L-08-160, March 2008 Discharge Monitoring Report (NPDES) Permit No. PA0025615
| ML081850569 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 04/28/2008 |
| From: | Ostrowski K FirstEnergy Nuclear Generation Corp |
| To: | Office of Nuclear Reactor Regulation, State of PA, Dept of Environmental Protection, Bureau of Water Quality Management |
| References | |
| L-08-160, PA0025615 | |
| Download: ML081850569 (34) | |
Text
Beaver Valley Power Station Route 168 FENOCP.O.
Box 4 FirstEnrgy Nclear Opeting C PngY Shippingport, PA 15077-0004 April 28, 2008 L-08-160 Department of Environmental Protection Bureau of Water Quality Management Attention: DMR Clerk 400 Waterfront Drive Pittsburgh, PA 15222
SUBJECT:
Beaver Valley Power Station Discharge Monitoring Report (NPDES) Permit No.
PA0025615 Enclosed is the March 2008 NPDES Discharge Monitoring Report (DMR) for FirstEnergy Nuclear Operating Company (FENOC), Beaver Valley Power Station, in accordance with the requirements of the Permit. Attachment 1 to this letter is supplemental monitoring data for Outfall 001 (dissolved oxygen). Attachment 2 to this letter is the quarterly stormwater results. as required by Permit Condition C-21. describes a condition where simultaneous multi unit dosing inadvertently occurred during clamicide.
Review of the data indicates no permit parameters were exceeded during the month Included with the report this month are two Supplemental Laboratory Accreditation Forms for analyses performed to support permit requirements as required by 25 Pa.
Code § 252.
Should you have any questions regarding the attached and enclosed documents, please direct them. to Mr. Michael Banko at 724-682-4117.
.Sincerely, Kevin L. Ostrowski Director, Site Operations
"-XA
Beaver Valley Power Station, Unit Nos. 1 and 2 L-08-160 Page 2 Attachment(s):
- 1. Weekly Dissolved Oxygen Monitoring Results at Outfall 001
- 3. Inadvertent Treatment at Two Units Enclosure(s)
A.,Supplemental Laboratory Accreditation Form B. Discharge Monitoring Report cc:
Document Control Desk US NRC (NOTE: No new US NRC commitments are contained is this letter.)
US Environmental Protection Agency
Discharge Monitoring Report Attachment for NPDES Permit No. PA0025615 FirstEnergy Nuclear Operating Company (FENOC)
Beaver Valley Power Station L-08-160 ATTACHMENT 1 Weekly Dissolved Oxygen Monitoring Results at Outfall 001 The following supplemental dissolved oxygen monitoring data for Outfall 001 is provided as agreed.
SAMPLE DATE SAMPLE TIME VALUE UNITS 3/8/08 0900 9.18 mg/L 3/12/08 1220 8.62 mg/L 3/17/08 1030 9.23 mg/L 3/34/08 1120 9.54 mg/L 3/31/08 0915 8-47 mg/L
- Attachment 1 END -
Discharge MonitoringReport Attachment for NPDES Permit No. PA0025615 L-08-160 FirstEnergy Nuclear Operating Company (FENOC)
Beaver Valley Power Station ATTACHMENT 2 Permit Part C.21 Iron and Zinc Stormwater Monitoring Results Sample Sample Date Time Outfall Parameter Result Units 02/05/08 09:45 Outfall #003, Zinc 59 ug/l 02/05/08 09:45 Outfall #003, Iron 210 ug/I 02/05/08 11:30 Outfall #008, Zinc 36 ug/I, 02/05/08 11:30 Outfall #008, Iron 453 ug/l 02/05/08 10:10 Outfall #011, Zinc 75 ug/Il 02/05/08 10:10 Outfall #011, Iron 162 ug/I
- Attachment 2 END -
r..g Discharge Monitoring Report Attachment for NPDES Permit No. PA0025615 L-08-160 FirstEnergy Nuclear Operating Company (FENOC)
Beaver Valley Power Station Inadvertent Treatment at Two Units NPDES Permit Part C.15 provides general guidance for Beaver Valley Power Station (BVPS) in the use of biocide for clamicide treatment of macrofoulers (e.g., Asiatic clams and Zebra mussels). It also allows for the treatment of small subsystems under which BVPS performs daily treatments for microbiological control of cooling systems.
On March 27, 2008 it was discovered that a valve, manipulated on the previous day to perform a daily microbiological treatment of a Unit 2 subsystem, was found open during a clamicide treatment at Unit 1. That condition essentially caused simultaneous multi-unit dosing contrary to Permit Part C.15 (first paragraph). As soon as the condition was discovered, the effects were evaluated. It should be noted that treated water from both units mixed together before the point of detoxification and prior to discharge at the Ohio River via Outfall 001. No biocide was detected in accordance with limits established for Outfall 001 in Permit Part A, Page 2e of 14. In addition, a surveillance of the area was conducted and no harmful effects were identified.
The condition was investigated and documented in the FENOC Problem Identification and Resolution program under Condition Report CR-08-37330. The apparent cause was human performance related to less than adequate procedure use by a technician.
Corrective actions that have been implemented include strengthening the procedures that control manipulation of the valves, acquiring additional support for valve verification during the critical procedure steps, and coaching the personnel involved.
- Attachment 3 END -
f*1¶ I fI*.JIl~l. rJLLU I
M NT R
G i
II.Jt.jI Ifv%3L.
L.
iilr5 I ItiS 5 I'd I
(
lDM i 1a15 L U
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 55 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA00256157 I'01A I
PERMIT NUMBER DISCHARGE NUMBER IMONITORING PERIOD YEARI MO DAY I
YEAR MO DAY FROM 08 103 01 TO 0
03 131 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNITS 1&2 COOLG. TOWER BLWDN External Outfall No Data Indicator s
PARAMETER pH SAMPLE.
N/A N/A N/A 7.58 N/A 8.11 pH 0
1/
7 GRAB 00400 1 0 PERMIT
'ýecklo A
Effluent Gross REQUIREMENT pH SAMPLE -
NA.NA NA NA**m/
Nitrogen, ammonia total (as N)
MEASUREMENT N/A N/A N/A N/A mg/L 006101 0 PERMIT
,4-1 -".
ý -IAt, Effluent Gross REQUIREMENT
.u N/
M G
mq/L
-R SAMPLE24 HR CLAMTROL CT-1, TOTAL WATER EAUMPE N/A "N/A N/A N/A
<0.1"
<0.1"*
mg/L 0
1 / 31 COMP MEASUREMENT oi 04251 1 0 PERMIT 0
Ni When Effluent Gross REQUIREMENT N1,AV N/AL MX m /L
- D I ýCOMP21I SAMPLE
- 3.
78 MD NANANANADIY CN Flow, in conduit or thru treatment plant MEASUREMENT 32.7 37.8 MGD N/A NA N/A DAILY CONT 500501 0 PERMIT o*.*
M,.
i e* Mon*.N/A iy...OTI Effluent Gross REQUIREMENT MA DILY' M,1, Mgal/d Chlorine, total residual SAMPLE N/A N/A N/A N/A 0.01 0.03 mg/L 0
11 / 31 GRAB MEASUREMENTI 50060 1 0 PERMIT
- ,5v.
G.
Effluent Gross REQUIREMENT 1 N/A
.M..
mg/L Chlorine, free available SAMPLE N/A N/A N/A N/A 0.002 0.02 mg/L 0
CONT RCRD MEASUREMENT 500641 0 PERMIT
-2 Effluent Gross REQUIREMENT AV GEAMA*X MUM m /L C.i
.s RCD Hydrazine SAMPLE N/A N/A N/A N/A mg/L MEASUREMENT 81313 1 0 PERMIT 0
VOO
":l O
B, FN/A 0
~
'Im Effluent Gross REQUIREMENT M Q*
L
/eG NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I cetify uotde penalty of lam that this document and al1 attachments wenere frepared under my TELEPHONE DATE direction or supervisio in accoroance with. system designed to assure that qua.1e1 posorr propery gather and evaluate the information submrited. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE po, n....o manage the systen
., those parsons diretly responsible for gathedng the a7 information, the information submitted is, to the best of my knowledge and belief, true, acmurate, 724 682-7773 08 4
28 OPERATIONS and complete, I
.awaret hatfthere r
significant penalies for submitring false information.
including the possibility of fine and imprisonment fot knowing violatlons..
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTSAND EXPLANAT1ON OFANY VIOLATIONS (Reference all attachments hem)
The BETS DT-1 daily maximum was 7.6 mg/L HYDRAZINE AND AMMONIA MONITORING TO APPLY DURING PERIODS OF WET LAYUP. REPORT THE DAILY MAXIMUM FOR BETZ DT-1 WHEN DISCHARGING. THE LIMIT IS 35 MG/L AS A DAILY MAX.
