DCL-03-054, Special Report 03-01: Results of Steam Generator Tube Eddy Current Inspections During Eleventh Refueling Outage
| ML031480561 | |
| Person / Time | |
|---|---|
| Site: | Diablo Canyon |
| Issue date: | 05/19/2003 |
| From: | Oatley D Pacific Gas & Electric Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| DCL-03-054, OL-DPR-82 | |
| Download: ML031480561 (32) | |
Text
Pacific Gas and Electric Company David H. Oatley Diablo Canyon Power Plant Vice President and P.O.
Box 56 General Manager Avila Beach, CA 93424 May 19, 2003 805.545.4350 Fax: 805.545.4234 PG&E Letter DCL-03-054 U.S. Nuclear Regulatory Commission ATIN: Document Control Desk Washington, D.C. 20555-0001 Docket No. 50-275, OL-DPR-82 Diablo Canyon Unit 1 Special Report 03-01: Results of Steam Generator Tube Eddy Current Inspections During Unit I Eleventh Refueling Outage
Dear Commissioners and Staff:
In accordance with Diablo Canyon Power Plant Technical Specification 5.6.10.b, this special report provides the results of steam generator (SG) tube eddy current inspections performed during the Unit 1 eleventh refueling outage, completed in May 2002.
The enclosed tables provide the number and extent of tubes inspected in each SG, the location and percent through-wall penetration of each indication identified, and identification of tubes plugged.
Sincerely, David H. Oatley ddm/469 Enclosure cclenc:
Ellis W. Merschoff David L. Proulx Girija S. Shukla State of California Diablo Distribution A member of the STARS (Strategic Teaming and Resource Sharing) Alliance Callaway Comanche Peak Diablo Canyon Palo Verde South Texas Project
- Wolf Creek
Enclosure PG&E Letter DCL-03-054 SPECIAL REPORT 03-01 RESULTS OF STEAM GENERATOR TUBE EDDY CURRENT INSPECTIONS DURING UNIT 1 ELEVENTH REFUELING OUTAGE Enclosure PG&E Letter DCL-03-054 Introduction Technical Specification 5.6.10.b requires that the results of steam generator tube inspections be submitted to the NRC within 12 months following completion of the inspection. The report shall include:
- 1. Number and extent of tubes inspected,
- 2. Location and percent of wall thickness penetration for each indication of an imperfection, and
- 3. Identification of tubes plugged.
Table 1 provides the number and extent of tubes inspected in each SG.
Table 2 provides the location and percent through-wall of each indication identified, and identifies the tubes that were plugged in the Unit 1 eleventh refueling outage (1 RI 1). Some tubes were preventively plugged due to data quality concerns, even though no indication was detected by eddy current.
Notes:
- 1. Free span indications (e.g., manufacturing burnish mark) that had eddy current signals traceable to preservice inspection data are not considered as reportable indications and are not included in this report.
- 2. Bobbin distorted outside diameter support signals (DOS) that were not confirmed by Plus Point are not reportable indications and are not included in this report. These signals were addressed in the 90-day report for voltage-based alternate repair criteria (ARC).
Abbreviations and Terms The following provides a definition of abbreviations and terms used in Tables 1 and 2.
SG Steam Generator Row Row Col Column Location SG location codes Inch Distance above or below the center line of the TSP or the top of TS, inches Bobbin Differential inside diameter coil probe
+Point Plus Point rotating probe TSP Tube support plate TS Tubesheet Indication Type of indication: Indication Code, anti-vibration bar AVB) wear, or cold leg thinning (CLT)
ID/OD Location of crack-like indications on tube surface, either inside diameter (ID) or outside diameter (OD)
%TW Depth of indication as percent through-wall. 0% indicates a signal with shallow OD phase angle.
INDICATION CODES SAI Single axial indication (from +Point exam)
Note: SAI may be left in service for the following reasons:
Voltage-based ARC for axial outside diameter stress corrosion cracking (ODSCC) at TSP intersections W ARC for axial primary water stress corrosion cracking (PWSCC) in WEXTEX tubesheet PWSCC ARC for axial indication(s) at dented TSP intersections SCI Single circumferential indication (from +Point exam)
SVI Single volumetric indication (from +Point exam)
AONDB Axial ODSCC not detected by bobbin coil I i Enclosure PG&E Letter DCL-03-054 Table I Number and Extent of Tube Inspections During 1 RI 1 SCOPE PROBEl SG 11 SG 12 SG 13 SG 14
~~~~TYPE.
Full length (except Rows 1 Bobbin 100%
100%
100%
100%
and 2 U-bends)
Rows I and 2 U-bends
+ Point 100%
100%
100%
100%
Row 3 U-bends
+ Point 20%
NA 20%
NA Hot Leg top-of tubesheet
+ Point 100%
100%
100%
100%
> 5 volt dented TSP
+ Point 100% 1H to 5H, 100% 1H to 6H, 20% (50 min) 1H 100% 1H to 3H, intersections 20% (50 min) 5H 20% (50 min) 7H to 7H 20% (50 min) 4H to to 7H 7H
>2 and < 5 volt dented
+ Point 100% from IH to 100% from I H to 20% (50 min) at 100% from 1 H to TSP intersections 5H. 20% (50 min) 6H, 20% (50 min) 1 H 3H, 20% (50 min) at 5H at 7H at 4H Distorted OD bobbin
+ Point Per voltage-based Per voltage-based Per voltage-based Per voltage-based signals at TSP repair criteria repair criteria repair criteria repair criteria intersections Distorted OD bobbin
+ Point 100%
100%
100%
100%
signals at TSP intersections in Deplugged Tubes Distorted ID bobbin
+ Point 100%
100%
100%
100%
signals at TSP intersections..
> 2 volt free span dings
+ Point 20% TSH to 7H 20% TSH to 7H 20% TSH to 7H 20% TSH to 7H Baseline TSP ligament
+ Point 100%
NA NA 100%
indications Repeat PWSCC at dents
+ Point 100%
100%
100%
100%
and TTS I
I I
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/ODMTV Status Reason for Plugging Notes 11 1
25 Plugged U-Bend Data Quality - Preventive 11 1
26
=
=
Plugged U-Bend Data Quality - Preventive 11 1
=______
11 1
41 Plugged U-Bend Data Quality - Preventive 11 1
43 Plugged U-Bend Data Quality - Preventive 11 1
45 Plugged U-Bend Data Quality - Preventive 11 1
68 Plugged U-Bend Data Quality - Preventive 11 1
89 Plugged U-Bend Data Quality - Preventive 11 2
6 TSH -1.77 SCI ID Plugged ID-SCI atTSH 11 2
46 1 H -0.07 SAI OD Plugged SAI-OD, DOS>2v at 1 H 11 3
2 TSH -1.45 SAI ID 11 3
28 2H
-0.14 SAI ID 11 3
41 1H -0.01 SAI ID 11 4
67 IH -0.16 SAI OD Plugged SAI-OD, DOS>2vat IH 11i 4
92 IC 0.07 CLT 20 11
.4 92 2C
-0.09 CLT 35 11 4
94 2C 0.11 CLT 30 11 5
11 5
86 1H 0.03 SAI OD Plugged SAI-OD at 1 H Wedge 11 5
94 1C 0.07 CLT 0
11 5
94 2C 0.11 CLT 9
11 6
31 1H 0
SAl I OD 11 6
49 TSH -0.02 SCI OD Plugged OD-SCI at TSH 11 6
93 1 C 0.09 CLT 0
11 7
10 1H
37 3H
2 2C
-0.07 CLT 0
11 8
42 1H
69 1H 0
69 1H 0
69 2H
82 1H 0
=
0 11 9
