W3F1-2004-0107, Supplement to Amendment Request NPF-38-249

From kanterella
(Redirected from ML043080403)
Jump to navigation Jump to search

Supplement to Amendment Request NPF-38-249
ML043080403
Person / Time
Site: Waterford Entergy icon.png
Issue date: 10/29/2004
From: Mitchell T
Entergy Nuclear Operations, Entergy Nuclear South
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NPF-38-249, W3F1-2004-0107
Download: ML043080403 (6)


Text

-- Entergy Entergy Nuclear South Entergy Operations. Inc.

17265 River Road Killona, LA 70057 Tel 504-739-310 Fax 504-739-6698 tmitchl@entergy.corn W3F1 -2004-0107 Timothy G. Mitchell Director, Engineering Waterford 3 October 29, 2004 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

SUBJECT:

REFERENCES:

Supplement to Amendment Request NPF-38-249 Extended Power Uprate Waterford Steam Electric Station, Unit 3 Docket No. 50-382 License No. NPF-38

1. Entergy Letter dated November 13, 2003, 'License Amendment Request NPF-38-249 Extended Power Uprate"
2. Entergy Letter dated May 7, 2004, "Supplement to Amendment Request NPF-38-249 Extended Power Uprate"
3. Entergy Letter dated October 29, 2004, "Supplement to Amendment Request NPF-38-249 Extended Power Uprate"
4. Entergy Letter dated July 14, 2004, "Supplement to Amendment Request NPF-38-249 Extended Power Uprate"

Dear Sir or Madam:

By letter (Reference 1), Entergy Operations, Inc. (Entergy) proposed a change to the Waterford Steam Electric Station, Unit 3 (Waterford 3) Operating License and Technical Specifications to increase the unit's rated thermal power level from 3441 megawatts thermal (MWt) to 3716 MWt.

As committed to in Reference I and mentioned in Reference 2, Entergy performed confirmatory testing of the emergency Diesel Generator (DG) fuel oil consumption rate to validate the consumption rate assumed in the analysis supporting the Extended Power Uprate (EPU). During reviews of these test results, Entergy discovered that instrument uncertainties had not been adequately addressed in the supporting analysis and therefore the assumptions used in support of the EPU were non-conservative. As a result, a revised basis for showing that acceptable fuel oil inventories are available in support of the EPU based on the existing licensing basis has been provided for NRC staff review in Reference 3. Therefore, the information in Reference 3 supersedes information regarding the use of a DG fuel oil consumption rate less than that provided by the vendor previously submitted in Reference 1 (i.e., portions of Section 2.5.8.1 in Attachment 5) and Reference 2 (i.e., the response to Question 10 in Attachment 1).

oc

W3Fl-2004-01 07 Page 2 of 3 Post-EPU DG load summaries are attached to this letter providing updated information and supercede the load summaries previously provided in Reference 2. For comparison, the pre-EPU DG load summaries are located in Final Safety Analysis Report Table 8.3-1.

The no significant hazards consideration included in Reference 4 is not affected by any information contained in this letter. There are no new commitments contained in this letter.

If you have any questions or require additional information, please contact D. Bryan Miller at 504-739-6692.

I declare under penalty of perjury that the foregoing is true and correct. Executed on October 29, 2004.

Sincerely, TGM/dbm

Attachment:

Updated Emergency Diesel Generator Load Summaries

W3FI-2004-0107 Page 3 of 3 cc:

Dr. Bruce S. Mallett U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011 NRC Senior Resident Inspector Waterford 3 P.O. Box 822 Killona, LA 70066-0751 U.S. Nuclear Regulatory Commission Attn: Mr. Nageswaran Kalyanam MS O-7D1 Washington, DC 20555-0001 Wise, Carter, Child & Caraway Attn: J. Smith P.O. Box 651 Jackson, MS 39205 Winston & Strawn Attn: N.S. Reynolds 1400 L Street, NW Washington, DC 20005-3502 Louisiana Department of Environmental Quality Office of Environmental Compliance Surveillance Division P. O. Box 4312 Baton Rouge, LA 70821-4312 American Nuclear Insurers Attn: Library Town Center Suite 300S 29t S. Main Street West Hartford, CT 06107-2445

Attachment To W3FI -2004-0107 Updated Emergency Diesel Generator Load Summaries

EMERGENCY DIESEL GENERATOR A LOADING SEQUENCE (STEADY STATE)

CD n ° w._

-.L. _=...........

