O PSEG Public Service Electric and Gas Company P.O. Box 168 Hancocks Bridge, New Jersey 08038 Salem Generating Station November 25, 1981 Mr.

R.

C. Eaynes Director of USNRC m.

Office of Inspection and Enforcement k/'

Pegion 1 6) 4 p )y dt, h 'p "?,,

631 Park Avenue s

King of Ftussia, Pennsylvania 19406

'y

/

'%q, S 'Yh

$jq ky p Q'; [L.)

Dear Mr. Haynes:

Q

- Q r2 v

9 LICENSE NO. DPR-70

/,.,

W%y DOCKET NO. 50-272 V.

A

'x,[ h,',lj,.-

REPORTABLE OCCURRENCE 81-106/03L

,L' Pursuant to the requirements of Salem Generating Station Unit No.

1, Technical Specifications, Section 6.9.2, we are submitting Licensee Event Report for Reportable occurrence 81-106/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, Y

M

,4)

H.

J.

Midura General Manager -

Salem Operations CC:

Distribution gb

$;l 8112090082 811125 al PDR ADOCK 05000272 S

PDR 9s2 m n:sw n m

(

Report Number:

81-106/03L Report Date:

11-25-81 Occurrence Date:

10-29-81 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Penetration Fire Barriers - Inoperable.

This report was initiated by Incident Report 81-431.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 97% - Unit Load 1040 MWe DESCRIPTION OF OCCURRENCE:

On October 29, 1981, upon completion of a fire door inspection, it was determined that 14 fire doors did not meet the acceptance criteria.

At 0001 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> they were declared inoperable and Action Statement 3.7.ll.a was entered.

This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The fire doors were in need of mechanical repair.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.7.ll.a requires:

With one or more of the required Fire Barrier Penetrations inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the operability of fire detectors on at least one side of the inoperable fire barrier and establish an hourly fire watch patrol.

Restore the inoperable Fire Barrier Penetration (s) to operable status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a special report to the Commission pursuant to Specification 6.9.2 within the next 30 days.

L

f LER 81-106/03L.

7.

CORRECTIVE ACTION

Because the applicable fire detectors were operable, an hourly fire watch patrol was-established to comply with the. requirement of the Technical Specification.

The fire doors identified were satisfactorily repaired.

Three doors are still~ inoperable due to cable runs and ventilation problems preventing proper closing.

24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> fire watches are being established.for these and any other problem areas.

Design Change Request lEC-1333-has been initiated to improve the present door system.

A supplemental report will be issued

[-

upon its completion.

1 FAILURE DATA:

Penetration Fire Barriers.

Various Parts 1

i Prepared By F.

Dickey

/./,M M General Manager -

Salem Operations 1

SORC Meeting No.81-121 I