931 IC -0.29 CLT I___20 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind IDIOD%T\\tA Status Reason for Plugging Notes 11 10 28 1H 0.06 SAI OD 11 10 39 IH -0.03 SAI OD 11 10 71 1H 0
-0.27 CLT 0
11 10 93 IC -0.29 CLT 15 11 11 15 3H
-0.24 SAI OD 11 11 22 2H 0.08 SAI OD 11 11 40 2H
-0.03 SAI OD 11 11 93 1C -0.25 CLT 3
11 12 63 2H 0.02 SAI OD 11 12 91 1C
-0.22 CLT 18 11 13 44 2H 0.01 SAI OD 11 14 12 2H 0.33 SAI OD Plugged AONDB, >5v Dent at 2H 11 14 28 2H 0.31 SAI ID 11 14 62 2H
-0.07 SAI OD 11 14 68 TSH -0.03 SCI OD Plugged OD-SCI at TSH 11 14 83 1 H
=
11 14 87 2H 0.15 SAI ID Plugged SAI-ID/OD at 2H 1
14 87 2H
-0.16 SAI OD Plugged SAI-ID/OD at 2H 11 14 88 1 H 0.03 SAI OD II 15 10 TSH -8.96 SAI ID 11 15 10 TSH -8.42 SAI ID 11 15 16 2H -0.04 SAI ID 11 15 30 2H
-0.12 SAI ID 11 15 81 2H 0.14 SAI ID Plugged SAI-ID/OD at 2H 11 15 81 2H
-0.03 SAI OD Plugged SAI-ID/OD at 2H 11 15 92 1C
-0.11 CLT 7
11 16 45 2H
-0.07 SAI OD Plugged SAI-ID/OD at 2H 11 16 45 2H
-0.09 SAI OD Plugged SAI-ID/OD at2H 11 16 45 2H
-0.01 SAI ID Plugged SAI-ID/0D at 2H 11 16 79 2H -0.11 SAI OD 11 17 27 3H 0.1 SAI OD 11 17 35 7H 35 AVB wear 16 11 17 58 TSH -0.03 SCI OD Plugged OD-SCI at TSH 11 17 60 TSH -0.07 SCI ID Plugged ID-SC) at TSH 11 17 74 7H 33.64 AVB wear 20 11 17 76 1H
SAI OD 11 18 39 TSH 0.03 SCI OD Plugged OD-SCI atTSH 11I 18 89 2C
-0.25 CLT 19 11 19 15 3H 0.08 SAI ID Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 Ri 1 SG Row Col Loc Inch Ind ID/ODI%T\\
Status Reason for Plugging Notes 11 19 23 2H 0
SAI OD 11 19 31 2H 0.13 SAI OD 11 19 31 2H 0.04 SAI OD 11 19 39 1 H
-0.03 SAI OD 11 19 46 1 H -0.01 SAI OD 11 19 46 1 H
-0.1 SAI OD 11 19 52 1 H 0.04 SAI OD 11 19 61 1H
-0.24 SAI ID 11 20 29 2H 0.25 SAI ID 11 20 33 IH -0.14 SAI ID 11 20 40 1H
-7.9 SAI ID 11 20 46 2H
-0.25 CLT 0
11 21 51 2H
-0.31 CLT 14 11 22 23 2H
-0.3 SAI ID 11 22 23 2H 0.21 SAI ID 11 22 71 2H 0.05 SAI OD
=
Plugged SAI-ID/OD at 2H 11 22 71 2H 0.06 SAI ID Plugged SAI-ID/OD at 2H 11 23 14 3H
-0.1 SAI ID 11 23 58 3H
-0.1 SAI OD 11 23 59 1 H 0.12 SAI OD 11 23 59 1 H -0.01 SAI OD 11 23 74 1 H
-0.04 CLT 0
11 23 88 2C
-0.2 CLT 0
11 24 20 2H 0.09 SAI ID I Plugged SAI-ID/OD at 2H 11 24 20 2H
-0.04 SAI OD Plugged SAI-ID/OD at 2H 11 24 51 1 H 0.02 SAI OD 11 24 67 2H
-0.05 SAI ID
=
11 24 87 2C
-0.22 CLT 9
i-11 25 43 2H 0.15 SAI OD 11 25 57 3H 0.15 SAI ID 11 25 62 7H 45.03 AVB wear 20 11 25 62 7H 63.61 AVB wear 26 11 25 85 1 C 0.09 CLT 20 11 25 86 2C
-0.2 CLT 0
11 26 19 2H 0.03 SAI OD 11 26 25 1 H 0.36 SAI ID Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 Rl I SG Row lCol Loc Inch Ind IDtODIO/oTW Status [
Reason for Plugging Notes 11 26 34 1H
-0.2 CLT 23 11 27 28 1H 0.12 SAI OD 11 27 44 2H
=
11 27 47 1 H 0.2 SAI OD Plugged SAI-OD, DOS>2v at 1 H 11 27 75 2H 0.03 SAI ID 11 28 25 2H 0.06 SAI OD I1 28 27 1 H
-0.38 SAI ID 11 28 27 1 H
-0.12 SAI ID I1 28 29 1 H 0.06 SAI OD 11 28 29 1 H
-0.1 SAI OD 11 28 48 7H 50.51 AVB wear 19 11 28 48 7H 73.14 AVB wear 22 11 28 48 7H 84.74 AVB wear 27 11 28 85 1C
-0.06 CLT 21 11 29 29 2H
-0.07 SAI OD 11 29 37 2H 0.13 SAI ID 11 29 84 2C
-0.18 CLT 21 11 30 21 2H
-0.15 SAI ID 11 30 30 2H
-0.08 SAI OD Plugged SAI-OD, DOS>2v at 1 H 11 30 58 4H
-0.15 SAI OD_
11 30 67 2H 0.09 SAI ID 11 30 83 1 C
-0.29 CLT
=
26 11 31 17 1H 0.03 SAI OD Plugged SAI-OD at I H Wedge 11 31 81 2C
-0.23 CLT 27 11 32 24 2H
CLT 10 11 33 40 2H
-0.05 SAI OD Plugged SAl-ID/0D at 2H 11 33 40 2H
-0.15 SAI ID Plugged SAl-ID/OD at 2H 11 33 40 2H
-0.12 SAI OD Plugged SAI-ID/OD at 2H 11 33 55 1 H 0.06 SAI OD I
11 33 77 2C
-0.31 CLT 38 1 11 33 79 1C 0.29 CLT 21 11 34 24 3H 0.02 SAI ID 11 34 24 3H 0.25 SAI ID 11 34 79 1 C
-0.34 CLT 25 11 35 17 1C
-0.13 CLT 21 1 11 35 43 2H 0.07 SAI OD
=
11 35 43 2H
-0.12 SAI OD Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/OD Status Reason for Plugging Notes 11 35 59 3H 0.01 SAI ID
=
11 35 76 2C
-0.2 CLT 3
11 35 78 IC -0.36 CLT 14 11 36 30 2H -0.11 SAI OD
=
Plugged SAI-ID/OD at 2H 11 36 30 2H 0.2 SAI OD Plugged SAI-ID/OD at 2H 11 36 30 2H -0.21 SAI ID Plugged SAI-ID/0D at 2H 11 36 73 2C -0.18 CLT 0
11 36 77 IC 0.22 CLT 27 11 36 77 2C -0.22 CLT 7
11 37 41 2H -0.02 SAI OD 11 37 45 2H 0.08 SAI OD
=
11 37 46 7H 62.91 AVBwear 36 11 37 75 2C -0.14 CLT 10 11 38 41 4H -0.26 SAI ID 11 38 54 2H -0.02 SAI OD I
11 38 72 1 C -0.32 CLT 21 11 39 54 7H 101.6 AVB wear 28 11 39 54 7H 66.29 AVB wear 23 1 139 54 7H 129.7 AVB wear 21 11 39 56 7H 131.1 AVB wear 18 11 39 57 2H
-0.18 SAI ID 11 39 73 1 C -0.32 CLT 10 11 40 43 7H 104.4 AVB wear 36 Plugged 42%TWAVB Wear 11 40 43 7H 67.31 AVB wear 35 Plugged 42%TWAVB Wear 11 40 43 7H 103.7 AVB wear 42 Plugged 42%TW AVB Wear 11 40 50 1 H 0.12 SAI OD
_1 40 68 7H 68.12 AVB wear _
21 11 40 68 7H 103.1 AVB wear 28 11 41 32 2H -0.04 SAI OD Plugged SAI-OD @ 2H Wedge 11 41 44 7H 137.9 AVB wear 16 11 41 44 7H 107.4 AVB wear 20 11 41 64 2C
-0.2 CLT 18 11 41 68 2H 0.01 SAI OD 11 41 68 2H -0.14 SAI OD 11 42 29 2C
-0.21 CLT 31 11 42 50 4H 0
=
11 42 58 2C
-0.27 CLT 14 11 42 62 IC -0.34 CLT 27 11 42 65 IC -0.36 CLT 21 11 43 30 7H 37.89 AVB wear 25 11 44 55 2C 0.25 CLT 10 11 44 59 1C -0.11 CLT 18 11 44 60 2C -0.29 CLT
=
23 1 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc I Inch Ind
[IDIODL%TV Status Reason for Plugging Notes 11 44 61 1C -0.36 CLT 0
11 45 59 2C -0.27 CLT 27 11 46 51 IC -0.16 CLT 28 11 l 46 54 IC -0.27 CLT 2
12 1 44 5H 0.03 SAI OD Deplugged 1 Rl1 12 1
57 Plugged U-Bend Data Quality - Preventive 12 1
64 Plugged U-Bend Data Quality - Preventive 12 2
1 1C -0.21 CLT 14 12 2
10 3H -0.08 SAI ID Deplugged IR11 12 2
28 3H -0.14 SAI ID
=
Deplugged IRI1 12 2
68 1H
-0.2 SAI ID Plugged SVI-OD at IH Deplugged 1RI1 12 2
68 1H -0.06 SVI OD Plugged SVI-OD at IH Deplugged 1RI1 12 2
68 1H 0.23 SVI OD Plugged SVI-OD at 1H Deplugged IRl1 12 2
76 2H -0.09 SAI ID 12 2
78 1H 0.13 SAI ID 12 2
79 3H 0.05 SAI ID 12 2
90 3H -0.24 SAI OD Deplugged 1R11 12 2
90 4H -0.38 SAI ID I
_Deplugged 1Rl1 12 2
90 4H -0.12 SAI ID Deplugged Rll 12 2
92 5H -0.41 SAI ID
=
12 2
92 5H
-0.03 SAI ID 12 2
92 5H 0.18 SAI ID 12 2
93 4H 0.17 SAI ID 12 3
1 1C -0.13 CLT 3
12 3
38 TSH -0.23 SAI ID Plugged SAI-ID at TSH 12 4
1 2C 0.08 CLT 33 12 4
48 1H 0.05 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 4
48 2H -0.26 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 4
50 2H -0.01 SAI OD Deplugged Rl 12 4
54 2H 0.03 SAI ID Deplugged IRI1 12 4
57 1 H 0.06 SAI ID 12 4
58 1H
-0.17 SAI ID Deplugged 1RI1 12 4
58 1H 0.17 SAI ID Deplugged IRI1 12 4
84 1 H 0.04 SAI ID 12 4
94 1 C 0.11 CLT 36 12 5
1 2C 0.02 CLT 0
12 5
4 1C
-0.22 CLT 33 12 5
39 2H -0.13 SAI ID Deplugged 1RlI 12 5
49 2H -0.17 SAI OD Deplugged 1R11 12 5
52 2H 0.02 SAI OD Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 RI 1 SG Row Col Loc lnch Ind ID/ODfrOTWl Status J Reason for Plugging
[
Notes 12 5
59 1H
-0.1 SAI OD Plugged SAI-IDIOD at 1H Deplugged 1Rl1 12 5