- Not in Wet layup this Period. ** One Clamicides this period 3/26-3/27. **0. I mg/L is minimum detectable level. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (rev. 01106)
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 56 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER 002A DISCHARGE NUMBERI DMR MAILING ZIP CODE:
150770004 MAJOR (SUBROS)
INTAKE SCREEN BACKWASH External Outfall No Data Indicator D
MONITORING PERIOD YEARI MO DAY YEAR MO -DAY FROM 08 03 01 TO 108 03 31 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS Flow, in conduit or thru treatment plant MamilfrF61M~N 0.006 1
0.046 1 MGD N/A N/A N/A N/A 1/7 EST 50050 1 0 PERMIT R
W6n1
-aq.M*,*
1 t
" *eEM Effluent Gross REQUIREMENT DA1 AYM), j1 Mgaf/d L
L I
NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of law that this documentand an ll attachments iwere prepared under my TELEPHONE DATE direction or supervision in -
enormo wth a System designed to assote that qualitiad personnel properly gather and evaluate the information Submnitted. Based on my Inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE p.erons who na..gtte system.
or.t.... persons directly responsibleforgt lngth.
724 682-7773 08 04 28 informotion, the Information Submitted 15, to the best of my knowM g
!nele
,h tr.e
- waclrae, O PERATIO NS and'complete. I am......that ther are.. Significant pena~ltes for submitting false information, including the possibility of fine and imprisonment for knowng violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all afttchments here)
Computer Generated Version of EPA Form 3320-1 (rev. 01106)
DISCHARGE MONITORING REPORT (DMR)
OMB No, 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM Page 57 PA002561 PERMIT NUMBE 003A 1
DISCHAR--NMR DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05) 003 External Outfall MONITORING PERIOD YEAR MO I DAY YEAR MO DAY FROM 08 03 01 TO 108 103 31 No Data IndicatorD1 NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of Im thatthli danumant end all attachments wir yrepared onden hy TELEPHONtE DATE direction ot supervision in accordance with. aystem desIgned to attuh e that qu-liPfeed upnoenM l properly gat her.nd evaluate tha informatitn
.ubm..td.
B.... on my inquiry ot person or.--
Kevin L. Ostrowski, DIRECTOR OF SITE p....
- who managegthe systn.., orthose parsons directly reponslblefor gatheri.ngthe724 OPERAo~~*
TIO NS
,information.
the inf--or-ation submitted Is. to the best of mry knowiadge and belief tue, 72tru
- 6ccur0te, OP E RATIO N S and complete. I a..nt..re that the ta.t. signiflcant penalties for submitting false information, including the possibility of finle and imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
THE FLOWS FOR OUTFALLS 103, 203, 303, AND 403 ARE TO BE TOTALED AND REPORTED AS THE 003 FLOW.
Computer Generated Version of EPA Form 3320-1 (rev. 01/06)
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM Page 58 PA0025615 004A PERMIT NUMBER DISCHARGE NUMBER MONITORING PERIOD YEARI MO I DAY YEAR MO DAY FROMI 08 1 03 1 01 TO
,08 1 03 1 31 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT ONE COOLG TOWER OVERFLOW External Outfall No Data Indicator[j PARAMETER pH 00400 1 0 Effluent Gross QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE f
VALUE.
UNITS VALUE VALUE VALUNITS I
I bAMPLb MEASUREMENT PERMIT REQUIREMENT I
N/A N/A I
~7*~3/4~ii~CG-
¶2 Flow, in conduit or thru treatment plant SAMPLE MEASUREMENTI I
I 50050 1 0 PERMIT 611,Mf
~ky
?4AR Effluent Gross REQUIREMENT I,.*
AtLY. MX Mgal/d Chlorine, total residual SAMPLE N/A MEASUREMENT 500601 0 PERMIT 00*0*,.1 N/A y1 5,':
W,:ekjY*,.*GRAB Effluent Gross REQUIREMENT GRAC-TlXm/
Chlorine, free available M
AMPLE N/A MEASUREMENT 50064 1 0 PERMIT
~Wl-Gi~
Effluent Gross REQUIREMENT
-6 A'JAG.
M m/L0 NAMETITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of I.w that this aouurnent end all attachments were prepared under my TELEPHONE DATE direction or supervislon In accordance won. Ssotemr desligned to.surm ftrat quaelfif
-iedpaono properly gather and evaluate the information submitfed. Based an my inquiry of the parton 0o Kevin L. Ostrowski, DIRECTOR OF SITE p,..
re.
h mana.ge th.esy..
thoser
.... h, dlr.ly, mpcl.o folrgarrlgth.I g -
724 682-7773 08 04 28 lnforVat/n, the intformation submittfed Is, to the best of my knowfadge and belief, t-u,
- cut, OPERATIONS and oomplete. I a.. awa that there
.sgnilficant penareis for submitting false informati SP...
including the possibility of fine and Imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR
'I NM E ER M
TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
Computer Generated Version of EPA Form 3320-1 (ray. 01/06)
NA I IUI*NML I-ULLU I/I1t' I l,
l n-\\ r.
DISCHARGE MONITORING REPORT (DMR)
OMB No, 2040-0004 PERMITTEE NAMEIADDRESS (include Facility Name/Location if Different)
Page 59 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER 006A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
AUX. INTAKE SCREEN BACKWASH External Outfall No Data Indicatorf-j MONITORING PERIOD YEAR MO DAY MO DAY FROM]
08 03 TO 1'08 1 03 I 31 NAMEMTITLE PRINCIPAL EXECUTIVE OFFICER cetdify under penalty of law that this document and all attachments 'were prepared under my TELEPHONE DATE drecition or bupatvision int accordance with a system designed to assura that quaified pesronnele TE E H NED T
properly gather and e-eluate the intormation submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE persons no.rna e tre system, or. tose persons tiractly responsible for gahring ti*re 724 682-7773 08 04 28 infornmtlon, the informatlon submitted Is, to the best of my knOWcedge and belief, true. accurate.
OPERATIONS and ompt.t..
am.mon at t*en. ar signiftcant penetties for submitting false information.
including the possibility of fine and imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VOLATlONS (Reference alt attachments here)
Computer Generated Version of EPA Form 3320-1 (rev, 01106)
NA I IUNAL -'ULLU I AN I UItd-
\\
LV,
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Narme/Location if Different)
Page 60 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERANMGR ENV & CHEM PA0025615 q 007A PERMIT NUMBER DISCHARGE NUMBER FMONITORING PERIOD IYEARI MO DAY I YEAR MO DAY FROMI 08 1031 0[1 TO[
08 1: 03'1-31 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
AUX. INTAKE SYSTEM External Outfall No Data Indicatorf*
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH 00400 1 0 MEASUREMENT PERMIT 77 Effluent Gross REQUIREMENT MiNIUM J
.*T'<,
u f1lF3t*
pH
,7*i*'T,"
Flow, in conduit or thru treatment plant MEASUREMENT 50050 1 0 PERMIT t
- eq.
M15h ReMn.
R
- "ý B
Effluent Gross REQUIREMENT A
- VG DILY, i;M Mgal/d
=ekIr*Q,GRAB.
Chlorine, total residual MA ME MEASUREMENT 500601 0 PERMIT
.n*
EffluentGross REQUIREMENT
'NS mgIL
~
Wel SAMPLE Chlorine, free available MAME MEASUREMENT 50064 1 0 PERMIT 2
ek.
.5A' Effluent Gross REQUIREMENT J4-a V
,AVEJAGE
- mgIL, NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I cetify under penalty of 1-that this document and e1l attchmoent= were prepared under my TELEPHONE DATE direction or supervclslon In accordance with,. system designed to assure that qualified personnfel TE E H NED T
Properly gather and evaluate the information submitted. eased on my Inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE p.eson.s
.mang.t the system, or those..
persons onsleorot.rlng th.
724 682-7773 08 04 28 Information. the Information submitted is, to the best of my ktmow~dg* aind be{lref, 72u6 2-77 0
0,2 OPERATIONS and corrrplete. I.am awarethat there am signiflcant penaft:.s for submitting SGAlsR InformOtConR I ncluding th. Possibilty of M.. old I M4 nt fo, kn SIGNATUoRE OF PRINCIPAL.r EXECrUTIVE OtFFICoER O R TYPED OR PRINTED AUTHORIZED AGENT AREA Code.
NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference oll ottachments here)
MONITORING FOR FLOW, FREE AVAILABLE CHLORINE, AND TOTAL RESIDUAL CHLORINE ARE REQUIRED ONLY DURING THOSE PERIODS OF DISCHARGE FROM THE ALTERNATE FLOW PATH OF THE REACTOR PLANT RIVER WATER SYSTEM.
Computer Generated Version of EPA Form 3320-1 (rev. 01/06)
NATIONAL POLLU I ANI UlJ.,-iMrQLt r'LttVIItl'lxr I DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 Page 61 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER 008A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 1 COOLING TOWER PUMPHOUSE External Outfall No Data IndicatorF-7 F
-MONITORING PERIOD YEAR I MO I DAY YEAR MO DAY FROMI 08 1.03 1
TO "08 1
03 1 31 PARAMETER pH QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE" VALUE VALUE UNITS MEASUREMENT 004001 0 PERMIT 6Tiee' Effluent Gross REQUIREMENT pHonhi Solids, total suspended SAMPLE MEASUREMENT 00530 1 0 PERMIT 30iOlT~iP Effluent Gross REQUIREMENTP TO*
G*"IL M
r./L G RnA6 SAMPLE OIl & grease MEASUREMENT 00556 1 0 PERMIT 20~~~'
~T~dPt Effluent Gross REQUIREMENT GRA BG A,.lEM7,.