LOAD WITH LOSS OF OFFSITE POWER O r 3 EOUIPMENT NOTES RATED RUNNING SKVA TIME LOCA MSLB SHUTDOWN g

0 g KW KVAR KW KVAR KNW K/AR b,

LOAD

SUMMARY

0 0-10s :Generator Starts 10-10.5s:Load Block Ia 336.66 274.56 336.66 274.56 322.24 260.14 10.5-11s:Load Block lb 336.66 274.56 336.66 274.56 327.19 260.14 11-11.5s:Load Block ic 363.13 321.89 363.13 321.89 353.66 307.46 11.5-15s:Load Block 1d 1017.07 628.23 1017.07 628.23 353.66 307.46 15-17s :Load Block 2a 1062.58 664.11 1062.58 664.11 399.17 343.34 17.27s Load Block 2b 1884.36 1222.28 1884.36 1222.28 1205.90 856.21 27-39s :Load Block 3 2538.69 1604.38 2538.69 1604.38 1549.26 1075.52 39-51s :Load Block 4 2755.99 1695.03 2755.99 1695.03 1717.89 1138.28 51-60s :Load Block 5a 3417.75 2065.23 3417.75 2065.23 2379.65 1508.48 60-120s :MOVs Deenergize 3402.00 2049.47 3402.00 2049.47 2378.32 1507.15 120-178s:Load Block 5b 3475.48 2064.86 3475.48 2064.86 2451.80 1522.54 178-201s:Load Block 6a 3495.86 2082.38 3495.86 2082.38 2472.19 1540.06 201-210s:Load Block 6b 3496.56 2083.24 3496.56 2083.24 2472.88 1540.92 210-229s:Load Block 6c 3536.43 2112.32 3536.43 2112.32 2512.75 1570.00 229s-30m:Load Block 6d 3952.80 2370.44 3952.80 2370.44 2892.06 1805.13 30m-30m25s:Auto Load Bloc 4122.14 2500.46 4122.14 2500.46 3440.19 2080.34 30m25s-75m:Manual Loading 4121.44 2499.76 4121.44 2499.76 3440.19 2080.34..75-90m :LPSI Deenergizes 3774.38 2321.72 3774.38 2321.72 3440.19 2080.34 90m-2h:Turb Aux Deenergize 3718.42 2283.44 3718.42 2283.44 3384.23 2042.06 2h-2h50s: Manual MOV 3719.08 2284.10 3718.42 2283.44 3384.23 2042.06 2h50s-4h:MOV Deenergkze 3718.42 2283.44 3718.42 2283.44 3384.23 2042.06 4-6h

EFW Deenergize 3413.58 2095.29 3413.58 2095.29 3276.37 2030.99 6-8h: SFP Pump Start 3454.29 2121.61 3454.29 2121.61 3317.08 2057.31 8-Oh: BA Pumps Deenergize 3427.83 2108.85 3427.83 2108.85 3290.62 2044.55 10-14h Chrg Deenergize 3362.37 2064.09 3362.37 2064.09 3290.62 2044.55 14-17h: CCW Makeup 3335.73 2041.39 3335.73 2041.39 3263.98 2021.85 17-4d :de EDG Xfer pump 3314.29 2025.11 3314.29 2025.11 3242.55 2005.56 4-7d :WCT fans 5-8 de 3218.59 1969.08 2917.49 1847.90 3242.55 2005.56

Coc3 EMERGENCY DIESEL GENERATOR B LOADING SEQUENCE (STEADY STATE)

D C =

LOAD WITH LOSS OF OFFSITE POWER

°0 EQUIPMENT NOTES RATED RUNNING SKVA TIME LOCA MSLB SHUTDOWN KW KVAR KW KVAR KW KVAR 0 0 LOAD

SUMMARY

0 4.

0-10s :Generator Starts 10-10.5s:Load Block Ia 320.81 265.49 320.81 265.49 304.67 249.35 10.5-11s:Load Block lb 320.81 265.49 320.81 265.49 309.52 249.35 11-11.5s:Load Block ic 346.92 312.60 346.92 312.60 335.64 296.46 11.5-15s:Load Block id 1000.69 618.90 1000.69 618.90 335.64 296.46.15-17s :Load Block2a 1046.20 654.78 1046.20 654.78 381.15 332.35 17-27s :Load Block 2b 1864.60 1212.24 1864.60 1212.24 1184.65 844.42 27-39s :Load Block 3 2536.48 1593.94 2536.48 1593.94 1546.26 1083.26 39-51s :Load Block 4 2753.70 1684.52 2753.70 1684.52 1714.90 1145.97 51-60s :Load Block 5a 3415.56 2053.57 3415.56 2053.57 2376.75 1515.02 60-120s :MOVs Deenergize 3398.09 2036.10 3398.09 2036.10 2375.42 1513.69 120-178s:Load Block Sb 3464.22 2051.34 3464.22 2051.34 2441.54 1528.93 178-201s:Load Block 6a 3485.59 2072.50 3485.59 2072.50 2462.91 1550.10 201-210s:Load Block 6b 3486.28 2073.37 3486.28 2073.37 2463.60 1550.96 210-229s:Load Block 6c 3512.99 2096.09 3512.99 2096.09 2490.32 1573.69 229s-30m:Load Block 6d 3929.30 2354.16 3929.30 2354.16 2869.57 1808.78 30m-30m25s:Auto Load Bloc 4098.96 2480.30 4098.96 2480.30 3421.22 2079.96 30m25s-75m:Manual Loading 4098.26 2479.60 4098.26 2479.60 3421.22 2079.96,75-90m :LPSI Deenergizes 3751.92 2321.52 3751.92 2321.52 3421.22 2079.96' 90m-2h:Turb Aux Deenergize 3695.97 2283.27 3695.97 2283.27 3365.27 2041.71 2h-2h5Os: Manual MOV 3696.63 2283.93 3695.97 2283.27 3365.27 2041.71 2h5Os4h:MOV Deenergize 3695.97 2283.27 3695.97 2283.27 3365.27 2041.71 4-6h

EFW Deenergize 3391.13 2095.11 3391.13 2095.11 3256.69 2010.69 6-8h: SFP Pump Start 3431.84 2121.44 3431.84 2121.44 3297.39 2037.01 8-1Oh: BA Pumps Deenergize 3431.84 2121.44 3431.84 2121.44 3297.39 2037.01 10-14h: Chrg Deenergize 3366.44 2076.71 3366.44 2076.71 3297.39 2037.01 14-17h: CCW Makeup 3339.73 2053.98 3339.73 2053.98 3270.67 2014.28 17-4d: de EDG Xfer pump 3318.41 2037.71 3318.41 2037.71 3249.35 1998.01 4-7d :WCT fans 5-8 de 3221.69 1965.80 2919.87 1824.67 3249.35 1998.01