59 1H 0.06 SAI ID Plugged SAI-ID/OD at IH Deplugged 1Rl1 12 5
59 1H 0.09 SAI OD Plugged SAI-ID/OD at IH Deplugged 1Rl1 12 5
65 1H
-0.09 SAI ID 12 5
66 2H
-0.08 SAI ID 12 5
77 5H
-0.18 SAI ID 12 5
78 1H 0.07 SAI ID Deplugged 1RI1 12 5
92 1H
-0.05 SAI ID Plugged SAI-ID at 1H Deplugged Rl1 12 5
93 1H
-0.08 SAI ID 12 6
49 1H
53 1H
-0.12 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 6
53 1H
-0.09 SAI OD Plugged SAI-OD, >2v DOS at IH 12 6
53 1 H 0.04 SAI OD Plugged SAI-OD, >2v DOS at 1 H 12 6
54 3H
12 6
54 3H
56 2H
=
12 6
59 1 H -0.02 SAI 0
0 12 6
=
12 6
65 5H
70 2H
-0.04 SAI OD Plugged SAl-ID/OD at2H Deplugged Rl 12 6
70 2H
-0.03 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 6
70 2H 0.25 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 6
74 3H
-0.02 SAI ID 12 6
93 1C
-0.19 CLT 23 12 7
2 2C -0.04 CLT 38 12 7
4 1C 0
CLT 1
12 7
20 2H
12 7
28 2H
-0.06 SAI ID Plugged SAI-ID/ODat 2H Deplugged Rl 12 7
28 2H
-0.02 SAI 0D Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 7
31 1 H 0.07 SAI ID 12 7
33 TSH -1.95 SAI ID Deplugged IR11 12 7
53 3H 0.01 SAI ID Deplugged 1Rl1 12 7
56 1 H -0.01 SA ID Plugged SAI-ID/ODatH Deplugged Rl 12 7
56 1 H 0.3 SAI 0D Plugged SAI-ID/OD at I H Depfugged I Rl1 12 7
=
12 7
68 3H 0.21 SAI ID 12 7
84 1H 0.02 SAI ID Plugged SAI-ID/OD at IH Deplugged IRI1 12 7
84 1H 0.31 SAl 00 Plugged SAI-ID/OD at 1H Deplugged IR11 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/OD/TWI Status Reason for Plugging
[
Notes 12 7
94 IC
-0.19 CLT 8
12 8
2 2C
-0.04 CLT 42 Plugged 42%TW CLT at 2C 12 8
15 2H
-0.01 SAI ID 12 8
20 2H
51 H
0.01 SAI 00 Plugged SAI-IDIOD at 1H Deplugged Rli 12 8
51 1H 0.01 SAI ID Plugged SAI-IDIOD at IH Deplugged IRI1 12 8 551 H -0.08 SAI ID Plugge Deplugged 1Rl1 12t 8
57 1 H -0.16 SAI ID
=
-Deplugged 1 R 1 12 8
57 1H
-0.16 SAI ID Deplugged 1R11 12 8
61 2H
-0.21 SAI ID 12 8
61 2H
-0.01 SAI ID 12 8
61 2H 0.15 SAI ID 12 8
66 2H -0.23 SAI ID 12 8
67 1H
-0.18 SAI OD Plugged SAI-ID/OD at 1H 12 8
67 11H 0.01 SAI ID Plugged SAI-ID/OD at 1H 12 8
81 1H -0.25 SAI OD Plugged AONDB, >5v Dentat 1 H 12 8
84 1H 0.31 SCI OD Plugged SCI-OD at 1H 12 8
85 1H 0.3 0CI OD Plugged SCI-OD at1H 12 8
86 3H 0.07 SAI OD Plugged SAI-OD at 3H Wedge 12 8
92 2C -0.23 CLT 21 12 8
93 1H
-0.1 SAI ID 12 9
3 1C 0.02 CLT 0
12 9
27 3H -0.13 SAI ID Deplugged IRI1 12 9
28 1H
-0.23 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 9
28 1H
-0.23 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 9
28 1H
-0.17 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 9
30 1H 0.01 SAI ID Deplugged 1Rl1 12 9
38 2H
-0.1 SAI ID Deplugged 1RI1 12 9
45 1H 0.15 SAI ID Deplugged 1Rl1 12 9 53 1H 0.06 SAI ID Deplugged 1Rl1 12 9
56 1H
-0.24 SAI ID 12 9
66 2H 0.14 SAI OD Plugged AONDB, >5v Dent at 2H 12 9
70 1H -0.15 SAI OD Plugged AONDB, >5v Dent at H 12 9
70 1H -0.08 SAI OD Plugged AONDB, >5v Dent at1H 12 9
77 1H
-0.04 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 9
77 1H 0.27 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 9 82 3H 0.2 SAI ID Deplugged 1Rl1 12 9
92 2C
-0.11 CLT 30 12 10 35 IH
-0.07 SAI OD Plugged SAI-ID/OD at 1H Deplugged RI 12 10 35 IH 0.18 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 10 41 2H -0.01 SAI OD Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 RI 1 S
Row Col Loc Inch Ind JID/OD%TW Status Reason for Plugging Notes 12 10 43 1 H 0
12 10 45 2H
-0.16 SAI OD 12 10 49 3H 0.24 SAI ID
=
Deplugged RI1 12 10 62 1H 0.03 SAI ID Deplugged Rll 12 10 67 1H -0.19 SAI ID
=
12 10 68 1H -0.11 SAI ID Deplugged 1RI1 12 10 69 2H
-0.24 SAI ID 12 10 80 1 H -0.21 SAI ID 12 10 81 1 H -0.11 SAI OD 12 10 83 1H -0.19 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1RII 12 10 83 1H -0.17 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 10 83 1H -0.03 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 10 85 4H 0.19 SAI ID 12 11 18 2H
-0.21 SAI OD 12 11 20 2H 0.07 SAI ID Deplugged 1RI 12 11 27 1H -0.23 SAI ID Plugged SAl-ID/OD at 1H Deplugged 1RlI 12 11 27 1H -0.05 SAI OD Plugged SAl-ID/OD at 1H Deplugged 1RII 12 11 27 1H -0.05 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RI 12 11 27 1H 0.15 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RII 12 11 27 2H
-0.32 SAl 00 Plugged SAl-ID/CD at H Deplugged RII 12 11 27 4H 0.13 SAI OD Plugged SAI-ID/OD at 1H Deplugged Rll 12 11 45 1 H 0.2 SAI ID 12 11 47 2H
-0.19 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1RI1 12 11 47 2H
-0.05 SAI ID Plugged SAl-ID/CD at 2H Deplugged Rll 12 11 66 3H
-0.1 SAI ID 12 11 71 IH -0.14 SAI ID Deplugged 1 RI 12 11 71 1H
-0.1 SAI ID Deplugged 1RII 12 11 75 2H
=
=
=
=
Plugged Restriction above IH Deplugged 1RI1 12 11 81 2H 0.1 SAI ID Plugged SCI-lD/SAI-lD at 2H 12 11 81 2H 0.13 SCI ID Plugged SCI-ID/SAI-ID at 2H 12 11 84 2H
-0.16 SAI ID Deplugged 1Rl1 12 11 84 2H 0.15 SAI ID Deplugged Rll 12
_1 86 1H
-0.21 SAl ID Plugged SCI-OD/SAI-ID at H Deplugged Rll 12 11 86 IH 0.16 SAI ID Plugged SCI-OD/SAI-ID at 1H Deplugged RlI 12 11 86 1H 0.35 SCI 0D Plugged SCI-OD/SAI-ID at 1H Deplugged 1Rl1 12 11 86 2H
-0.15 SAI ID Plugged SCI-OD/SAI-ID at 1H Deplugged IR1I 12 11 86 2H 0.06 SAI ID Plugged SCI-OD/SAI-ID at IH Deplugged Rll 12 11 87 1H 0.02 SAI ID Deplugged 1RI 12 11 93 2C -0.13 CLT 28 12 12 3
IC -0.02 CLT 25 12 12 4
1C -0.13 CLT 1
12 12 46 2H -0.11 SAl 00
=
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 l
Row Coll Loc Inch Ind IDIOD %TWj Status Reason for Plugging Notes 12 12 65 2H 0.2 SAI OD 12 12 66 2H 0
SAI ID Plugged SAI-ID/OD at2H Deplugged 1Rl1 12 12 66 2H 0.21 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 12 76 1 H -0.27 SAI 0OD 12 12 77 1H
-0.01 SAI ID Deplugged 1Rl1 12 12 80 1H 0.02 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 12 80 1H 0.18 SAI ID Plugged SAI-ID/OD at 1H Deplugged IRI1 12 12 80 3H
-0.1 SAI ID Plugged SAI-ID/OD at 1H Deplugged IRI1 12 12 80 6H -0.07 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 12 83 2H 0.03 SAI OD 12 12 84 2H 0
SAi ID Plugged SAI-ID/OD at2H Deplugged 1Rl1 12 12 84 2H 0.24 SAI OD Plugged SAI-ID/OD at 2H Deplugged Ril 12 12 84 4H -0.22 SAI OD Plugged SAI-ID/OD at 2H Deplugged I R11 12 13 3
1C
-0.04 CLT 7
12 13 6
2C -0.15 CLT 30 12 13 10 1H
-0.38 SAI ID 12 13 34 1H 0.14 SAI ID Deplugged 1Rl1 12 13 34 2H -0.09 SAI OD Deplugged IRl1 12 13 34 2H 0.06 SAI OD Deplugged 1Rl1 12 13 44 1H 0.01 SAI ID Deplugged 1Rl1 12 13 60 2H 0.01 SAI ID
=
Deplugged 1Rl1 12 13 66 2H 0.33 SAI OD
=
12 13 81 1H
-0.1 SAI ID Plugged SAI-ID/OD at 1 H Deplugged 1Ri1 12 13 81 1H 0.21 SAI OD Plugged SAI-ID/OD at IH Deplugged IRII 12 13 82 5H -0.15 SAI OD 12 13 83 1H
-0.23 SAI OD Deplugged 1 Rl1 12 13 83 1H
-0.01 SAI OD Deplugged 1 Rl1 12 13 83 1H 0.13 SAI OD
=
Deplugged 1Rl1 12 13 83 1H 0.17 SAI OD.