Il/L nTe,. j Flow, in conduit or thru treatment plant SAMPLE MEASUREMENT 500501 0 PERMIT R
'g f*b*
o..
- q.
A.
Effluent Gross REQUIREMENT IiOAVG M
Mgal/d N/Akl:
4ESTIMA NAME/TITLE PRINCIPAL EXECUTIVE OFFICER ce.ttiy under penalty af lawthat this documnent and all attachments wate prepared under my TELEPHONE DATE tractlon or supervislon In accordance with a system designed to allure that qualified personnela Kevin L. Ostrowski, DIRECTOR OF SITE p.eo...ns wh m ganha..
e.the.systeo thosepe.on.
directlytresponsible tnathe 724 682-7773 08 04 28 information, the Information s ubmittedf 14, to the beat of my knoM*.edge and belief, true, accunate74627730.4 2
OPERATIONS and coptnla. I.a.ar. that the.a an. hignificant penalties for submitting SNlUE InformationP including the possibility of fine and imprlionment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VOLATIONS (Reference all attachments here)
Computer Generated Version of EPA Form 3320-1 (rev. 01106)
NATIONAL POLLUTANT DISCHARU-
"LIMINA I IUN ;'I
=
I k.M ili'drUro)
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM Page 62 PA0025615 010A PERMIT NUMBER DISCHARGE NUMBER MONITORING PERIOD YEAR I MO I DAY YEAR MO I DAY FROMI 08 1 03 1
TO 1 08 1 03 1 3.
DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 2 COOLING WATER External Outfall No Data Indicator-PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE
- VALUE VALUE UNITS VALUE
'VALUE VALUE UNITS pH 00400 1 0 Effluent Gross SAMPLE MEASUREMENT PERMIT N/A IN/A N/A 7.12 N/A 7.62 pH 0
1 / 7 GRAB N/A
~
I I
I U
~
~
CLAMTROL CT-1, TOTAL WATER 04251 1 0 IPffh. rant /'lrncc MEASUREMENT N/A N/A NIA N/A t
I
'k PERMIT N/A DI I:=*I I IIM IPJT
/
I 2.
7~~2~)i;*
I~
j us Ij
~~C%:W%1en mn/I Flow, in conduit or thru treatment plant MEASUREMENT 3.17 4.32 MGD N/A
/ 7 50050 1 0 PERMIT prr6.M"n2)"t
-Req
ý NA r
ARD Effluent Gross REQUIREMENT VG AlL*Y PAX Mgal/d i*
Chlorine, total residual SAMPLE N/A N/A N/A N/A 0.004 0.02 mg/L 0
1 / 7 GRAB MEASUREMENT 50060 1 0 PERMIT
..We ekl....
Effluent Gross REQUIREMENT 1N G,.
~
'SftiMA.W; mg/L Chlorine, free available MEASUREMENT N/A N/A N/A 0.004 0.02 mg/L 0
1 / 7 GRAB 500641 0 PERMIT X
Effluent Gross REURMNqAE.~E MXMM m/L<.Wel NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under penily of lowthat this document and alltachments vers prepared under my TELEPHONE DATE di-etion or supervision in accordance with a systenm dahigned to a&sur, tirst qualified prsonnal properly gatrher and evaluate the information submitted. Bated on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE persoo r.o mnrange ther. syste. ofthose persons directly responsible fora.....
724 682-7773 08 04 28 Information, the information submitted It, to the best of my kno~edge and belief. true, 724682 77 3
0te,2 O PERATIONS arrdnrpleto. t.am a..
are tha th Ore are.igni*icet petal..ti for subnittrng fal.. eInfonrmtion.
including the possibility otfine and Imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all sttachrtents there)
REPORT THE DAILY MAXIMUM FOR BETZ DT-1 WHEN DISCHARGING (24 HR. COMP.):
MG/L. (THE LIMIT IS 35 MG/L AS A DAILY MAX)
- No clamicides this period. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (rev. 01/06)
NA I I L tULLCA I M111 ITR I
RPORT (MR DISCHARGE MONITORING REPORT (DMR)
PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER S
NU011A DISCARGE NUMBERI OMB No. 2040-0004 Page 63 DMR MAILING ZIP CODE: ' 150770004 MAJOR (SUBR05)
DIESEL GEN & TURBINE DRAINS External Outfall No Data Indicator--
MONITORING PERIOD LJYEARI MO I DD I YEAR MO FDAY FROMI 08 1 03 1 TO 1 08 1I0 1 311 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION jNO.
FREQUNACYSIS MTPLE VLEX OF ANALYSIS TYPE VALUE VALUE UIS VALUE VALUE VALUE UNT Flow, in conduit or thru treatment plant ME MEASUREMENT 500501 0 PERMIT Effluent Gross REQUIREMENT 0.004 1
0.004 I MGD I N/A I
N/A I
N/A IN/A 1/7 EST I
1 Re b pqAldin Ir N/A L___
Prek 1 KA.1d IVl* *tl*
Effluent Gross REQUIREMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under penaty or law that this document and all attachments were prepared under My TELEPHONE DATE directrn or supervision in eccodance wihO a system designed to assure that qualified personnel T
L P
O ED T
properly gather and evaluate the information submitted. Based on my inquiry of the person or
/
Kevin L. Ostrowski, DIRECTOR OF SITE pt.....r. w... ranagethe system, or thosepersons directly responsible for gattherlng the......
724 682-7773 08 04 28 information, the information submitted Is, to the best of my knowledge and belief, true, eurate, OPERATIONS end nplera. I ann aware that there rer hignificant penalties for.ubmittIng falseinformation..
including the poseibility of fne and Imprisonment for knowing violations.
SIG NATURE OF PRINCIPAL EXECUTIVE OFFICER OR R
TYPED OR PRINTED AUTHORIZED AGENT ARA od NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL POLLUTANT DISCHANL*- t-LIMIr4PIh I I'4
\\..
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 Page 64 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615]
PERMIT NUMBER D
012A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
BLOWDOWN FROM THE HVAC UNIT External Outfall No Data IndicatorZ'-
F MONITORING PERIOD YEAR I MO I DAY YEAR MO DAY FROM 08 103 1
TO 08 03 131 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE
[UNIT EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH 00400 1 0 Ffflue~nt C rn*.
ME-ASE M iE MEASUREMENT 1 N/A N/A N/A 7.26 N/A 8.57 pH 0
2 / 31 GRAB PERMIT I
1 I
I~l~ -
1ý
~7' I
A4?,A~th.A olJ ftA,,,,.i.
j Copper, total (as Cu)
MEASUREMENT N/A N/A N/A N/A 0.166 0.228 mg/L 0
2 / 31 GRAB 01042 1 0 PERMIT
) *
' 'N/AN/A t Mori
'ReN/05i/.
mLmg t2ic,31 lG Effluent Gross REQUIREMENT DAILY AAm/MX mg.L...
G oBt".
Fl~, n onui o thu retmntplnt SAMPLE
- '*=<.01001NA
/A MEASUREMENT Zoinc, total (assoZn)dMEASUREMENTSM E
N/A N/A N/A N/A
}
0718 0.1882 mgIL 0
2 / 31-GRAB 01092 1 0 PERMIT 5
T r
GýR.B' Effluent Gross REQUIREMENT I
.N/A M
AVI AILYM i mg/L Month Flow, In conduIt or thru treatment plant SAMPLE
<0.001
<0.001 MGD N/A N/A N/A ON/A 1 / 31 EST MEASUREMENT
_n evltethinfion
. _n N/Ah o
500501 0 PERMIT R......
Rg17Tca t
penats fo.ubvtt*nfalsN/A P...
I Effluent Gross REURMN iM 1 M' M'
MgaI/d ~>.,
~~,Mrt$v--
SAMPLE 0
2GA Solids, total dissolved MEASUREMENTI NAm N/
NlA N/A 798 1032 mg/L 02I...RA 70295 1 0 PERMIT Req.N/A-R
,(
1?t.
GRA
,Effluent Gross REQUIREMENT
/LMO AGEN AREA C
/LEYAR__A NAME/TITLE PRINCIPAL EXECUTIVE OFFICER enie Ude petalty of em that this document and ali attachentss were pper" under try TELEPH direction or suPorvieon in eccortifonce with aSsystem destigned to assure that qualified personnel Propetly gather end evaluate tho information submitted. Basead an my inquiry of the person ot Kevin L. Ostrowski, DIRECTOR OF SITE petrona who maflage terystem, or those persnsdiretly respontsible for gathering the 724 682-7773 08 04 28 OPERATIONS and oompht. ra.
thtte.asinfcant penalties fot submritting false Informntiton, including the possibility otyfne end Imprisonment for krncing violation,.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Cod NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachrments here)a Computer Generated Version of EPA Form 3320-1 (Rev, 01/06)
NATIONAL POLLUI AN I UIbUI1 KM, A.1 CLUIVII,'OrNtM II' s.t s,..
