Where:

T is measured RCS T, °F.

T0 is the indicated T at RATED POWER, °F.

s is the Laplace transform operator, sec-1.

T is the measured RCS average temperature (Tavg), °F.

T' is the nominal Tavg at RATED POWER, < [*] °F.

K4 < [*]

K5 > [*]/°F for decreasing Tavg K6 > [*]/°F when T > T'

[*] / °F for increasing Tavg

[*]/°F when T< T' t3 > [*] sec f(I) = [*]

The values denoted with [*] are specified in the CORE OPERATING LIMITS REPORT.

The channels maximum Trip Setpoint shall not exceed its computed Trip Setpoint by more than 2.0% of the T span. (Note that 2.0% of the T span is equal to 3.0% of T Power.)

(f) Low reactor coolant loop flow - 91% of normal indicated loop flow as measured at elbow taps in each loop (g) Low reactor coolant pump motor frequency - 57.5 Hz (h) Reactor coolant pump under voltage - 70% of normal voltage

3. Other reactor trip settings (a) High pressurizer water level - 89.12% of span (b) Low-low steam generator water level - 16% of narrow range instrument span (c) Low steam generator water level - 19% of narrow range instrument span in coincidence with steam/feedwater mismatch flow - 1.0 x 106 lbs/hr (d) Turbine trip (e) Safety injection - Trip settings for Safety Injection are detailed in TS Section 3.7.

TS 2.3-3 Amendment Nos.