Deplugged 1Rl1 12 13 83 3H -0.18 SAI OD
_Deplugged RlI 12 13 83 3H 0.2 SAI OD Deplugged R1l 12 13 83 5H -0.32 SAI OD
_Deplugged 1R1I 12 13 83 5H -0.14 SAI OD Deplugged Rll 12 13 84 1H
-0.01 SAI ID 12 13 84 1H 0
SAI ID 12 13 84 2H 0.18 SAI OD 12 13 89 1H
-0.16 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 13 89 1H 0.39 SAI OD Plugged SAI-ID/OD at 1H Deplugged IRI1 12 13 92 2C
-0.06 CLT 18 12 14 5
2C
-0.26 CLT 17 12 14 16 4H
-0.04 SAi ID 12 14 30 2H 0.05 SAI OD
=
12 14 45 1 H -0.03 SAI ID
=
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 RI 1 SG Row Col Loc Inch Ind ID/OD %
Status Reason for Plugging
[
Notes 12 14 68 1H
-0.07 SAI ID 12 14 70 1H
-0.05 SAI ID 12 14 74 1H
-0.16 SAI ID Deplugged 1RI1 12 14 76 I 1H 0.08 SAI OD 12 14 84 2H 0.22 SAI OD 12 14 91 1C
-0.15 CLT 16 12 15 5
2C
-0.15 CLT 26 12 15 42 2H 0.02 SAI OD 12 15 74 1H
-0.02 SAI OD 12 16 12 5H -0.03 SAI ID 12 16 30 2H
=
12 16 33 2H 0.01 SAI OD 12 16 40 2H
=
12 16 59 2H 0.07 SAI ID Deplugged 1Rl1 12 16 73 1H
-0.26 SAI ID Plugged SAI-ID/OD at 1H 12 16 73 IH -0.25 SAI OD Plugged SAI-IDIOD at IH 12 16 73 1H
-0.21 SAI ID Plugged SAI-ID/OD at 1H 12 16 76 2H
-0.04 SAI ID Plugged SAI-IDIOD at 2H 12 16 76 2H 0.28 SAI OD Plugged SAI-ID/OD at 2H 12 16 82 IH 0.16 SAI ID Deplugged I Rl 12 16 82 4H 0.14 SAI ID Deplugged 1Rl1 12 16 85 2H
-0.23 SAI ID Deplugged 1R11 12 16 85 2H
-0.05 SAI ID Deplugged 1R11 12 16 87 2H 0.01 SAI ID Deplugged IR11 12 16 88 2H
-0.02 SAI ID Deplugged 1R11 12 17 8
6H
-0.08 SAI ID Plugged SAI-ID/ODat6H Deplugged 1RI1 12 117 18 6H
-0.07 SAI OD Plugged SAI-ID/OD at 6H Deplugged 1 Rl1 12 17 8
6H
-0.07 SAl 00 Plugged SAl-ID/OD at 6H Deplugged 1R11 12 17 9
6H
-0.07 SAI ID Deplugged 1RlI 12 17 16 3H
-0.07 SAI OD 12 17 47 1 H -0.03 SAI OD 12 17 54 1H 0.08 SAI ID Deplugged 1RII 12 17 59 1H 0.1 SAl ID Deplugged IRI1 12 17 66 1H
-0.02 SAI ID Deplugged 1RI1 12 17 67 1H
-0.34 SAI ID Deplugged 1Rl1 12 17 67 1H
-0.28 SAI ID Deplugged 1Rl1 12 17 68 1 H
-0.23 SAI ID Plugged SAI-ID at 1H Deplugged 1Rl1 12 17 77 1H
-0.15 SAI ID Plugged SAI-ID at 1H Deplugged 1RI1 12 17 79 1H 0.29 SAI OD
=
12 17 88 2H 0.13 SAI ID
=
Deplugged lRll !.
I I
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 Rl 1 SG Row Col Loc Inch Ind ID/OD %TW Status Reason for Plugging Notes 12 18 5
2C
-0.02 CLT 46 Plugged 46%TW CLT at 2C 12 18 22 1H 0.13 SAI OD 12 18 63 7H 36.83 AVB wear 17 12 18 63 7H 49.33 AVB wear 21 12 18 64 3H
-0.12 SAI ID Deplugged 1Rl1 12 19 14 2H
-0.01 SAI OD Plugged SAI-ID/OD at 2H Deplugged R1l 12 19 14 2H
-0.01 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1RI 12 19 31 4H
-0.02 SAI ID 12 19 34 2H 0.16 SAI ID Deplugged Rll 12 19 39 2H 0.04 SAI OD
=
12 19 39 7H 36.46 AVB wear 19 12 19 41 1 H -0.12 SAI OD 12 19 41 1 H -0.02 SAI OD 12 19 48 1 H 0.29 SAI OD 12 19 51 1 H
-0.24 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1 R11 12 19 51 1H 0.07 SAI ID Plugged SAI-ID/OD at 1H Deplugged IRI1 12 19 57 2H
-0.08 SAI OD 12 19 67 7H 35.94 AVB wear 26 12 19 67 7H 37.41 AVB wear 16 12 19 67 7H 50.13 AVB wear 26 12 19 67 7H 51.25 AVB wear 21 12 19 67 7H 62.22 AVB wear 23 12 19 74 2H
-0.11 SAI ID
=
12 19 79 1 H -0.13 SAI OD 12 19 79 1 H 0.25 SAI OD 12 19 85 2H
-0.11 SAI OD Deplugged 1 Rl1 12 19 85 2H 0.09 SAI OD Deplugged.1 R 1I 12 19 89 2C
-0.17 CLT 6
12 20 7
2C
-0.17 CLT 44 Plugged 44%TW CLT at 2C 12 20 37 TSH -1.76 SAI ID
-Deplugged RlI 12 20 40 1H
-0.09 SAI OD Deplugged 1Rl1 12 20 40 IH 0.15 SAI OD Deplugged 1Rl1 12 20 43 3H
-0.04 SAI ID 12 20 51 IH -0.18 SAI OD 12 20 51 1H
=
12 20 52 2H 0.13 SAI ID Plugged SAI-ID/OD at 2H Deplugged I Rl1 12 20 52 2H 0.16 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 20 54 1 H 0.08 SAI OD 12 20 58 1H
-0.16 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 20 58 1 H 0.04 SAI ID Plugged SAI-ID/OD at 1 H Deplugged I R11 12 20 58 1H 0.19 SAI ID Plugged SAI-ID/OD at IH Deplugged IRI1 12 20 72 1H
-0.05 SAI OD Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During R 1 SG Row Col Loc Inch Ind
[IDIOD%TV\\
Status Reason for Plugging Notes 12 20 77 1H 0.01 SAI ID Deplugged 1R11 12 20 83 1 H -0.07 SAI OD 12 20 87 1H
-0.01 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 20 87 1H 0.01 SAI OD Plugged SAI-OD, >2v DOS at IH 12 20 87 1H 0.02 SAI OD Plugged SAI-OD, >2v DOS at IH 12 20 87 1H 0.05 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 20 87 1H 0.08 SAI OD Plugged SAI-OD, >2v DOS at 1H 12 21 21 1 H
-0.2 SAI OD 12 21 32 1 H 0.04 SAI OD 12 21 37 4H
-0.07 SAI ID Plugged SAI-lD/OD at 4H Deplugged 1 Rl1 12 21 37 4H 0.13 SAI OD Plugged SAI-ID/OD at 4H Deplugged 1 R1 12 21 37 6H
-0.03 SAI ID Plugged SAI-ID/OD at 4H Deplugged I R1 12 21 38 IH 0.03 SAI ID Deplugged Rl 12 21 42 1H
-0.19 SAI ID Plugged SCI-OD/SAI-OD&ID at 1H Deplugged 1Rl1 12 21 42 1H 0.18 SCI OD Plugged SCI-OD/SAI-OD&ID at 1 H Deplugged 1 R11 12 21 42 1H 0.24 SAI OD Plugged SCI-OD/SAI-OD&ID at 1H Deplugged 1RI1 12 21 42 2H
-0.17 SAI OD Plugged SCI-OD/SAI-OD&ID at 1H Deplugged 1Rl1 12 21 46 1H 0.23 SAI OD Deplugged RlI 12 21 50 1H
-0.14 SAI ID Plugged SAl-ID/OD at 1H Deplugged Rl1 12 21 50 1H 0.04 SAI ID Plugged SAI-ID/OD at IH Deplugged IR11 12 21 50 1H 0.25 SAI OD Plugged SAI-ID/OD at IH Deplugged 1Rl1 12 21 53 6H
-0.25 SAI ID Plugged SAI-IDIOD at 6H Deplugged 1 R1 12 21 53 6H
-0.11 SAI OD Plugged SAI-ID/OD at 6H Deplugged 1Rl1 12 21 55 7H 40.41 AVB wear 25 12 21 55 7H 57.01 AVB wear 15 12 21 57 1H
-0.11 SAI ID Deplugged 1Rl1 12 21 60 2H
-0.21 SAI ID 12 21 65 2H 0.01 SAI ID Deplugged IRI1 12 21 65 7H 26.17 AVB wear 16 Deplugged 1RI1 12 21 65 7H 40.45 AVB wear 17 Deplugged IRl1 12 21 65 7H 57.21 AVB wear 18 Deplugged Rll 12 21 72 4H 0.12 SAI OD 12 21 82 1H -0.03 SAI OD 12 22 32 2H
-0.18 SAI OD Plugged SAI-ID/OD at 2H Deplugged I RI1 12 22 32 2H
-0.1 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1Rl1 12 22 32 2H 0.22 SAI ID Plugged SAI-ID/OD at 2H Deplugged IRI1 12 22 34 1H 0.18 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1Rl1 12 22 34 2H
-0.26 SAI OD Plugged SAI-IDIOD at 2H Deplugged 1 RI1 12 22 34 2H
-0.01 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 22 34 2H 0
SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 R11 12 22 34 2H 0.34 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 R 1 12 22 34 4H