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM Page 65 PA0025615]
PERMIT NUMBER RGU013A DISCHAR-G"E-NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
OUTFALL 013 External Outfall MONITORING PERIOD YEAR MO DAY YEAR MO IDAY FROMI 08 1 03 1 01 TOe1 08 03 31 No Data IndicatorZ" PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO..
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE
[NITS VAL=U VALUE VALUE UNITS MEASUREMENT N/A N/A N/A 6.91 I
N/A 1
7.64 1
N/A 0
1 /7 GRAB 0
1/7 GRAB 00400 1 0 Effluent Gross REQUIREMENT A
N/A el GRAýB.
oH 7 711 ý ý I y Cyanide, total (as CN)
SAMPLE MEASUREMENT N/A N/A N/A I
N/A I
<0.01*
I
<0.01*
I N/A 0
2 / 31 24 HR COMP 00720 1 0 PERMIT 0=E lI I=ftAM lUT I
- 1:
N/A n;
IaI i1 bA i
1 1
I I --
SAMPLE I
Copper, total (as Cu)MEASUREME N/A N/A NA N/ A 0.022 0.031 N/A 0
2 I 31 COMP 01042 1 0 PERM IT 7
N/A C.
.M P24 Effluent Gross REQUIREJIENT Mh, O~A
,U
- h.
, CiX mg/L Mth Chlorobenzene SAMPLE N/A N/A N/A N/A
<0.005**
<0.005**
N/A 0
2 / 31 24 HR MEASUREMENT COMP 34301 1 0 PERMIT R/AT....
Effluent Gross REQUIREMENTI mg/L Mt Flow, In conduit or thru treatment plant MEASUREMENT 0,003 0.003 MGD N/A N/A N/A N/A 2 I 31 EST 50050 1 0 PERMIT
. Req'oo..
Re...o... t N/A E
e P E
SIr7 r
i Effluent Gross REQUIREMENT I' M
.v NAMEITLE PRINCIPAL EXECUTIVE OFFICER I rnder penalty of law tht this document and a a ttachments were prepared under my TELEPHONE DATE NAMETITL PRICIPA EXE UTIV OFFCER direcio or supervision in aocand-to,nrttr a syatemt designed to assure that qualified personnel T L P O ED T
properly gather and evaluate the information submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE person, who nagethesystem or. thosrepersons directly responsibleforgrather/ng ":.rae, 724 682-7773 08 04 28 Information, the Information submited is, to the beat of my knaowadge and belief, true, accurate, OPERATIONS and ompler,. I am...aretha th ar.. era significant penalties tot submitting falseintformation, includlng the possibility of fine
- nd Imprisonment for knowing ulolailon.,
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
THERE SHALL BE NO DISCHARGE OF FLOATING SOLIDS OR VISIBLE FOAM IN OTHER THAN TRACE AMOUNTS.
- 0.01 mg/L is minimum detectable level ** 0.005 mg/L is minimum detectable level. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NA IA(JNALf GELLU ONiV O LRREPORTDMR DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 Page 66 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM PA0025615
}
101A PERMIT NUMBER DISCHARGE NUMBERI I
MONITORING PERIOD IYEARI MO IDAY YEAR MO I DAY FROMI-08 1 03 01 TO1 08 1[03 1 31 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05) 101 CHEMICAL WASTE TREATMENT Internal Outfall No Data Indicatorl--
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE VALUE VALUE UNITS VALUE VALUE VALUE UNITS OF pH bAMPLt:
MEASUREMENT 00400 1 0 PERMIT
-W.....-*GRAB Effluent Gross REQUIREMENT UMNIUM,.
,M.
IMLUM pH V
Solids, total suspended SAMPLE MEASUREMENT 005301 0 PERMIT 10 We**.....C***"**"
o" Effluent Gross REQUIREMENT DAILY MX CO/"
SAMPLE Oil & grease MEASUREMENT 005561 0 PERMIT
.Y'***y.o.....15..
'20 Effluent Gross REQUIREMENT MMLe Nitrogen, ammonia total (as N)
SAMPLE MEASUREMENT 006101 0 PERMIT 1
-r*
,eq
,o'i 61 Mon W.kly Effluent Gross REQUIREMENT MOAcG
'ALotM mg/L v-
~
~
i.
Flow, In conduit or thru treatment plant SAMPLE MEASUREMENT 500501 0 PERMIT
_P. 1.i A ILY-1.'
CONTN Effluent Gross REQUIREMENT DM.&GýWG OAwI.Y*MV Mgal/d SAMPLE Hydrazine MEASUREMENT 813131 0 PERMIT
- orn n Rnq. Mon.
- q. Mon.,
Effluent Gross REQUIREMENT
- MOAVG%
DAILY*MX mg/L
-'GAB NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of law that this document and all attachment. wete prepared under my TELEPHONE DATE direction at supervision in accordance with a system designed to seuethat qualified petsonne properly gather and evaluate the Information submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE persons
.o. *.nae the ytem, or those perons rey responsible tfot thering the 724 682-7773 08 04 28 information, the information submitted is, to the best of my knowledge and belief. true,.=crate.,
ýI 2
8
-7 30 4
2 OPERATIONS and ompilete. I ant awar that there are signlficant penarties for submitting false Information, includTng the possibility of fine and imprAsonment for knowing violation,.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT
.AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
HYDRAZINE AND AMMONIA MONITORING TO APPLY DURING PERIODS OF WET LAYUP. SAMPLES SHALL BE TAKEN AT THE DISCHARGE FROM THE CHEMICAL WASTE SUMP PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL POLLUTAN I UIbMrUt*,*'
C.iVIiII,*, I,1,.u t DISCHARGE MONITORING REPORT (DMR)
OMB No. 204040004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 67 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER 102A N DISCHARGENUMBER]
DMR MAILING ZIP CODE:
150770004 MAJOR (SUBROS) 102 INTAKE SCREEN HOUSE Internal Outfall No Data Indicator-]
I MONITORING PERIOD I
YEAR MO DAY I YEAR MO DAY FROMF 08 1"03 1 0j 1 TO 08 I03 31 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE N
EX OF ANALYSIS TYPE VALUE T
VALUE UNITS VALUE ]
VALUE VALUE UNITS N/A 7.14 N/A 7.41 pH 2 / 31 GRAB 00400 1 0 Effluent Gross NI G
1 Solids, total suspended SAMPLE MEASUREMENT N/A I
N/A N/A 20.1 28.7 mg/L 0
2 / 31 GRAB 4
- 4.
~
~
-~
-~
LEffluent Gross REQUIREMENT OAVG DAIMX
%/'xonh-Oil & grease MEASUREMENT NAPEA NA/A N/A
<5 *
<5
- mg/L 0
2 / 31 GRAB 005561 0 PERMIT
.¶"
IT c -Pe Effluent Gross REQUIREMENT
%10 AV A
%44 mglL
] K J.o.nt!-
Flow, in conduit or thru treatment plant SAMPLE
<0.001
<0.001 MGD N/A N/A N/A N/A 2 / 31 EST
- Flo, n
onui o thu retmntplnt MEASUREMENTt 500601 0 PERMIT R41 Th Req T~ li* PVr F
Effluent Gross REQUIEMEN A
BAI N/A ItSTA NAMEMTITLE PRINCIPAL EXECUTIVE OFFICER I cettify under penalty of lew that this document and all attnctments were prepared under my TELEPHONE DATE direction, or supervision in Accordance with a system designed to Assure that qualified personnelTLPHNDT pro perly gather and evaluate the information submted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE persons who man.ge the system, or those persons directly responsible for gttegthe770 in~fo mation, the Informaton submitted is, to the best of my knoviedge And beeftr....t, 724 682-7773 08 04 28 O P E R A T I O N S a nd r oo,, st e.,.....th at th e a re....n fic a n p n a lti s fo o u b t fi
, at."
Including the possibility of fine and imprisonment for kn*oyng violations, SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT THE DISCHARGE OF COLLECTED PUMP BEARING LEAKAGE PRIOR TO MIXING WITH ANY OTHER WATER.
