| | | Reporting criterion |
|---|
| 05000293/LER-1978-002-01, /01X-1:on 780120,100-ft Shielding Mast Fell Across 345 Kv Yard Bus Works & Interrupted Power to Startup Transformer from Transmission Line 355.Caused by Cyclical Fatigue Cracking at Stress Points Due to Wind | /01X-1:on 780120,100-ft Shielding Mast Fell Across 345 Kv Yard Bus Works & Interrupted Power to Startup Transformer from Transmission Line 355.Caused by Cyclical Fatigue Cracking at Stress Points Due to Wind | |
| 05000293/LER-1978-004, Forwards LER 78-004/03L-0 | Forwards LER 78-004/03L-0 | |
| 05000293/LER-1978-019, Forwards Updated LER 78-019/03X-1 | Forwards Updated LER 78-019/03X-1 | |
| 05000293/LER-1978-019-03, Inboard MSIV-AO-203-1D Declared Inoperable & Outboard MSIV-AO-203-2D Secured in Close Condition When MSIV-AO-203-1 Disc Separated from Stem. Caused by High Cycle Bending Fatigue | Inboard MSIV-AO-203-1D Declared Inoperable & Outboard MSIV-AO-203-2D Secured in Close Condition When MSIV-AO-203-1 Disc Separated from Stem. Caused by High Cycle Bending Fatigue | |
| 05000293/LER-1978-040, Forwards LER 78-040/03L-0 | Forwards LER 78-040/03L-0 | |
| 05000293/LER-1978-040-03, /03L-0 on 780808:time Delay Relay Tdu 2E-K5B Settings Were Incorrect Due to Minor Setpoint Drift. Adjustments Were Made.(Encl to 7809180302 | /03L-0 on 780808:time Delay Relay Tdu 2E-K5B Settings Were Incorrect Due to Minor Setpoint Drift. Adjustments Were Made.(Encl to 7809180302 | |
| 05000293/LER-1978-045-03, /03L-0:on 780926,indicator Needle for TI-5047 Water Temp Gauge Snapped Off from Dusting.Caused by Needle Being Exposed by Broken Protective Covering | /03L-0:on 780926,indicator Needle for TI-5047 Water Temp Gauge Snapped Off from Dusting.Caused by Needle Being Exposed by Broken Protective Covering | |
| 05000293/LER-1978-045, Forwards LER 78-045/03L-0 | Forwards LER 78-045/03L-0 | |
| 05000293/LER-1978-046-03, /03L-0 on 781006:oxygen Analyzer Valves CV-5065-12,CV-5065-16 & CV-5065-25 Appeared Inoperable,But Local Observation Showed Valves Working Properly.Caused by Switch Misalignment.Ler Inconsistent W/Ler in Cover Ltr | /03L-0 on 781006:oxygen Analyzer Valves CV-5065-12,CV-5065-16 & CV-5065-25 Appeared Inoperable,But Local Observation Showed Valves Working Properly.Caused by Switch Misalignment.Ler Inconsistent W/Ler in Cover Ltr | |
| 05000293/LER-1978-046, Forwards LER 78-046/03L-0 | Forwards LER 78-046/03L-0 | |
| 05000293/LER-1978-047-03, /03L-0 on 781002:Position of Chief Radiol Engr Was Incorp Into PNPS Organization Which Assumed Responsibilities of Health Physics Organization.Caused by Efforts to Improve Quality of Health Physics Prog | /03L-0 on 781002:Position of Chief Radiol Engr Was Incorp Into PNPS Organization Which Assumed Responsibilities of Health Physics Organization.Caused by Efforts to Improve Quality of Health Physics Prog | |
| 05000293/LER-1978-047, Forwards LER 78-047/03L-0 | Forwards LER 78-047/03L-0 | |
| 05000293/LER-1978-048, Forwards LER 78-048/03L-0 | Forwards LER 78-048/03L-0 | |
| 05000293/LER-1978-048-03, /03L-0 on 781009:reactor Scrammed on a Load Rejection Causing Generator Lockout Relay Trip.Cause Was Excessive Pilot Seat Leakage Keeping Second Stage & Main Valve Open.Relief/Safety Valve Replaced | /03L-0 on 781009:reactor Scrammed on a Load Rejection Causing Generator Lockout Relay Trip.Cause Was Excessive Pilot Seat Leakage Keeping Second Stage & Main Valve Open.Relief/Safety Valve Replaced | |
| 05000293/LER-1978-049, Forwards LER 78-049/03L-0 | Forwards LER 78-049/03L-0 | |
| 05000293/LER-1978-049-03, /03L-0:on 781011,while Performing Surveillance Testing on Diesel Generator B,Generator Output Breaker Tripped Due to Short from One Coil to Stator.Caused by Loose Laminations.Coils Replaced & Test re-run Satisfactorily | /03L-0:on 781011,while Performing Surveillance Testing on Diesel Generator B,Generator Output Breaker Tripped Due to Short from One Coil to Stator.Caused by Loose Laminations.Coils Replaced & Test re-run Satisfactorily | |