-0.18 SAI OD Plugged SAl-ID/0D at 2H Deplugged I R1 12 22 35 7H 25.13 AVB wear 24 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During I R 1 SG Row Col[ Loc Inch Ind IDlOD%
Status Reason for Plugging Notes 12 22 38 1H
-0.24 SAI OD Plugged SAI-ID/OD at IH Deplugged 1Rl1 12 22 38 H
-0.17 SAI ID Plugged SAID/OD at IH Deplugged IR11 12 22 38 IH 0.23 SAI ID Plugged SAI-ID/OD at IH Deplugged 1Rl1 12 22 38 1H 0.33 SAI OD Plugged SAI-ID/OD at 1H Deplugged IRl1 12 22 42 1H 0.11 SAI ID Deplugged 1Rl1 12 22 43 IH -0.06 SAI OD Plugged SAl-OD, >2v DOS at 1H 12 22 43 1H
-0.05 SAI OD Plugged SAI-OD, >2v DOS at 1 H 12 22 43 1H
-0.05 SAI OD Plugged SAI-OD, >2v DOS at IH 12 22 54 2H 0
SAI ID Deplugged 1 Rl1 12 22 54 7H 0.04 SAI OD Deplugged Rl1 12 22 55 3H 0.07 SAI ID 12 22 57 1H 0.06 SAI OD 12 22 62 2H 0.01 SAI OD
=
12 22 80 IH -0.17 SAI OD 12 22 83 1H
2C
-0.28 CLT 31 12 23 17 IH 0.14 SAI OD
=
Deplugged IRl1 12 23 25 3H
-0.19 SAI ID 12 23 54 1H 0.14 SAI ID 12 23 71 2H
-0.14 SAI OD 12 23 82 1H 0.18 SAI ID 12 24 15 2H 0.09 SAI ID Plugged SAI-ID at 2H Deplugged I RI1 12 24 31 1 H 0.01 SAI OD 12 24 32 1 H 0.08 SAI OD 12 24 48 4H -0.27 SAI OD 12 24 49 2H -0.01 SAI OD _
12 24 55 1 H 0.05 SAI OD 12 24 65 2H 0.08 SAI OD 12 24 74 1 H 0.03 SAI OD 12 24 77 1 H -0.14 SAI ID 12 25 17 2H
-0.28 SAI ID 12 25 32 1 H -0.08 SAI OD 12 25 37 1 H 0.05 SAI OD 12 25 50 2H
-0.06 SAI ID Deplugged 1Rl1 12 25 55 2H 0.19 SAI ID 12 25 72 1H -0.29 SAI OD Plugged SAI-ID/OD at 1H 12 25 72 1H 0.03 SAI ID Plugged SAI-ID/OD at 1H 12 25 74 1 H -0.26 SAI ID 12 25 78 1_H 0.03 SAl 0D 12 25 81 2H
-0.06 SAI OD 12 25 85 2H 0.07 SAI OD 12 25 85 4H -0.09 SAI ID Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1I SG Row Col Loc Inch Ind ID/OD%TVv Status Reason for Plugging Notes 12 25 87 4H -0.05 SAI ID Deplugged 1Rl1 12 26 10 2C -0.13 CLT 29 12 26 17 3H
SAI ID Deplugged 1Rl1 12 26 27 1H -0.03 SAI OD 12 26 27 1 H -0.02 SAI OD 12 26 32 1H 0.04 SAI OD 12 26 32 1H 0.04 SAI OD 12 26 39 2H -0.03 SAI ID I
12 26 52 2H -0.03 SAI OD 12 26 64 2H 0.18 SAI OD 12 26 68 7H 28.91 AVB wear 23 12 26 68 7H 47.24 AVB wear
=
20 12 26 68 7H 67.95 AVB wear 22 12 26 68 7H 86.8 AVB wear 28 12 26 71 2H 0.02 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 26 71 2H 0.22 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 RI1 12 26 73 1H 0
SAI ID
_Deplugged Rll 12 26 77 2H -0.07 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 RI 1 12 26 77 2H 0.13 SAI ID Plugged SAI-IDlODat2H Deplugged IRl1 12 26 77 2H 0.18 SAI OD Plugged SAI-lD/OD at 2H Deplugged 1 R1 12 26 78 1 H -0.02 SAI ID Plugged SAI-ID/OD at 1 H Deplugged 1 R1 12 26 78 1H 0.27 SAI OD Plugged SAI-ID/OD at 1H vDeplugged 1Rl1 12 26 79 1 H 0.04 SAI ID 12 27 10 2C -0.24 CLT 6
12 27 11 1C 0.17 CLT 17 12 27 36 2H
-0.04 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 RII 12 27 36 2H
-0.01 SAI ID Plugged SAI-ID/OD at2H Deplugged 1RI1 12 27 36 3H
-0.08 SAI ID Plugged SAI-ID/OD at2H Deplugged 1Rl1 12 27 50 1H
-0.25 SAI ID I Plugged SAI-ID/OD at 1H 12 27 50 1H -0.07 SAI OD Plugged SAI-ID/OD at 1H 12 27 55 1 H 0.3 SAI ID 12 27 56 1 H -0.22 SAI ID 12 27 57 1H
-0.03 SAI OD Deplugged 1RII 12 27 57 1 H 0
SAI OD Deplugged 1 RI1 12 27 63 2H -0.13 SAI ID Deplugged 1Rl1 12 27 63 2H 0.21 SAI ID Deplugged 1Rl1 12 27 64 3H -0.09 SAI ID 12 27 65 2H 0.07 SAI ID Deplugged RI1 12 27 66 2H 0.04 SAI OD 12 27 67 1H
-0.18 SAI ID Deplugged IRl1 12 27 67 4H
-0.1 SAI ID
=
Deplugged 1Rl1 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During I R 1I SG Row _Col Loc lInch Ind jID/OD /0 TWJ Status Reason for Plugging Notes 12 27 69 IH
-0.09 SAI ID
=
Deplugged IRl1 12 27 69 1H 0.06 SAI ID Deplugged IRl1 12 27 83 2H
-0.22 SAI OD 12 27 83 3H 0.12 SAI OD 12 28 11 2C
-0.13 CLT 4
12 28 27 2H
-0.06 SAI OD 12 28 36 2H 0.06 SAI OD 12 28 47 3H 0.18 SAI ID
=
DepluggedlR1l 12 28 50 IH 0.02 SVI OD Plugged SVI-OD at 1 H 12 28 50 1H 0.06 SAI OD Plugged SVI-OD at 1 H 12 28 56 1 H -0.02 SAI OD Plugged SAI-ID/0D at 2H Deplugged 1 Rl1 12 28 56 2H 0.03 SAI ID Plugged SAI-ID/ODat2H Deplugged 1Rl1 12 28 56 2H 0.06 SAI OD Plugged SAI-ID/OD at 2H Deplugged IR11 12 28 58 1H
-0.19 SAI ID Plugged SAI-ID/OD at IH Deplugged IR11 12 28 58 1H
-0.06 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1RI1 12 28 66 2H 0.03 SAI ID 12 28 68 2H
-0.25 SAI OD Plugged SAI-ID/OD at 6H Deplugged 1 R 1I 12 28 68 3H
-0.12 SAI OD Plugged SAI-ID/ODat6H Deplugged Rl1 12 28 68 3H
-0.01 SAI OD Plugged SAI-ID/OD at 6H Deplugged 1 Rl1 12 28 68 6H 0.03 SAI OD Plugged SAI-ID/OD at 6H Deplugged 1 Rl1 12 28 68 6H 0.1 SAI ID Plugged SAI-ID/OD at 6H Deplugged I Rl1 12 29 12 2C -0.13 CLT 29 12 29 24 3H 0.2 SAI ID
=
Deplugged I Rl1 12 29 26 1 H -0.06 SAI OD 12 29 38 1H 0.06 SAI OD Deplugged 1Rl1 12 29 40 5H
-0.2 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 R11 12 29 43 2H 0.1 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 R11 12 29 43 2H 0.11 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 R11 12 29 49 3H
-0.03 SAI ID 12 29 56 2H
-0.19 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 29 56 2H 0.07 SAI ID Plugged SAI-ID/OD at 2H Deplugged I Rl1 12 29 61 3H 0.01 SAI OD 12 29 66 1H 0.02 SAI ID Deplugged 1Rl1 12 29 67 2H
-0.06 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 29 67 2H 0.1 SAI OD Plugged SAI-ID/OD at2H Deplugged 1Rl1 12 29 67 3H
-0.13 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 29 69 1H 0.08 SAI OD 12 29 77 2H
-0.17 SAI OD Plugged SAI-ID/OD at 1H 12 30 16 1H 0.01 SAI ID Plugged SAl-ID/OD at 1H Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col] Loc Inch Ind ID/OD%TW Status Reason for Plugging Notes 12 30 21 2H -0.03 SAI OD Plugged OD-SAI at 2H Wedge 12 30 21 2H 0.16 SAI OD Plugged OD-SAI at 2H Wedge 12 30 30 1H
-0.02 SAI OD Deplugged 1RI 12 30 30 1H 0.14 SAI OD Deplugged 1Rl1 12 30 56 1H 0.03 SAI ID Deplugged 1RI1 1_2 30 62 H
-0.12 SAl ID 12 30 62 1 H 0.07 SAI ID 12 30 67 2H -0.23 SAI ID Deplugged 1RI1 12 31 32 IH -0.02 SAI OD
= Plugged SAI-ID/ODat3H Deplugged IRII 12 31 32 3H
-0.23 SAl OD Plugged SAI-IDIOD at 3H Deplugged 1Rl1 12 31 32 3H -0.04 SAI ID Plugged SAl-ID/OD at 3H Deplugged 1 R 1 12 31 32 3H 0.07 SAI ID Plugged SAI-ID/OD at 3H Deplugged I Rl1 12 31 37 3H -0.11 SAI ID 12 31 37 3H 0.02 SAI ID 12 31 44 4H 0.25 SAI OD 12 31 47 2H
-0.03 SAI ID Deplugged IRI1 12 31 53 2H
-0.19 SAI ID Deplugged 1Rl1 12 31 62 1 H
-0.22 SAI OD 12 31 64 1 H 0.09 SAI OD 12 31 66 4H 0.07 SAI ID Deplugged 1R1I 12 31 68 1H 0.07 SAI ID Deplugged R11 12 31 78 5H 0.63 SAI ID 12 31 80 4H