- 5 mg/_L is minimum detectable level. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL tVULLU I/xAN I Ulrimmrr rIjim t
- ,,s,, -, -
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 68 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER 103A DISCHARGE NUMBER]
DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
SLUDGE SETTLING BASIN Internal Outfall No Data IndicatorF-D F
MONITORING PERIOD YEAR MO I DAY YEAR MO DAY FROM 08" 03 1
TO 08 03 31 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH 00400 1 0 Effluent Gross MEASUREMENT PERMIT REQUIREMENT I N/A N/A i
N/A 6.94 NIA 7.37 pH 0
4 /31 GRAB NIA-N/A V MINIMUM AI M
j T
er
~
B-t Solids, total suspended 00530 1 0
- mf Iin o'rB flri SAMPLE MFASUREMENT N/A N/A N/A N/A 10.2 13.8 mg/L 0
2 / 31 24 HR COMP MEASUREMENT PERMIT-D~lAI' IIIDCUI=Irr I
~ 1i~i~777~§ N/A
~0 t
ýAA r'fA 100I
,K"IP24 ý mn/,I Eflu n Grs IT
!~.iht~c~~m thhh V~c 3/4i tuOl~u~- ~0.~--0.iO tui~~
-,a'.,ii~*
+/-
,nON
~ ~
Flow, in conduit or thru treatment plant 50050 1 0 Effluent Gross SAMPLE MEASUREMENT PERMIT REQUIREMENT 0.022 0.034 MGD O
i
%IonMZa
/d M,0 A VG
- fm ILY JX Ma N/A N/A N/A N/A 2 / 31 EST N/A Tv-icw Mon NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I cattily unde po'lty of law that this dcument and all attachments were prepared under MY TELEPHONE DATE direction or spermislon In aoccordance with a system designedl to assure that qualified personnel propldy gather and ov.luath the informatlon submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE parsons w.ho manage the system.
or those p.. sons directly responsible
,for ather th 724 682-7773 08 04 28 information, the Intona~tion submitted IS. to the beef of my knowledge and belief, true cuse OPERATIONS and complete. I am....r that ther significant pernaflies for submitting false informstion.
iOncluTiO S thn possibilin y of fine and imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTlORIZED AGENT AREA Code j NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT THE OVERFLOW FROM THE BASIN PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL VULLU I.,AN I UIOiM rM LwM M
DISCHARGE MONITORING REPORT (DMR)
PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM
[A002561 PERMTN~E DlfSH 1A i
0M8 No. 2040-0004 Page 69 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05) 111 DIESEL GENERATOR BLDG Internal Outfall No Data IndicatorlI I
MONITORING PERIOD YEAR MO DA YEAR I MO"I DAYI FROMI 08 1 03 1
TO 08 1 031 31[1 PARAMETER pH 00400 1 0 NO.
FREQUENCY SAMPLE QUANTITY OR LOADING QUALITY OR CONCENTRATION EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS MEASUREMENT I N/A N/A N/A 7.85 N/A 8.19 pH 0
1/7 GRAB PERMIFT N/A f.JiNi MUM "A
iý e,I f GR48 Solids, total suspended SAMPLE N/*A NA N/A N/A 4
.<4*
mg/L 0
1 I 7 GRAB MEASUREMENT 0053010 PERMIT Effluent Gross REQUIREMENT
- m.
DAI m /L Oil & grease MEASRMPEN Oil graseMEASUREMENT N/A NA/A/A
<5
- 5 mg/L 01/
7 GRAB 005561 0 PERMIT l
- ....*0*
15 i
...R Effluent Gross REUIEMN G.
~
MAGm/
Flow, in conduit or thru treatment plant SAMPLE 0.002 0.002 MGD N/A N/A N/A N/A 1 / 7 EST MEASUREMENT*
50050 1 0 PERMIT pl§N/EOn.ý R~e¶-
y S-flM Effluent Gross REQUIREMENT N6IAV,.D)IL'Y MX MgaI/d NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I-nti unlder pnallty of 6lw that this document And all attachmentfs we prer n
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualifled patsonnef T
Properly gather anrd evsluat.te in* rt~finstion subm~itted.
Based on m~y Inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE personts who manage tho.ystan..
or those persons dir.ctly responsible to, gthering 724 682-7773 08 04 28 intoruingon, the inf fnm e ntion submitted Is, to the best of my knowledge and betlef, true, accurate.
OPERATIONS and Comnplete. I am..... that ther significant penaltie for submitting false inlformation,.
Including the possibility of fine and Imprisonment for kaonngntolitions.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
- 4 mg/L is minimum detectable level. ** 5 mg/L is minimum detectable level. iPc 4-m-e Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NAI tONAL lULLU I AN I L I-.-..flMr¶
- eLIlIIVtI14 I 'Jr's
- . s
-1
, 1,111 DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 70 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBER]
113A N IDISCHARGE NUMBERI DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 2 SEWAGE TMT PLANT Internal Outfall No Data Indicatorl*
MONITORING PERIOD YEAR MO I DAY IIYEAR MO DAY FROMI
,08 03 101 1 TO[
08 03 31 PARAMETER QUANTITY OR LOADING QUALITY ORCONCENTRATION, NO.
FREQUENCY SAMPLE QUATIT ORLODIN QULIT O
COCENRATONEX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS 00400 1 0 Effluent Gross MEASUREMENT PERMIT REQUIREMENT pH I'..
1Twice/P~
GRAB..
Solids, total suspended 00530 1 0 SAMPLE MIAA1URF*MFFNT MEASUREMENT,~.
.~
,rm~.an.uI Ku~~li>,;
V~~AD~4vIt?'r-PERMIT
- ~n 0~~l~
Effluent Gross REQUIREMENT
%O A
VGI
- A(L MX m/L Flow, in conduit orthru treatment plant ASAMPLE Fo.ocoo II"
!*O0~~
n o*o
-~-
~"'~
Effluent Gross REQUIREMENT r,4 o;4.'
AILY ',!X Mgal/d
~
Chlorine, total residual MEASUREMENT 50060 1 0 PERMIT T0 1 4' P
Effluent Gross REQUIREMENT IMA h
-.*,MA mg/L
, I.h.
Coliform, fecal general MERAS REMENT 74055 1 1 PERMIT o*.
20 "vcPe, Effluent Gross REQUIREMENT
%10 DRCO S.*
./100mL BOn, carbonaceous, 05 day 20 C SAMPLE 80082 1 0 PEMI Effluent Gross REQUIREMENT AUT "O AC)
C'odeL N
RMXU mgYLEAR O
D NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I certity under penalty ot lawthatthis document and al attachments were preyard unroe my TELEPHONE DATE directiorr or supTervision In accordane withT aSystem designad to TA u eR that qualified :r TH ANYEA properly gather end -vluate the Ittormiation aubmnrled. Based on my inquiry of the peroart
~f Kevin L. Ostrowski, DIRECTOR OF SITE persons woh nranage the system, or those persona directly rsponsiblefor gathering the
/ !.,o
,74 8-73 0
4 2
Intormetion, the Information submitted Ise to tire beat ot my knooiedg. and belif at rosnurae,
/"1.~L 724 682-7773 08 04 28 0OPE RATIO~N S end complete. e m ewaft thet there are significant penalties tot submitting tols Informarion, includting the possibility oftltn. end imprisonment lto knowing volations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code T-NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOL.ATIONS (Reference all attachments heret SAMPLES SHALL BE TAKEN AT OVERFLOW FROM THE CHLORINE CONTACT TANK PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL POLLU I AN I U htiUMA
.M tL..
r tIVIII4m I ItJl ) I o I v,,
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 Page 71 PERMITTEE NAMEIADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM IPA0025615 PERMIT NUMBER 203A I
DIscHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
MAIN SEWAGE TMT PLANT Internal Outfall No Data lndicator-'
IMONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 08 03 01" TO 08 03 31 PARAMETER 00400 1 0 Effluent Gross Solids, total suspended 00530 1 0
- 61,fn-irn-rc SAMPLE MEASUREMENT PERMIT oc~nIIIIorMei
~ BA A / -
Tvpow~e"ý Ier tor'p
-n/I Flow, In conduit or thru treatment plant MEASUREMENT 50050 1 0 PERMIT 0Rqý Mon.
Win:kl*?
MEASRD Effluent Gross REQUIREMENT DA, Al!
M Mgal/d,
______D Chlorine, total residual MA ME MEASUREMENT 5006010 PERMIT 1*.
3*3*
gsi r
Effluent Gross REQUIREMENT MQ0-4VG
-11 NSjI4T1X
.0mg/L M'ih SAMPLE Coliform, fecal general MEASUREMENT 74055 1 1 PERMIT I
T%%~P?
Effluent Gross REUIREMENT
~EM~#/1OOmL BOD, carbonaceous, 05 day 20 C SAMPLE MEASUREMENT 8 0 0 8 2 1 0 P E R M I T I-4*O
,OO 0 *
ý i j T w i c eP e r, E ffl u e n t G ro s s R E Q U IR E M E N T
- M b
.G..
.AIIgY m0/L NAMEMTITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of lew that this document and ail attachments vare prepared under My TELEPHONE DATE directio or superviuion In slcoordence mith is sytemn designed to assure that qualified peronnel properly gatheý,and evnluste the Information submitted. Based on My Intquily of the person 0, Kevin L. Ostrowski, DIRECTOR OF SITE perso.n ". M.nage ths.ystem,
.pers...d..on.,ponit.,ornthon.*th.
724 682-7773 08 04 28 information, the Infor atlot submittled Is. to the beat of my knowiledge and belief, true. accurteh, 72 68.7 30 4
2 OPERATIONS and complete, I...
m.r. thatthere.....signif...t penel.
etot submi.ring fatls.
Information, I
including the possibility of fine and Imprisonment for knowing vnolations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANA71ON OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT OVERFLOW FROM THE CHLORINE CONTACT TANK PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL POLLUTANT DlSCHANl*:: t-lVllVA,,V I rVI I
DISCHARGE MONITORING REPORT (DMR)
PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM PA0025615 PERMIT NUMBE AG U211A DICARGE NUMBERI OMB No. 2040-0004 Page 72 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBROS) 211 TURBINE BLDG Internal Outfall No Data Indicator D
I MONITORING PERIOD IYEARI'MO IDAY YEAR MO DAY FROMI 08 1 03 1 TO 08 03 31I PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE SEX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS j
NT X
O NLSS TP pH MEASUREMENT I N/A N/A N/A 7.15 N/A 7.74 pH 0
1/7 GRAB 004001 0 PERMIT 000*
- 11,.