| 05000293/LER-1978-050-04, /04T-0 on 781106:Yankee Environ Lab Indicated That 63pGi/kg of CO-60 Existed in Sample Mussel Meat.This Exceeds by 10 Times the Concentration Measured at Marshfield Control Station.Resulted from New Analysis Technique | /04T-0 on 781106:Yankee Environ Lab Indicated That 63pGi/kg of CO-60 Existed in Sample Mussel Meat.This Exceeds by 10 Times the Concentration Measured at Marshfield Control Station.Resulted from New Analysis Technique | |
| 05000293/LER-1978-050, Forwards LER 78-050/04T-0 | Forwards LER 78-050/04T-0 | |
| 05000293/LER-1978-051-01, /01X-0 on 781030: of Operable SRMs Was Reduced Below Minimum Req When SRM a Was Jumpered to Eliminate Problems W/Downscale Rod Block.Caused by Inadvertent Jumpering of Entire a SRM Trip Logic.Procedures Being Rev | /01X-0 on 781030: of Operable SRMs Was Reduced Below Minimum Req When SRM a Was Jumpered to Eliminate Problems W/Downscale Rod Block.Caused by Inadvertent Jumpering of Entire a SRM Trip Logic.Procedures Being Rev | |
| 05000293/LER-1978-051, Forwards LER 78-051/01X-0 | Forwards LER 78-051/01X-0 | |
| 05000293/LER-1978-052, Forwards LER 78-052/03L-0 | Forwards LER 78-052/03L-0 | |
| 05000293/LER-1978-052-03, /03L-0 on 781028:SJAE Offgas Radiat Monitor Readings Were Low Caused by Shut Block Valve to FCV-118. Valve Was Opened.Proper Flow Rate Established.Valve Will Be Properly Identified in Future by Personnel | /03L-0 on 781028:SJAE Offgas Radiat Monitor Readings Were Low Caused by Shut Block Valve to FCV-118. Valve Was Opened.Proper Flow Rate Established.Valve Will Be Properly Identified in Future by Personnel | |
| 05000293/LER-1978-053, Forwards LER 78-053/01T-1 | Forwards LER 78-053/01T-1 | |
| 05000293/LER-1978-053-01, /01T-0 on 781116:during Repair of Fire Hydrant Facing Condenser Retube bldg,shut-off Valve Blew Off Line Causing Local Flooding & Removal of Fire Suppression from Svc.Cause Was Improper Reinstallation at Retube Bldg Constr | /01T-0 on 781116:during Repair of Fire Hydrant Facing Condenser Retube bldg,shut-off Valve Blew Off Line Causing Local Flooding & Removal of Fire Suppression from Svc.Cause Was Improper Reinstallation at Retube Bldg Constr | |
| 05000293/LER-1978-054-03, /03L-0 on 781115:during Test of Reactor Water Level,Level Switches L1S-263-57A&B Observed to Trip at Values Greater than Specified in Tech Specs.Caused by Minor Setpoint Drift | /03L-0 on 781115:during Test of Reactor Water Level,Level Switches L1S-263-57A&B Observed to Trip at Values Greater than Specified in Tech Specs.Caused by Minor Setpoint Drift | |
| 05000293/LER-1978-054, Forwards LER 78-054/03L-0 | Forwards LER 78-054/03L-0 | |
| 05000293/LER-1978-055-03, /03L-0 on 781202:during Control Rod Pattern Change & Scram Test,Control Rod Drives 46-39 & 38-39 Could Not Be Scrammed from Reactor Protection Sys Test & Monitor Panel C916,caused by Scram Pilot Valves Not Bleeding Down | /03L-0 on 781202:during Control Rod Pattern Change & Scram Test,Control Rod Drives 46-39 & 38-39 Could Not Be Scrammed from Reactor Protection Sys Test & Monitor Panel C916,caused by Scram Pilot Valves Not Bleeding Down | |
| 05000293/LER-1978-055, Forwards LER 78-055/03L-0 | Forwards LER 78-055/03L-0 | |
| 05000293/LER-1978-056-03, /03L-0 on 781212:pulling Power Fuse to Diesel Generator Smoke Detector Panel Caused No Alarm in the Main Control Room.Caused by Discrepancy Between Actual Sys Wiring & That Specified by Vendor | /03L-0 on 781212:pulling Power Fuse to Diesel Generator Smoke Detector Panel Caused No Alarm in the Main Control Room.Caused by Discrepancy Between Actual Sys Wiring & That Specified by Vendor | |
| 05000293/LER-1978-056, Forwards LER 78-056/03L-0 | Forwards LER 78-056/03L-0 | |
| 05000293/LER-1978-057-03, /03L-0 on 781230:while Operating in Full Flow Test,Hpci Tripped.Investigation Revealed Low Level in Oil Sump & Overflow Pit Around Turbine Filled W/Oil.Caused by Disconnected Fitting for Discharge Pressure Gage Oil Pump | /03L-0 on 781230:while Operating in Full Flow Test,Hpci Tripped.Investigation Revealed Low Level in Oil Sump & Overflow Pit Around Turbine Filled W/Oil.Caused by Disconnected Fitting for Discharge Pressure Gage Oil Pump | |
| 05000293/LER-1978-057, Forwards LER 78-057/03L-0 | Forwards LER 78-057/03L-0 | |