-0.19 SAI ID Deplugged IRI1 12 32 37 3H 0.06 SAI ID 12 32 44 4H
-0.12 SAI ID Deplugged Rll 12 32 45 3H 0
-0.1 SAI ID Deplugged 1Rl1 12 32 50 7H 33.1 AVB wear 24 12 32 50 7H 57.6 AVB wear 22 12 32 50 7H 83.51 AVB wear 29 12 32 52 2H 0.14 SAI ID Plugged SAI-ID at 2H Deplugged IRI1 12 32 54 1 H
-0.05 SAI OD 12 32 54 1 H 0.25 SAI OD 12 32 55 7H 32.47 AVB wear 20 Plugged 42%TWAVB Wear 12 32 55 7H 57.06 AVB wear 28 Plugged 42%TWAVB Wear 12 32 55 7H 83.86 AVB wear 42 Plugged 42%TWAVB Wear 12 32 55 7H 108.5 AVB wear 19 Plugged 42%TW AVB Wear 12 32 57 2H 0.09 SAI OD Plugged AONDB, >5v Dent at 2H 12 32 62 1 H
-0.02 SAI ID 12 33 40 1 H -0.03 SAI OD 12 33 47 7H 86.61 AVB wear 19 12 33 54 7H 59.28 AVB wear 13 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During IRl1 SG Row Col Loc Inch Ind ID/OD%TW Status Reason for Plugging Notes 12 33 57 2H 0.12 SAI ID Deplugged 1RI1 12 33 68 2H 0.07 SAI ID 12 33 71 1 H
-0.02 SAI OD 12 33 72 4H 0.02 SAI ID Deplugged 1Rl1 12 33 73 1 H -0.07 SAI OD Plugged OD-SAI at 1H Wedge 12 34 17 IC
-0.17 CLT 19 12 34 19 1 C -0.26 CLT 7
12 34 36 3H
-0.05 SAI ID 12 34 42 2H 0.11 SAI ID 12 34 45 1 H
-0.01 SAI OD 12 34 47 2H 0.05 SAI ID
=
_____Deplugged I RI1 12 34 49 2H
-0.18 SAI ID Deplugged 1Rl1 12 34 51 6H 0.1 SAI ID
=
12 34 51 7H 88.43 AVB wear 38 12 34 51 7h 115.1 AVB wear 21 1_2 34 53 2H
-0.07 SAI ID Deplugged IRI 12 34 53 2H
-0.02 SAI ID Deplugged 1Rl1 12 34 55 IH
-0.18 SAI ID Deplugged 1Rl1 12 34 57 2H
-0.11 SAI ID Deplugged 1RI1 12 34 57 2H 0.021 SAI ID Deplugged IRl1 12 34 57 4H
-0.11 SAI OD Deplugged IRI1 12 34 58 2H -0.01 SAI ID Deplugged IRI1 12 34 59 2H 0.01 SAI ID Deplugged Rll 12 34 61 1H
-0.03 SAI OD 12 34 65 2H 0.01 SAI ID 12 34 66 7H 89.11 AVB wear 20 12 34 71 1H 0.13 SAI OD Deplugged 1Rl1 12 34 71 1H 0.27 SAI OD Deplugged IR11 12 35 19 1C
-0.3 CLT 16 12 35 19 2C
-0.15 CLT 11 12 35 45 2H
-0.31 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 RI1 12 35 45 2H
-0.01 SAI ID Plugged SAI-ID/OD at 2H Deplugged 1 Rl1 12 35 49 2H
-0.01 SAI ID Deplugged 1Rl1 12 35 52 3H
-0.05 SAI ID _
12 35 56 2H 0.14 SAI ID 12 35 65 2H
-0.18 SAI OD Plugged SAI-IDIOD at 2H Deplugged I Rl1 12 35 65 2H
-0.01 SAI OD Plugged SAI-IDIOD at 2H Deplugged 1 R 1 12 35 65 2H 0
SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 RI1 12 35 65 2H 0.02 SAI ID Plugged SAI-IDIOD at 2H Deplugged I Rl1 12 35 65 3H
-0.1 SAI OD Plugged SAI-ID/OD at 2H Deplugged I Rl1 12 35 65 3H 0.15 SAI OD Plugged SAI-ID/OD at 2H Deplugged 1 RI1 12 35 65 3H 0.16 SAI OD Plugged SAI-ID/OD at 2H Deplugged IRI1 12 35 68 1 H 0.03 SAI OD -@
I " I X,,, :
t I of 11.
r,,
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/ODl%TV\\
Status Reason for Plugging Notes 12 35 69 2H -0.05 SAI OD Plugged SCI-OD/SAI-OD at 2H 12 35 69 2H 0.12 SCI OD Plugged SCI-OD/SAI-OD at 2H 12 35 70 2H
-0.05 SAI ID 12 36 53 IH
-0.2 SA OD Deplugged RI 12 36 53 1 H 0.32 SAI OD Deplugged I Rl1 12 36 53 3H
-0.09 SAI ID Deplugged 1Rl1 12 36 58 7H 63.36 AVB wear 14 12 36 60 4H
-0.11 SAI ID 12 36 63 7H 63.87 AVB wear 17 12 36 63 7H 94.72 AVB wear 33 12 36 64 7H 34.64 AVB wear 25 Plugged 40%TW AVB Wear 12 36 64 7H 63.32 AVB wear 40 Plugged 40%TWAVB Wear 12 36 64 7H 94.45 AVB wear 29 Plugged 40%TWAVB Wear 12 36 68 7H 35.07 AVB wear 19 12 36 68 7H 62.82 AVB wear 14 12 37 19 1C 0.17 CLT 33 12 37 30 IH -0.07 SAI OD Plugged OD-SAI at I H Wedge 12 37 34 3H 0.03 SCI ID Plugged SCI-ID at 3H 12 37 53 2H
-0.04 SAI ID Deplugged 1Rl1 12 37 65 1H
-0.31 SAI ID I Plugged SAl-IDat IH Deplugged IRI1 12 37 69 1H
-0.15 SAI ID Deplugged 1Rl1 12 37 69 1H
-0.01 SAI ID Deplugged 1Rl1 12 37 69 IH 0.2 SAI ID Deplugged 1Rl1 12 37 69 3H 0.17 SAI ID Deplugged R11 12 37 70 1H 0.04 SAI ID Deplugged 1Rl1 12 37 72 1H
-0.01 SAI ID Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 37 72 1H 0.24 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 37 73 3H 0.01 SAI ID 12 37 74 3H 0.06 SAI ID Deplugged IRl1 12 38 22 2C
-0.13 CLT 6
12 38 23 2C
-0.13 CLT 37 12 38 25 1 C
-0.28 CLT 14 12 38 25 2C
-0.06 CLT 15 12 38 34 7H 34.99 AVB wear 14 12 38 34 7H 65.67 AVB wear 12 12 38 41 1 H
-0.12 SAI OD 12 38 41 1 H 0.05 SAI OD 12 38 49 7H 129.5 AVB wear 32 12 38 51 7H 98.42 AVB wear 20 12 38 51 7H 128.7 AVB wear 18 12 38 52 7H 66.88 AVB wear 21
_ =
12 38 53 7H 129.3 AVB wear 31 12 38 60 7H 35.55 AVB wear 15 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/OD %TW Status Reason for Plugging Notes 12 38 60 7H 66.71 AVB wear 23 12 38 64 7H 98.97 AVB wear 22 12 38 64 7H 129.2 AVB wear 25 12 38 66 1H 0.08 SAI ID 12 38 66 7H 98.78 AVB wear
=
19 12 38 66 7H 128.6 AVB wear 22 12 38 67 7H 98.15 AVB wear 17 12 38 70 1H
-0.06 SAI OD Plugged SAI-ID/OD at 1H Deplugged 1Rl1 12 38 70 1H
-0.04 SAI ID Plugged SAI-ID/OD at 1H Deplugged IRI1 12 38 72 7H 66.47 AVB wear 19 12 38 72 7H 98.18 AVB wear 11 12 39 37 1H 0
SAI OD Plugged OD-SAI at 1H Wedge 12 39 51 7H 36.17 AVB wear 21 12 39 51 7H 67.99 AVB wear 34 12 39 51 7H 101.5 AVB wear 22 12 39 57 7H 101.7 AVB wear 21 12 39 66 7H 100.9 AVB wear 11 12 39 69 7H 132.1 AVB wear 24 12 39 70 1H
-0.1 SAI OD 12 39 71 7H 67.85 AVB wear 23 12 39 71 7H 100.7 AVB wear 27 12 40 27 1 H 0
SAI OD Plugged SAI-OD, >2v DOS at 1H 12 40 42 7H 36.14 AVB wear 7
12 40 54 7H 69.67 AVB wear 40 Plugged 40%TW AVB Wear 12 40 54 7H 104.3 AVB wear 24 Plugged 40%TW AVB Wear 12 40 54 7H 136.7 AVB wear 17 Plugged 40%TWAVB Wear 12 40 56 2H 0.05 SAI OD 1_2 40 63 1H
-0.01 SA ID Plugged SAI-ID/OD at 1H Deplugged IRI 12 40 63 1H 0.2 SAI 0D Plugged SAI-IDIOD at 1H Deplugged RI1 12 40 68 2H
-0.13 SAI OD 12 41 33 1 C -0.02 CLT 15 12 41 46 7H 106.2 AVB wear 19 12 41 50 7H 71.21 AVB wear 15 12 41 52 7H 106.6 AVB wear 13 12 41 54 3H
-0.26 SAI OD 12 42 28 2H 0.02 SAI OD Plugged SAI-ID/OD at 2H 12 42 28 2H 0.03 SAI ID Plugged SAI-ID/OD at 2H 12 42 31 1H
-0.03 SAI OD Plugged OD-SAI at 1H Wedge 12 42 55 1 H -0.01 SAI OD 12 42 61 2H
-0.02 SAI OD Plugged OD-SAI at 2H Wedge 12 43 32 1 C
-0.17 CLT 26 12 43 33 1 C -0.24 CLT 27 12 43 49 3H
-0.04 SAI ID Deplugged 1Rl1 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/OD%TV\\
Status Reason for Plugging Notes 12 43 64 2C
-0.17 CLT 33 12 45 42 IH -0.02 SAI OD 12 45 58 1C -0.04 CLT 7
12 46 43 1C -0.34 CLT 28 13 2
14 TSH -8.36 SVI ID
.I__
I_I 13 4
9 3H
=
13 5
11 3H
12 1H
=
13 5
=
13 6
=I.