Wk-j
ý rA Effluent Gross REQUIREMENT MiNlM t M MXMM lv1 pH
- Solis, ttal uspededSAMPLE Solids, total suspended MEASUEE NAN/A N/A N/A 16.1 33.0 mg/L 0
1 I 7 GRAB 0053010 PERMIT
~RA Effluent Gross REQUIREMENT mg/L Oil & grease SAMPLE N/A N/A N/A N/A
<5 *
<5 mg/L 0
1 / 7 GRAB MEASUREMENT 0055610 PERMIT EffluentGross REQUIREMENT NI M
mglL Flow, in conduit or thru treatment plant SAMPLE 0.002 0.002 MGD N/A N/A N/A N/A 1 / 7 EST MEASUREMENT 50050 1 0 PERMIT r 10,oe N-e' Effluent Gross REQUIREMENT MO.AV4.
FA M..M.al/d NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under penalty of law that tlis document andt a)) attachments wera prepared under my TELEPHONE DATE dIrection or supervision in aocordanee with a system designed to assure that quallfied personnel property goiterr and evaluatethe infotrmation submitted. Bsdo o tptt ftt oer Kevin L. Ostrowski, DIRECTOR OF SITE personwho.,
managet sstem thos,...
iretly responsible for gatheringthe
/
724 682-7773 08 04 28 Infomrmtion, the Information submitted Is. to the best of my knowledge and belief, true, octurlt.,
72'8 7
30 4
2 O PERA TIO N S
- hd oompl.., I am.
awre that the m
.. signi*.*oent P. ea, " for *ubmitting falet IInfALmE CCR O
includ*ng the posslbility otf fne and Imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
- 5 mg/L is minimum detectable level. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL POLLU IANrJ UI MP¶.MI-IUZ rLt
- rrtn, I
o..-..--. %... -,
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 73 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATrN: DONALD J SALERAJMGR ENV & CHEM PA0025615 PERMIT NUMBER ARN213A FD SCHARGE NUMBE.R1 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 2 COOL TOWER PUMPHOUSE Internal Outfall No Data Indicator7 MONITORING PERIOD YEARI MO DAY yEAR MO DAY FROMI 08 1 03 1 _
TO 8
03 131 PARAMETER NO.
FREQUENCY SAMPLE QUANTITY OR LOADING QUALITY OR CONCENTRATION EX OF ANALYSIS TYPE VALUE I VALUE IUNITS VALUE VALUE VALUE UNITS MEASUREMENT I 00400 1 0
- - I,.a-mowa....~
cu1~.,th
~~tutWV~~fl I
4.'Vr.rrlŽ1/2~t
- o..X.V~
I I
t
>,}*~h 1
~
tn ~tct1/2P~.
I
.2W I E~Yt~~WVt 141.
c----1 V
PER=MI I I
e e, r Effluent Gross REQUIREMENT PH___
MNMM
,~
M~IU
~~.t-Solids, total suspended SAMPLE 005301 0 PERMIT Effluent Gross REQUIREMENT mgIL' MO SAMPLE T
i Oil & grease MEASUREMENT 005561 0 PERMIT i--
x
,,;/TwEie Effluent Gross REQUIREMENT M
AV.G DAIY MX mgIL L
- ,Montl-g3/4!,
Flow, In conduit or thru treatment plant SAMPLEN_'
MEASUREMENT 500501 0 PERMITR-o Effluent Gross REQUIREMENT DG I--Y m; Mqal/d Chlorine, total residual MEASU E MEASUREMENT 50060 1 0 PERMIT Tw Per,'.2.w Effluent Gross REQUIREMENT G
/L t P, NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certfy under penalty of law that this document and all attachmnts cerwe pepated under my" TELEPHONE DATE direcion o sup rvisnInacrdance with asystem designed tonasur. than qualdifid personnel properly gather and enaluate the information submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE pe.....wn r.... athe yat... rthosepar....direetly 0eopdrrlbla orgatnerngthe 724 682-7773 08 04 28 Information, the Information Submitted is. to the best of my knowledge and belief true, accurate.t OPERATIONS and complete, am amre. thitt tit..em.
aignit.uant penalties for submitting false Information including the possibility of fine ani Imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT DISCHARGE FROM THE PUMP HOUSE PRIOR TO MIXING WITH ANY OTHER WATER. NOTE: THE MONITORING OF THIS DISCHARGE IS NOT REQUIRED WHEN EFFLUENT FROM UNIT NO. 2 COOLING TOWER PUMP HOUSE FLOOR & EQUIPMENT DRAINS IS BEING RECYCLED TO THE UNIT NO. 2 WATER RECIRCULATION SYSTEM.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL I'VULLU IAN I U.
-rwr Ll
~ll tt, s r
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM Page 74 PA0025615 PERMIT NUMBER 301A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 2 AUX BOILER BLOWDOWN Internal Outfall No Data Indicator D
MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 08
[
03 1
TO 108
- 3.
3 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE Q
EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE LUNITS Solids, total suspended 00530 1 0 MEASUREMENT N/A N/A N/A N/A
<4*
<4
- mg/L 0
2 i 31 GRAB MEASUREMENT PERMIT N/A 10 C, 117 1
11 Effluent Gross REQUIREMENT
.u
- 4.
!DAM*AV fILY tMX I mgiL
ý___
IvnV!.,
I_______
Oil & grease SAMPLE N/A N/A N/A N/A
<5 **
<5
- mg/L 0
2 / 31 GRAB Oil reaseMEASUREMENT 005561 0 PERMIT 7~1 2r)~,
T~c~e Effluent Gross REQUIREMENT 10 MAVG.-,,,AL mg/L
- _*_t_
FSAMPLE
<0.001
<0.001 MGD N/A N/A N/A N/A 1 / 7 EST Flow, in conduit or thru treatment plant MEASUREMENTS MEASUREMENT 500501 0 PERMIT N/AR~
Mn
- O~i Effluent Gross REQUIREMENT
.V 4DA1LWP4LX-M al/d NAMErTITLE PRINCIPAL EXECUTIVE OFFICER I certy under penalty of lma that this document and.1 hattam Prepared under my TELEPHONE DATE dicreion or eup.'Arisn in ccoiosritvden.ath a system designed to asures that qualified personnerl properly gather end evaluate the Information submitted. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE persons whno nanane. the systr, o. thes.persons directly resp*nsible for gathering1th 724 682-7773 08 04 28 information, the information submitted Is, to the beaft of my knomledge and belief, Itrue. accurate.
OP ERAT IONS end Complee. I am ýrnthatthere ar signifant OenaRties for EubmTtting faOse IFE O
NTED Including the possibility of fine 'and Imprlsonrment for knowing violations, SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR AREA CodeT-NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT THE DISCHARGE OF BOILER BLOWN DOWN PRIOR TO MIXING WITH ANY OTHER WATER.
- 4 mg/L is minimum detectable level. ** 5 mgl/L is minimum detectable level JPC 4.14-os Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL PULLU I AN I UI W-M1/-lK k LIV-LIffvtIII I I*Jýiv. i, s
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 75 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM PA0025615 PERMIT NUMBER 303A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 1 OIL WATER SEPARATOR Internal Outfall No Data Indicator[-X]
I MONITORING PERIOD I YEARI MO IDAY YEAR MO DAY FROMI 08 03 1J TO 8
03 31 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS MEASUREMENT 00400 1 0 Ihnau.t.....
u 4uk
&S uur i4 u
cat
> I1/2>
~a..
u It.
iaf trt~
t, ft t
rr""IlVlI I RFOIIRFMF'NT V
C irl~
%Vwe ly I
C nI-SAMPLE Solids, total suspended MEASUREMENT 005301 0 PERMIT
- 0.
- W GRAB EffluentGross REQUIREMENT AV U.
DAILY MI mgIL SAMPLE Oil & grease MEASUREMENT 005561 0 PERMIT WekyGA Effluent Gross REQUIREMENT M C
".G
.1 AL mgIL Xk Flow, In conduit or thru treatment plant SAMPLE MEASUREMENT 5005010 PERMIT M..L N'
Effluent Gross REQUIREMENT MAG ID X-.
Mgal/d I
N eMA NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certfy unalr penalty of law that this document and ell attachments mee prepared under my TELEPHONE DATE NAME TLE RIN IPALEXE UTIV OFICER dthrefiton or supervisionr In acor~dance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person at Kevin L. Ostrowski, DIRECTOR OF SITE pesons who mattage the system, or those persons directly responsible for gatherinrg me 724 682-7773 08 04 28 information. the information submitted Is, to the best of my knowledge and belief. true, accurate.
