05000272/LER-1981-103, Forwards LER 81-103/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 81-103/03L-0.Detailed Event Analysis Encl
ML20033B514
Person / Time
Site: Salem PSEG icon.png
Issue date: 11/18/1981
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20033B515 List:
References
NUDOCS 8112010484
Download: ML20033B514 (3)


LER-1981-103, Forwards LER 81-103/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
2721981103R00 - NRC Website

text

,

O PSEG Public Service Electric and Gas Company P.O. Box 168 Hancocks Bridge, New Jersey 08038 Salem Generating Station November 18, 1981

,7,

$[s

\\

l Cl[

Mr.

R.

C.

Haynes g

0 ggy 1Q Director of.USNRC Office of Inspection and Enforcement 3

Region 1

( '-

631 Park Avenue

\\,8'

//

N King of Prussia, Pennsylvania 19406 q,.

s

Dear Mr. Haynes:

LICENSE NO. DPR-70 I

DOCKET NO. 50-272 REPORTABLE OCCURRENCE 81-103/03L Pursuant to the requirements of Salem Generating Station Unit No. 1, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable occurrence 81-103/02L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, l

H. J. Midura General Manager -

Salem Operations i

CC:

Distribution

(

8112010484 811118 6JA PDR ADOCK 05000272 f

j S

PDR S

j The Energy Pi ople 9s2ie9 fum it ao

Report Number:

81-103/03L Report Date:

11-18-81 Occurrence Date:

10-25-81 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancocks Bridge,-New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Intermediate Range Detector - Inoperable.

This report was initiated by Incident Report 81-423.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 98% - Unit Load 1040 MWe DESCRIPTION OF OCCURRENCE:

At 1710 hours0.0198 days <br />0.475 hours <br />0.00283 weeks <br />6.50655e-4 months <br />, October 25, 1981, the Control Operator noticed that the Intermediate Range Detector N-36 had failed.

The level trip switch for this channel was placed in the bypass position, and Action Statement 3.3.1.3.c was entered.

This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The cause was a failure of the detector high voltage power supply.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.3.1.3.c requires:

With the number of channels operable one less than required by the minimum channels operable require-ment and with the thermal power level above 5% of rated thermal power, power operation may continue.

CORRECTIVE ACTION

High voltage power supply was replaced and tested satisfactorily, and at 2115 hours0.0245 days <br />0.588 hours <br />0.0035 weeks <br />8.047575e-4 months <br />, October 27, 1981, Action Statement 3.3.1.3.c was terminated.

LER 81-103/03L -

FAILURE DATA:

Westinghouse High Voltage Power Supply Model No. 910057-54 Prepared By K. Whitcomb