room 'A'
+35.00 9.5.1-21 RAB 7B Relay Room 'B'
+35.00 9.5.1-21 RAB 7C Relay Room (Isolation Panel)
+35.00 9.5.1-21 RAB 7D Relay Room 'AB'
+35.00 9.5.1-21 RAB 8 Switchgear Envelope
+21.00 9.5.1-5 Dwg. G210 and Dwg. G1368 RAB 8A Switchgear Room A
+21.00 9.5.1-5
WSES-FSAR-UNIT-3 TABLE 9.5.1-3 (Sheet 2 of 4)
Revision 11-A (02/02)
Elevation Number Fire Area/Zone Designation (Ft. MSL)
Figure No.
RAB 8B Switchgear Room B
+21.00 9.5.1-5 Dwg. G210 and Dwg. G1368 RAB 8C Switchgear Room A/B
+21.00 9.5.1-5 RAB 9 Auxiliary Control Panel
+21.00 9.5.1-5 RAB 10 Deleted RAB 11 Battery Room 3BS
+21.00 9.5.1-5 RAB 12 Battery Room 3ABS
+21.00 9.5.1-5 RAB 13 Battery Room 3AS
+21.00 9.5.1-5 RAB 14 Deleted RAB 15 Emergency Diesel Generator 3BS
+21.00 9.5.1-5 RAB 15A Emergency Diesel Oil Feed Tank B Space
+46.00 9.5.1-6 RAB 16 Emergency Diesel Generator 3AS
+21.00 9.5.1-5 RAB 16A Emergency Diesel Oil Feed Tank A Space
+46.00 9.5.1-6 RAB 17 Component Cooling Water Heat Exch. B
+21.00 9.5.1-5 RAB 18 Component Cooling Water Heat Exch. A
+21.00 9.5.1-5 RAB 19 Component Cooling Water Pump A
+21.00 9.5.1-5 RAB 20 Component Cooling Water Pump AB
+21.00 9.5.1-5 RAB 21 Component Cooling Water Pump B
+21.00 9.5.1-5
¨(DRN 00-1054)
RAB 22 Hot Tool Room
+21.00 9.5.1-5 (DRN 00-1054)
RAB 23 Corridor Area & Common Passageways
-35.00 9.5.1-3
- 4.00 9.5.1-4
+21.00 9.5.1-5
+46.00 9.5.1-6
WSES-FSAR-UNIT-3 TABLE 9.5.1-3 (Sheet 3 of 4)
Revision 15 (03/07)
Elevation Number Fire Area/Zone Designation (Ft. MSL)
Figure No.
RAB 23A Radioactive Pipe Chase
-15.00 9.5.1-3
- 4.00 9.5.1-4 9.5.1-13
+21.00 9.5.1-5 Dwg. G210 and Dwg. G1368
+35.00 9.5.1-21 RAB 24 Decontamination Room - Hot Machine
+21.00 Dwg. G210 and Shop Dwg. G1368 RAB 25 Equipment Access Area
+21.00 Dwg. G210 and Dwg. G1368 RAB 26 Deleted
(DRN 99-2476, R11)
RAB 27 Mechanical - Electrical Equipment, HVAC
+ 7.00 9.5.1-10 Equipment and Administrative Area
(DRN 99-2476, R11)
RAB 28 Deleted RAB 29A Deleted RAB 29B Deleted RAB 30 Administration Area (Health Physics)
- 4.00 9.5.1-4 RAB 31 Corridors & Passageways
- 4.00 9.5.1-4 RAB 32 Pipe Penetrations; Auxiliary Component
-35.00 9.5.1-13 Cooling Water Pumps
- 4.00 9.5.1-13 RAB 33 Shutdown Cooling Heat Exch. A&B
-35.00 9.5.1-3 RAB 34 Valve Galleries
-15.50 9.5.1-3 RAB 35 Safety Injection Pump Area B
-35.00 9.5.1-3 RAB 36 Safety Injection Pump Area A
-35.00 9.5.1-3
(DRN 06-874, R15)
RAB 37 Emergency Feedwater Pump A
-35.00 9.5.1-3 RAB 38 Emergency Feedwater Pump B
-35.00 9.5.1-3
(DRN 06-874, R15)
WSES-FSAR-UNIT-3 TABLE 9.5.1-3 (Sheet 4 of 4)
Revision 10 (10/99)
Elevation Number Fire Area/Zone Designation (Ft. MSL)
Figure No.
RAB 39 General Area
-35.00 9.5.1-3
- 4.00 9.5.1-4 RAB 40 Diesel Oil Storage Tank A
-35.00 9.5.1-13 RAB 41 Diesel Oil Storage Tank B
-35.00 9.5.1-13
RCB Reactor Containment Building ALL 9.5.1-13 Dwg. G210 and Dwg. G1368 9.5.1-15
FHB Fuel Handling Building ALL 9.5.1-11
CTA Cooling Tower Area "A"
-35.00 Dwg. G210 and Envelope
+21.00 Dwg. G1356
CTB Cooling Tower Area "B"
-35.00 Dwg. G210 and Envelope Dwg. G1356
Roof E Roof East
+46.00 9.5.1-15 Roof W Roof West
+46.00 9.5.1-15
WSES-FSAR-UNIT-3 TABLE 9.5.1-4 (Sheet 1 of 4)
Revision 13 (04/04)
¨ (DRN 03-993, R13)
Table 9.5.1-4 (Sheet 1 of 4) Intentionally Deleted (This information is currently described in Section 9.5.1.3.2, Fire Area-by-Fire Area Analysis)
(DRN 03-993, R13)
WSES-FSAR-UNIT-3 TABLE 9.5.1-4 (Sheet 2 of 4)
Revision 13 (04/04)
¨ (DRN 03-993, R13)
Table 9.5.1-4 (Sheet 2 of 4) Intentionally Deleted (This information is currently described in Section 9.5.1.3.2, Fire Area-by-Fire Area Analysis)
(DRN 03-993, R13)
WSES-FSAR-UNIT-3 TABLE 9.5.1-4 (Sheet 3 of 4) Revision 13 (04/04)
¨ (DRN 03-993, R13)
Table 9.5.1-4 (Sheet 3 of 4) Intentionally Deleted (This information is currently described in Section 9.5.1.3.2, Fire Area-by-Fire Area Analysis)
(DRN 03-993, R13)
WSES-FSAR-UNIT-3 TABLE 9.5.1-4 (Sheet 4 of 4) Revision 13 (04/04)
¨ (DRN 03-993, R13)
Table 9.5.1-4 (Sheet 4 of 4) Intentionally Deleted (This information is currently described in Section 9.5.1.3.2, Fire Area-by-Fire Area Analysis)
(DRN 03-993, R13)