OPERATIONS end complete. lam w.r that there e signlficant penalties for submitting false information.
including the possibility of fine and Imprisonment for knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code T NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT THE OVERFLOW FROM THE OIL WATER SEPARATOR PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL POLLUTAN I UUI6L;AI-1-Kt
-LlUIVIintI IJI*N 0I N
.t,
\\,,t DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 76 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM PA0025615 PERMIT NUMBER 313A DISCHARGE NUMBER DMR MAILING ZIP CODE:
MAJOR (SUBR05) 313 TURBINE BLDG DRAIN Internal Outfall 150770004 I
MONITORING PERIOD
[YEARI MO IDAY YEAR MO DAY FROM[
08 1'03 1 O1 TO 08 1
03 31 No Data IndicatorF-X-PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH 00400 1 0 Ffflu tnt (*rn*~
N/A MEASUREMENT I N/A N/A 7.04 N/A 7.72 pH 0
1/7 GRAB PERMIT VL.e y*n*
/
e
[}r-i Solids, total suspended SAMPLE N/A N/A N/A N/A 7.3 9.4 mg/L 0
1 / 7 GRAB MEASUREMENT!
005301 0 PERMIT i00'V'.0 "r.
Effluent Gross REQUIREMENT M GAVG IX mg/L, C4* G B*
Oil & grease SAMPLENT N/A N/A N/A N/A
<5 *
<5 mg/L 0
1 / 7 GRAB MEASUREMENT 00556 1 0 PERMIT
(,;RA
.E.
k Effluent Gross REQUIREMENT I.Mg/L Flow, in conduit or thru treatment plant SAMPLE 0.002 0.002 MGD N/A N/A N/A N/A 1 / 7 EST Flo. n onui o thu retmntplnt MEASUREMENT 500501 0 PERMIT Fni.M.
N Effluent Gross REQUIREMENT MGA)
I3ALM X
M al/d NAME/TITLE PRINCIPAL EXECUTIVE OFFICER hort*if under paernatyt of n that this doument and all
- ttachments wPre apedunder m TELEPHONE DATE direction or supervislon in accordance with a system deaig ned to assura that qualified personnel T
DATE property gather and -Valuate the Information Submhited. Based on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE pe..sons wo manag thesys.tem o.. tho..pern dir*ctly responsible forgathigth.
724 682-7773 08 04 28 information, the Information submitted Is, to the best of my knowldodge and bolls"f
.rue, 724 82-77308 4
2 OPERATIONS end complrtete. Iat r
.taot thera ar significant penalt.ieo, f..
o m
false Information, I
R I
LV C
.including the possibiUity of fine and imprisonment for knO~ing dlolatlo ft.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR A0.f 7 -
TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT DISCHARGE FROM OWS #21 PRIOR TO MIXING WITH ANY OTHER WATER.
- 5 mg/L is minimum detectable level JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL I'ULLU I 1AN I UI0iLr1M!-
CLIIVIIIrM I I*r.
DISCHARGE MONITORING REPORT (DMR)
PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM PEMTUME 401A DISCHARGE NUMBER OMB No. 2040-0004 Page 77 DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
CHEM.FEED AREA OF AUX BOILERS Internal Outfall No Data IndicatorfZ F-MONITORING PERIOD YEAR MO DAYJ IYEAR MO DAY FROM 08 03 011 TO 08 103 31 QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE PARAMETEREX OANLSS TP VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH MEASUREMENT N/A N/A N/A 8.47 N/A 8.81 pH 0
2 / 31 GRAB 004001 0 PERMIT eMob wl 4P Eflun Gros N/A Rpq MflI'.GRAB 0Effluent Gross REQUIREMENT MINMIJm">
M
______.. I-M"*Ilth');
pH Solids, total suspended SAMPLE N/A N/A N/A N/A
<4
<4
- mg/L 0
2 I 31 GRAB MEASUREMENT 005301 0 PERMIT
~
- ~0
~
0Ti fI Effluent Gross REQUIREMENT A
M mR/C
_r.... To____t___
Olow, & n conduit rthrutreSAMPLE IA N/
<N/
MEASUREMENT mg/L 0
31 GRAB 005561 0 PERMIT N/A 2
15*'0 o,"
w**
Effluent Gross REQUIREMENT IjAVrG*
M m
- /L i
Flow, in conduit or thru treatment plant MEASRMPEN
<0.001
<0.001 MGD N/A N/A N/A N/A ST 5005010 PERMIT Rýý6.M11ýf
ýe 1%Mo-n' I
-~ty NIA
,Effluent Gross REQUIREMENT
[MOv'- G, L i AL YM
%1 1 Mgal/d I 1
1 NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I certify under Penalty of law that this document and oi1 attachments vare prepared under my TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualifled personnel Property gatner and evaluate rthe infornmation submitted. Bseod on my Inquiry ofith. person or
.S Kevin L. Ostrowski, DIRECTOR OF SITE per.ons. omnao...gethes.ystem.
or those persons diretly
.ponsibla for g**tngth.
724 682-7773 08 04 28 Information, the Information submitted Is. to the best of my knov~eoge aind befief. roe.
724 682 OPERATION S and compa.. I.... ina hat ther are..
significant pan.ttl, fo, submitin fase information,I including the possibility of fine and irnprison rit for knovng violations, SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
SAMPLES SHALL BE TAKEN AT CHEMICAL FEED AREA DRAINS PRIOR TO MIXING WITH ANY OTHER WATER.
- 4 mg/L is minimum detectable level. ** 5 mg/L is minimum detectable evel. JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev. 01(06)
NATIONAL IJULLUIMNI UL.Ii
.V3 rLIVy,*
'O,,
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 78 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERAIMGR ENV & CHEM PA0025615 PER NUMBER 403A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
CONDENSATE BLOWDOWN & RIVR WAT Internal Outfall No Data IndicatorL---
MONITORING PERIOD YEAR M
MO I DAY YEARI MO I DAYI FROM 08
[
03, 1 01 TO 08 03 31 i PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS pH 00400 1 0 lff"i, rantf rnww MEASUREMENT PERMIT
- 0*0*
-j *1
nrnUIJo ii
~i~~i vi SAMPLE Solids, total suspended MEASUREMENT 00530 1 0 PERMIT 2
30 10
-&k
'GA Effluent Gross REQUIREMENT At(3AV D IL Y
y G
SAMPLE Oil & grease MEASUREMENT, 005561 0 PERMIT...
2 i
Effluent Gross REQUIREMENT Nitrogen, ammonia total (as N)
SAMPLE 0
DIL{'
W kr MEASUREMENT 0 0 6 1 0 1 0 P E R M IT
.' *it
- .e EffluentGross REQUIREMENT mG,
',,MILY mg/L CLAMTROL CT-1, TOTAL WATER SAMPLE MEASUREMENT 04251 1 0 PERMIT w"
h
\\'O P
Effluent Gross REQUIREMENT
'I oMOiGMX;I mglL,,
Dischargirgt SAMPLE Flow, in conduit or thru treatment plant MEASUREMENT 500501 0 PERMIT '
ýR I.
2 Rc*
M'on -
- 000*0
,S'*
Effluent Gross REQUIREMENT
'MOA'
=Al-
- MŽ M al/d i,.
,i
~
SAMPLE Chlorine; total residual M A M E MEASUREMENT 500601 0 PERMIT Weeklji GRAB Effluent Gross REQUIREMENT MiAMG ljSAM.
mg/L NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I c,,
Under Palt of lw that this document ad all attachment prepared under my TELEPHONE ATE diraction or supervislon in accardaflo* with a system designed to stsut. thnt qualified personnelT LE H NED T
properly gather and evaluate the information submnred. Based on my inquiry of the parson or Kevin L. Ostrowski, DIRECTOR OF SITE porsons who managet th sy*tem, o.r.os. parsons diracnly responsbl or gathring th.
724 682-7773 08 04 28 information, the Information rsubmitted Is, to the best of my knowledge and belief, true, accurate, 7
6 OPERATIONS and complete. I am twar. that there. are sgnificant penalties for submitting false Information.
inctuding the possaitry of tin. and imprisonment to, knowing violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED
. AUTHORIZED AGENT AREA Code; NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments= hero)
HYDRAZINE AND AMMONIA MONITORING TO APPLY DURING PERIODS OF WET LAYUP. REPORT THE DAILY MAXIMUM FOR BETZ DT-1 WHEN DISCHARGING (24 HR. COMP.):
MG/L. (THE LIMIT IS 35 MG/L AS A DAILY MAX.) SAMPLES SHALL BE TAKEN AT MP 403 PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01106)
NATIONAL POLLUTANT UI5 -1`,
t-I=LlIvtII*M 1 I *LJ I o1, DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
Page 79 NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERANMGR ENV & CHEM PA0025615 PERMIT NME RENUMBERI DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
CONDENSATE BLOWDOWN & RIVR WAT Internal Outfall No Data Indicator*--7 FMONITORING PERIOD I YEAR IMO I'DAYI YEAR MO DAY FROMI 08 1 03 01,Ij TO 0,8 1 03 1 31 1 PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS Hydrazine 813131 0 MEASUREMENT 81313 1 0
- .~'j~uI; e~ly~ U I
T ~ t.
~
thIn I outiru~o it I
T r~. o~
I
~
~T tith~f~t~
rCrIVII I I
.: - 'ý 1 11 i I ý I I.