13 8
6 3H 0.02 SAI OD Plugged OD-SAI at 3H Wedge 13 8
77 1H 0.01 SAI OD Plugged AONDB, >5v Dent 13 10 47 2H 0.08 SAI OD 13 11 50 1 H -0.04 SAI OD Plugged AONDB, >5v Dent 13 12 34 7H 29.98 AVB wear 24 Plugged Preventative U-bend Wear 13 15 4
1C
-0.09 CLT 16 13 15 64 7H 40.87 AVB wear 11 13 16 78 3H 0
SAI OD Plugged SAI-OD and ligament indication 13 19 80 IH 0.05 SAI OD 13 19 88 10 0.09 CLT 20 13 20 33 1 H -0.06 SAI OD 13 21 25 7H 39.65 AVB wear 10 13 23 33 7H 42.83 AVB wear 9
13 23 57 7H 61.01 AVB wear 13 13 23 57 7H 42.71 AVB wear 12 13 25 40 7H 46.26 AVB wear 10 13 25 82 1 H 0
SAI OD 13 27 48 7H 71.1 AVB wear 10 13 27 48 7H 29.15 AVB wear 10 13 27 49 1 H -0.01 SAI OD 13 27 52 TSH -0.07 SCI OD Plugged OD-SCI atTSH 13 28 45 7H 73.75 AVB wear 10 13 28 45 7H 51.3 AVB wear 12 13 28 52 7H 72.83 AVB wear 9
13 28 52 7H 50.98 AVB wear 8
13 28 56 7H 50.51 AVB wear 10 13 28 56 7H 73.46 AVB wear 10 13 28 63 7H 50.33 AVB wear 10 13 29 48 7H 29.8 AVB wear 10 13 30 45 TSH -1.86 SAI ID 13 30 49 7H 99.71 AVB wear 15 13 30 49 7H 53.79 AVB wear I 11 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind I1D/OD %TW Status Reason for Plugging Notes 13 30 58 7H 101.8 AVB wear 19 13 30 58 7H 78.37 AVB wear 32 13 30 58 7H 30.02 AVB wear 24 13 30 58 7H 53.42 AVB wear 36 13 31 36 TSH -2.87 SAI ID 13 31 49 7H 55.51 AVB wear 12 13 32 24 2H
-0.03 SAI OD 13 32 38 7H 31.78 AVB wear 12 13 32 38 7H 56.66 AVB wear 28 13 32 40 1 H
=
13 32 61 7H 55.87 AVB wear 28 13 32 61 7H 83.42 AVB wear 39 13 32 61 7H 32.64 AVB wear 16 13 32 61 7H 56.43 AVB wear 27 13 32 75 2H 0.06 SAI OD Plugged OD-SAI at 2H Wedge 13 33 27 7H 86.66 AVB wear 12 13 33 37 TSH -5.77 SAI ID 13 33 40 1 H 0.03 SAI OD Plugged
>2 volt DOS, OD-SAI at 1 H 13 33 56 7H 33.12 AVB wear 33 13 33 56 7H 57.8 AVB wear 34 13 33 56 7H 111.5 AVB wear 23 13 33 56 7H 85.36 AVB wear
=
38 13 33 57 7H 57.86 AVB wear 18 13 33 64 7H 32.3 AVB wear 13 13 33 64 7H 57.78 AVB wear 21 13 33 64 7H 86.1 AVB wear 11 13 34 39 7H 33.13 AVB wear 20 13 34 58 7H 88.56 AVB wear 40 Plugged
>40%TWAVB Wear 13 34 58 7H 59.39 AVB wear 18 Plugged
>40%TW AVB Wear 13 34 68 7H 59.6 AVB wear 13 13 34 78 2C
-0.25 CLT 4
13 35 29 7H 61.08 AVB wear 13 13 35 34 7H 92.12 AVB wear 12 13 35 41 7H 61.11 AVB wear 11 13 35 48 7H 61.77 AVB wear 15 13 35 48 7H 91.41 AVB wear 14 13 35 57 7H 61.09 AVB wear 10 13 35 68 7H 117.4 AVB wear 10 13 36 36 7H 62.23 AVB wear 13 13 36 56 7H 93.64 AVB wear 21 13 36 56 7H 62.55 AVB wear
=
25 13 36 56 7H 121.9 AVB wear 15 13 36 57 7H 93.5 AVB wear 15 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 Rl1 SG Row CO1 Loc J Inch Ind ID/ODj°/OTWj Status Reason for Plugging Notes 13 36 59 7H 93.54 AVB wear 12
=
13 36 61 7H 93.92 AVB wear 34 13 36 61 7H 62.25 AVB wear 30 13 36 61 7H 121.2 AVB wear _
20 13 37 34 7H 97.06 AVB wear 19 13 37 45 7H 64.01 AVB wear 27 13 37 45 7H 122.8 AVB wear 28 13 37 45 7H 96.82 AVB wear 36 13 37 45 7H 124.7 AVB wear 29 13 37 45 7H 64.85 AVB wear 26 13 37 50 7H 63.93 AVB wear 36 13 37 68 7H 95.63 AVB wear 11 13 37 68 7H 64.7 AVB wear 20 13 37 69 7H 95.41 AVB wear 27 13 37 69 7H 64.31 AVB wear 10 13 37 70 7H 95.38 AVB wear 20 13 37 70 7H 64.54 AVB wear 10 13 37 75 2C
-0.3 CLT 17 13 38 45 7H 99.21 AVB wear 19 13 38 45 7H 127.4 AVB wear 14 13 38 45 7H 66.02 AVB wear 8
13 39 45 7H 68.05 AVB wear 12 13 39 45 7H 102.3 AVB wear 10 13 39 46 TSH -2.32 SAI ID =
13 39 52 7H 67.53 AVB wear 11 13 39 58 1H 0
SAI OD Plugged OD-SAI at 1H Wedge 13 39 58 7H 101.4 AVB wear 13 Plugged OD-SAI at 1H Wedge 13 39 66 7H 131.2 AVB wear 23 13 39 69 7H 67.73 AVB wear 10 13 40 34 7H 68.62 AVB wear 18 13 40 34 7H 104.1 AVB wear 25 13 40 34 7H 134 AVB wear 13 13 40 41 7H 134.3 AVB wear 28 13 40 41 7H 104.1 AVB wear 24 13 40 50 3H 0
SAI OD 13 40 63 7H 134.8 AVB wear 14 13 41 28 2C -0.27 CLT 31 13 41 50 7H 69.89 AVB wear 15 13 41 50 7H 106.2 AVB wear 16 13 41 50 7H 137.8 AVB wear 23 13 41 52 7H 70.29 AVB wear 11 13 41 52 7H 106.3 AVB wear 10 13 41 61 7H 69.53 AVB wear 11 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1I SG l Row Coll Loc [Inch Ind ID/OD %T/ Status Reason for Plugging Notes 13 41 63 2H 0.01 SAI OD 13 42 28 2C
-0.2 CLT 0
13 42 32 2C -0.18 CLT 0
13 42 45 7H 109.3 AVB wear 10 13 42 45 7H 72.05 AVB wear 1 1 13 43 36 2C
-0.22 CLT 21 13 43 37 2C -0.17 CLT 12 13 43 57 7H 37.61 AVB wear 10 13 43 64 1 C
-0.2 CLT 32 13 45 43 2C
-0.1 CLT 0
14 2
50 2H
-0.01 SAI OD Plugged AONDB, >5 volt dent at IH 14 2
92 IC -0.22 CLT 33 14 3
=
14 3
3 IC
-0.2 CLT 5
14 4
3 2C
-0.11 CLT 3
14 4
6 3H
72 2H 0
78 3H
3 2C
-0.13 CLT 2
14 7
31 1H
-0.03 SAI OD Plugged AONDB, >5 volt dent at 2H 14 8
29 1H
>2 volt DOS, OD-SAI at IH 14 8
30 1H
-0.02 SVI OD Plugged OD-SVI at 1H 14 8
2 2C
-0.22 CLT 27 14 9
5 2C 0.09 CLT 7
14 9
9 3H
-0.09 SAl OD 14 9
2C 0.05 CLT 0
14 11 19 3H
-0.15 SAI OD 14 11 46 1H 0.09 SAI OD 14 11 46 1H 0.08 SAI OD 14 11 53 1H
-0.22 SAI OD 14 12 14 3H 0.05 SAI OD 14 12 72 1H 0.03 SAI OD 14 13 6
-0.11 SAI OD 14 13 51 1H 0.03 SAI OD 14 14 34 1H