I i-k 1
pu-+/-
I I
I ý!,
I Weekiy
'I G P-ý'P
-r, /I E:..
lu n~t roatu
%A sur'.tit fa I~, I 1
29f tit1~ti' l*
~F'4 j
I4
~
NAMETI'TLE PRINCIPAL EXECUTIVE OFFICER I,ertif under penalty of law tht tis document..nd ali Amichmeht vere prepared under my--
TELEPHONE DATE direction or supervision in accordance with a sysefm designed to assure that qualified pteronnel properly gether and evaluate the information Submitted. eased on my inquiry of the person or Kevin L. Ostrowski, DIRECTOR OF SITE p sons ho managet* e systemh, orthos. ppersons diecity responsiblefor gatharing tha 724 682-7773 08 04 28 In formaetion. the Information submittd Is, to the be~at of my know~edge and belief, true. riccultt,7268 730 04 8
OPERATIONS
,nd complete. I am....
that that at... significant penaises for ifttig fallse Information, OEA O.
ancluding the possibility of fine aend Imprisonment for knawng violations.
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED te rAUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLAlIONS (Reference all attachments here)
HYDRAZINE AND AMMONIA MONITORING TO APPLY DURING PERIODS OF WET LAYUP. REPORT THE DAILY MAXIMUM FOR BETZ DT-1 WHEN DISCHARGING (24 HR. COMP.):
MG/L. (THE LIMIT IS 35 MG/L AS A DAILY MAX.) SAMPLES SHALL BE TAKEN AT MP 403 PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Generated Version of EPA Form 3320-1 (Rev. 01/06)
NATIONAL POLLUTANT DISCtHAt{-. tLIMIIN/ 1 IU,* Of.
L.o t
,, S..
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 Page 80 PERMITTEE NAME/ADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERANMGR ENV & CHEM PA0025615 PERMIT NUMBER 413A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
BULK FUEL STORAGE DRAIN Internal Outfall No Data Indicator lJ MONITORING PERIOD I
YEAR MO I DAY YEAR MO I DAYI FROM 08 103 1
TO 01 03 1 31 1
PARAMETER pH 004001 0 Effluent Gross QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
EX FREQUENCY OF ANALYSIS SAMPLE TYPE
¶ S
I*
- t
'5 VALUE VALUE UNITS VALUE VALUE VALUE UNITS MFASUR~M~NT I N/A N/A N/A 7.21 N/A 7.35 pH 0
1/7 GRAB pH GRABT PERMIT REQUIREMENT
- ~MINIMUM
~,.
U.
MAXIM W~kIyj'1GRAB~
SAMPLE Solids, total suspended SUME N/A N/A N/A N/A 10.4 14.1 mg/L 0
1 / 7 GRAB 0053010 P
IMEASUREMENT I
Effluent Gross REQUIREMENT AVG mg/L, Oil & grease SAMPLE N/A N/A N/A N/A
<5 *
<5
- mg/L 0
1 / 7 GRAB MEASUREMENT 005561 0 PERMIT
.O*,
Effluent Gross REQUIREMENT V0, N/A 15U 20 1Le'
________REQUIREMENT_____
MX',
IG At~o mg/L Flow, in conduit or thru treatment plant SAMPLE
<0.001
<0.001 MGD N/A N/A N/A NIA 1
7 EST MEASUREMENT
<001<.0 GD NANANAN/
S 5005010 PERMIT Ie reNEA Effluent Gross REQUIREMENT MOAVGD A G I)1L'M Mgal/d NAME/TITLE PRINCIPAL EXECUTIVE OFFICER Oat c
y under penalty of law that this document and all attachments wera prepared under my TELEPHONE DATE di'eotloni or supervisio in acorodance with a system designed to assure that qualified personnell properly gather and soaluata the information submitted. Based on my intuiryof the pperson or Kevin L. Ostrowski, DIRECTOR OF SITE personso ho anage
.te*system. or.thoe persons directly teponsiblefor gatheringth 7.248-7773 08 04 2
information, the Informstlan submitted I, to the best of my knowledge and belief., true ro.
724t e.
Is.m.,. that th.......ignifi penalties f-bitln Was Information, including the possibility of fine and Imprisonment for knowing violation..
SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR TYPED OR PRINTED AUTHORIZED AGENT AREA Code NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attchments here)
SAMPLES SHALL BE TAKEN AT DISCHARGE FROM OWS #24 PRIOR TO MIXING WITH ANY OTHER WATER.
- 5 mg/L is minimum detectable level JPC 4-14-08 Computer Generated Version of EPA Form 3320-1 (Rev, 01106)
NATIONAL POLLUTANT DISCHARU- -LIMIN' I IUIN 0 I 0, r-ti,.
DISCHARGE MONITORING REPORT (DMR)
OMB No. 2040-0004 PERMITTEE NAMEIADDRESS (include Facility Name/Location if Different)
NAME:
FIRST ENERGY NUCLEAR OPERATING ADDRESS:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 FACILITY:
BEAVER VALLEY POWER STATION LOCATION:
PA ROUTE 168 SHIPPINGPORT, PA 150770004 ATTN: DONALD J SALERA/MGR ENV & CHEM Page 81 PA0025615 PERMIT NUMBER, S501A DISCHARGE NUMBER DMR MAILING ZIP CODE:
150770004 MAJOR (SUBR05)
UNIT 1 GENRTR BLWDWN FILT BW Internal Outfall No Data IndicatorF-]
FMONITORING PERIOD I YEARI MO I DAY YEAR I MO DAY FROMI 08 1 03 1
TO 08 1 "03 1 31 QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
EX FREQUENCY OF ANALYSIS SAMPLE TYPE PARAMETER I
r VALUE VALUE I UNITS I VALUE VALUE VALUE UNITS Solids, total suspended 00530 1 0 MEASUREMENT MEASUREMENT PERMIT I
AA(t AAJ~~
frI VRA mnIl I
Vjee'dy GRAB Effluent~c Gross____
REQUIREMENT L-'.ý'"
MX Flow, in conduit or thru treatment plant
=*nn~n 1 n SAMPLE MEASUREMENT DI:BRIT
ý7',,
r ' ý ý ", -
r 1
ý71
ý,
! I -
Effluent Gross REQUIREMENT Mg, /d Weejy ICOMMENTtSundDrEX thatNthiVdOcumentNnd(Rleferenceent1 wrtprepardtundersm direcion ot supervision In accotdance vtnhtta systemn desigted ta assure that qualified parsohrl propetly gather and ealuate the Information submitted. Based o my inquiry ot the petsohna persons Ywtl mahage the system, or thase persons ditecoly responsible for gathering the Ithirdmetlon. the Iinfratmeion submttied Is, to the beot of my IcooMledge and belief. true. eccuite ahd complete. I am e-sa that thr.,* ate aignificnht penalties tot submittng tain Informatiot.
COMMENTS AND EXPLANATION OF ANY tAOLATIONS (Reference all attachnrents heare)
SAMPLES SHALL BE TAKEN AT INTERNAL MP 501 PRIOR TO MIXING WITH ANY OTHER WATER.
Computer Genterated Version of EPA Form 3320-1 (Reva. 011/06)
3800-FM-WSFR0189 6/2006 COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF WATER STANDARDS AND FACILITY REGULATION SUPPLEMENTAL LABORATORY ACCREDITATION FORM1 pH SM 4500-H+ B [20'h]
Beaver Valley Power Station 04-2742 Flow NA Beaver Valley Power Station 04-2742 Total Suspended Solids Si2ý01Q1,`
Beaver Valley Power Sýto 424 Hydrazine ASTM D1385-01 Beaver Valley Power Station 04-2742 Fe-cal Coliform' Standa~cdMethod 9222D.,'
<Bever-'Vlley Power Statiiorin 04-2742 Oil and Grease EPA 1664 Rev A FirstEnergy Corp-Beta Lab 68-01120 Tota Dissolved Solids M-254...0___
Firstlnergy Corp-Beta LabQ8 GW8_0 1OigO*
-1 I I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibly of fine and imprisonment for knowing violations.
Name/Title Principal Executive Officer Kevin L. Ostrowski Director Site Operations Phone: 724-682-7773 Date:
06 Signature of Principal Executive Officer or Authorized Agent Submit this form with each Discharge Monitoring Report (DMR), Annual Report or Recordkeeping and Reporting Form, where sample results are submitted to the Department for compliance purposes.
2 For parameter(s) covered under accreditation-by-rule, submit the lab's registration number in lieu of an accreditation number.
3 Analysis no longer performed.
3800-FM-WSFR0189 612006 Depn COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF WATER STANDARDS AND FACILITY REGULATION SUPPLEMENTAL LABORATORY ACCREDITATION FORM1 Cyanide I
SM 4500-CrN E [2 0th1 Precision Analytical Inc.
Ii 68-00434
- i I
I I
I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibly of fine and imprisonment for knowing violations.
Name/Title Principal Executive Officer Kevin L. Ostrowski Director, Site Operations Phone: 724-682-7773 Date:
0/9o Signature of Principal Executive Officer or Authorized Agent Submit this form with each Discharge Monitoring Report (DMR), Annual Report or Recordkeeping and Reporting Form, where sample results are submitted to the Department for compliance purposes.
2 For parameter(s) covered under accreditation-by-rule, submit the lab's registration number in lieu of an accreditation number.