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications dentified During 1 RI I SG Row Coi Loc Inch Ind IODTW Status Reason for Plugging Notes 14 14 36 1 H 0.06 SAI OD 14 15 22 7H 38.29 AVB wear
=
10 14 15 29 1 H 0
=
=
14 16 65 2H 0.16 SAI OD 14 16 66 1 H 0.04 SAI OD 14 16 66 1H -0.13 SAI OD 14 17 4
2C -0.14 CLT 0
14 17 6
2C -0.02 CLT 0
14 17 24 1 H 0.39 SAI ID 14 17 32 1 H -0.05 SAI OD
=
14 17 39 1H 0.01 SAI OD Plugged OD-SVI at lH 14 17 39 1H -0.08 SVI OD Plugged OD-SVI at 1H 14 17 39 TSH -9.38 SCI ID Plugged OD-SVI at 1H 14 17 45 1H -0.17 SAI OD Plugged AONDB >5 volt dent at 1H 14 18 6
2C 0.05 CLT 2
14 19 32 1H 0.02 SAI OD 14 19 40 1H 0.03 SAI OD 14 19 47 1H -0.01 SAI OD 14 20 25 1H -0.64 SAI ID 14 21 51 1 H -0.1 SAI OD 14 21 67 5H -0.14 SAI ID 14 21 76 1 H -0.14 SAI ID 14 21 84 1 H 0.05 SAI ID
=
14 22 34 1 H -0.03 SAI OD 14 22 55 1H 0.02 SAI OD Plugged AONDB, >5 volt dent at 1H 14 23 7 TSH -8.19 SAI ID 14 24 13 2C
-0.09 CLT 16 14 24 56 7H 43.8. AVB wear 10 14 24 62 1 H 0.02 SAI OD 14 24 75 1 H 0.14 SAI OD 14 25 60 1 H 0.01 SAI OD 14 26 37 6H 0.17 SAI ID 14 26 56 7H 87.56 AVB wear 22 14 26 61 7H 31.46 AVB wear 10 14 27 11 2C -0.11 CLT 24 14 27 12 2C -0.09 CLT 19 14 27 34 1 H 0.14 SAI OD 14 27 34 5H -0.07 SAI OD 14 27 36 4H -0.17 SAI 0D
=
14 27 76 7H 48.23 AVB wear 13 14 27 76 7H 70.6 AVB wear 11 Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During R11 SG Row Col Loc Inch Ind lID/OD%TV Status Reason for Plugging
]
Notes 14 28 12 2C
-0.07 CLT 28 14 28 57 TSH -7.14 SAI ID 14 28 57 TSH -3.16 SAI ID 14 28 63 1 H 0.09 SAI OD =
14 28 63 1 H 0.1 SAI OD 14 29 34 7H 32.35 AVB wear 17 14 29 34 7H 95.75 AVB wear 26 14 29 34 7H 75.52 AVB wear 17 14 29 57 2H -0.11 SAI OD 14 30 59 1H
-0.14 SAI OD 14 31 34 7H 102.5 AVB wear 17 14 31 34 7H 80.25 AVB wear 24 14 31 34 7H 54.13 AVB wear 20 14 31 42 7H 35.21 AVB wear 16 14 31 42 7H 56.17 AVB wear 10 14 31 55 7H 79.5 AVB wear 29 14 31 55 7H 54.66 AVB wear 23 14 31 64 7H 53.85 AVB wear 15 14 31 67 7H 107.4 AVB wear 12 14 31 67 7H 79.65 AVB wear 14 14 31 67 7H 80.6 AVB wear 19 14 31 72 7H 107.2 AVB wear 12 14 32 36 7H 56.01 AVB wear 29 14 32 36 7H 34.33 AVB wear 14 14 32 43 7H 103 AVB wear 24 14 33 16 2C
-0.2 CLT 0
14 33 33 7H 85.21 AVB wear 14 14 33 33 7H 109.6 AVB wear 15 14 33 53 7H 35.02 AVB wear 14 14 33 55 1 H 0.02 SAI OD 14 33 58 1 H -0.09 SAI OD 14 34 16 2C
-0.22 CLT 40 Plugged 40% TW CLT at 2H 14 34 32 7H 59.47 AVB wear 12 14 35 20 20
-0.16 CLT 26 14 35 21 2C
-0.13 CLT 24 14 35 22 2C -0.09 CLT 15 14 35 36 2H 0.25 SAI ID 14 35 44 7H 37.48 AVB wear 32 14 35 53 7H 60.23 AVB wear 30 14 35 53 7H 121.2 AVB wear 16 14 35 56 3H 0.05 SAI ID 14 35 56 3H
-0.1 SAI ID =
14 35 58 7H 33.29 AVB wear 18 1 4
I i
Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind ID/OD/OTW Status Reason for Plugging l
Notes 14 35 58 7H 60 AVB wear 38 14 35 58 7H 90.23 AVB wear 13 14 35 61 2H
-0.05 SAI ID 14 35 65 7H 90.26 AVB wear 23 14 35 65 7H 60.19 AVB wear 32 14 35 65 7H 36.36 AVB wear 20 14 35 66 7H 36.36 AVBwear 16 14 35 66 7H 89.8 AVB wear 21 14 35 66 7H 60.05 AVB wear 29 14 35 68 3H
-0.09 SAI ID 14 36 19 2C
-0.2 CLT 12 14 36 46 7H 119.1 AVBwear 24 14 36 47 1H 0.14 SAI OD 14 36 52 7H 92.09 AVB wear 36 14 36 52 7H 62.76 AVB wear 32 14 36 52 7H 124.1 AVBwear 27 14 36 57 7H 61.39 AVB wear 22 14 36 57 7H 34.12 AVB wear 25 14 36 59 7H 93.47 AVB wear 13 14 36 61 7H 123.1 AVB wear 26 14 36 61 7H 61.67 AVB wear 38 14 36 61 7H 124.2 AVBwear 25 14 36 61 7H 93 AVBwear 34 14 37 53 7H 127.8 AVB wear 16 14 37 53 7H 94.75 AVB wear 33 14 37 53 7H 63.8 AVBwear 15 14 37 53 7H 37.13 AVBwear 23 14 37 54 7H 94.82 AVB wear 11 14 37 66 7H 63.19 AVB wear 17 14 37 66 7H 95.09 AVB wear 10 14 37 66 7H 37.53 AVBwear 14 14 38 21 2C -0.16 CLT 17 14 38 62 7H 130.3 AVBwear 11 14 38 69 2H 0.05 SAI ID 14 38 72 1H 0.32 SAI ID 14 39 23 2C -0.16 CLT 11 14 39 48 3H 0.13 SAI ID
=
14 39 58 1H 0.25 SAI ID 14 39 58 7H 100.2 AVB wear 26 14 39 58 7H 133.4 AVB wear 14 14 39 58 7H 36.25 AVB wear 11 14 39 58 TSH
-6.2 SAI ID
=
14 39 66 1H -0.03 SAI OD Enclosure PG&E Letter DCL-03-054 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R 1 SG Row Col Loc Inch Ind 1D/O0 TV Status Reason for Plugging Notes 14 40 63 7H 68.02 AVB wear 11 14 40 63 7H 103 AVB wear 12 14 40 63 7H 68.39 AVB wear 17 14 40 64 1 H 0.08 SAI OD 14 40 64 7H 103.2 AVB wear 33 14 40 64 7H 68.08 AVB wear 22 14 40 66 7H 102.7 AVB wear 12 14 41 63 7H 105 AVB wear 19 14 41 63 7H 69.47 AVB wear 14 14 42 32 1H
-0.16 SAI OD Plugged AONDB, >5voltdentat 1 H 14 42 59 7H 142.9 AVB wear 10 14 42 61 7H 70.51 AVB wear 32 14 43 37 7H 72.84 AVB wear 11 14 43 46 7H 143.9 AVB wear 6
14 43 55 2H 0.32 SCI OD Plugged OD-SCI at 2H 14 43 56 7H 110 AVB wear 36 14 43 56 7H 145.5 AVB wear 39 14 43 56 7H 145.9 AVB wear 26 14 43 57 7H 145.6 AVB wear 30 14 43 57 7H 110.4 AVB wear 34 14 43 59 7H 111.1 AVB wear 12 14 43 65 7H 109.6 AVB wear 33 14 44 34 2C -0.23 CLT 13 14 44 57 2C
-0.04 CLT 10 14 44 58 7H 74.07 AVB wear 11 14 45 58 2C
-0.18 CLT 23 14 45 58 7H 115.6 AVB wear 24 14 46 42 1H
-0.15 SAI ID I
14 46 44 1H 0
= I II i
I;